| 2018-02-15 06:35:14 | DENIED |
| | 1. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE |
| | PROPOSED BACKFLOW PREVENTION DEVICE. YOU CAN DO A |
| | SKETCH OR USE PROPERTY APPRAISER WEB SITE HTTP://WWW.CO |
| | .PALM-BEACH.FL.US/PAPA/ASPS/PROPERTYDETAIL/STRUCTURALDE |
| | TAIL.ASPX?ENTITY_ID=74434334110020151&OWNER_NAME=ORTIZ+ |
| | RUIZ+ADRIAN+C . TELL US WHERE YOUR WATER METER IS AND |
| | WHERE THE BACKFLOW WILL BE PLACED. |
| | 2. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR |
| | THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF |
| | THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK |
| | SECTION ON THE PERMIT APPLICATION. |
| | 3. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE. |
| | 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS |
| | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY |
| | OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT |
| | OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT |
| | 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE |
| | PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY |
| | REQUIREMENTS. |
| | 5. THE CITY OF WEST PALM BEACH UTILITIES REQUIRES THE |
| | WATER SUPPLY PIPING BETWEEN THE METER AND THE BACKFLOW |
| | PREVENTION DEVICE TO BE A MINIMUM OF TYPE K COPPER. PVC |
| | PIPING IS NOT PERMITTED. EXISTING WATER SUPPLIES NOT |
| | MEETING THESE CRITERIA MUST BE UPGRADED. PLEASE CALL |
| | 561- 822-2240 FOR FURTHER INFORMATION. |
| | 6. ALL DEVICES MUST BE TESTED AND CERTIFIED BY THE CITY |
| | OF WEST PALM BEACH UTILITIES DEPARTMENT PRIOR TO THE |
| | FINAL INSPECTIONS BY THE BUILDING DEPARTMENT. PLEASE |
| | CONTACT THE CITY OF WEST PALM BEACH PUBLIC UTILITIES |
| | CENTRAL OPERATIONS AT 561-822-2210 TO ARRANGE FOR THE |
| | UTILITIES DEPARTMENT TO CERTIFY THE DEVICE. |
| | |
| | LUIS CRESPO |
| | PLUMBING INSPECTOR / PLUMBING PLAN EXAMINER |
| | CITY OF WEST PALM BEACH |
| | TELEPHONE: 561-701-6437 |
| | [email protected] |
| | |