Plan Review Details - Permit 18020521
Plan Review Stops For Permit 18020521
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-09-11 Cont ID  
Sent By jgomez Date 2018-09-11 Time 18:32 Rev Time 0.00
Received By jgomez Date 2018-09-11 Time 15:05 Sent To FIRE
Notes
2018-09-11 15:57:58BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR. NOTE: PRODUCT APPROVAL TO INCLUDE
 INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON
 PLANS.
 B) SLIDING WINDOW. NOTE: PRODUCT APPROVAL TO INCLUDE
 INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON
 PLANS.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NOTE:
 MET WITH ROBERT BROWN AND SAMANTHA HILL. OK TO USE
 BUSINESS GROUP CLASSIFICATION FOR FOOD PROCESSING
 ESTABLISHMENT SINCE THE FOOD PROCESSING AREA IS LESS
 THAN 2500 S.F. THE OTHER AREA IS OFFICE SPACE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-08-20 Cont ID  
Sent By jgomez Date 2018-08-20 Time 17:33 Rev Time 0.00
Received By jgomez Date 2018-08-17 Time 18:57 Sent To  
Notes
2018-08-17 19:13:55CHANGE OF OCCUPANCY, THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 ORIGINAL COMMENT:
 1-CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY
 CONSERVATION CODE.
  
 RESPONSE:
 (A) ENERGY CALCULATIONS SUBMITTED WERE CHANGED. THE NEW
 FORM NEEDS TO BE SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD ALSO AS REQUIRED BY SEC. C103.1.1.1.2 FBC-ENERGY
 CONSERVATION. NOTE: ENVELOPE INFORMATION SHOWN ON THE
 ENERGY CALCULATIONS AND PLANS DON'T MATCH. SEE TYPE OF
 WALLS FRAMING, CEILING INFORMATION INCLUDING
 INSULATION, ETC. CLEARLY ARCHITECT AND MECHANICAL
 ENGINEER TO COORDINATE INFORMATION TO AVOID
 CONFLICTS/DELAYS.
  
 (B)THE BOXES FROM THE MANDATORY REQUIREMENTS THAT ARE
 ASSIGNED TO THE PLANS REVIEWER AND INSPECTORS WERE
 CHECKED. ENGINEER CAN NOT CHECK THESE BOXES. REVISE AS
 REQUIRED.
  
 (C) THE OWNER OR OWNER'S AUTHORIZED AGENT NEED TO
 CERTIFY THE FORM AFTER CALCULATIONS ARE REVISED. SEC.
 C103.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 2-IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 ORIGINAL COMMENT:
 3- LIFE SAFETY PLAN NOT PROVIDED.
  
 RESPONSE:
 LIFE SAFETY PLAN SHEET A-3 SUBMITTED. :
 (A)CLARIFY WHY PROVIDING THE "MEANS OF EGRESS"
 INFORMATION SHOWN IN THE LIFE SAFETY PLAN. IT DOESN'T
 SEEM TO APPLY TO THIS PROJECT. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 (B)THIS IS A MIXED OCCUPANCY. FACTORY AND BUSINESS
 (OFFICE/FOYER/RECEPTION AREA). PROVIDE OCCUPANCY LOAD
 CALCULATIONS FOR THE FACTORY AREA AND LOAD CALCULATIONS
 FOR THE OFFICE AREA. THESE ARE TWO DIFFERENT
 CALCULATION'S. SEE TABLE 1004.1.2 FBC AND REVISE AS
 REQUIRED.
  
 (C) INFORMATION SHOWN AT THE BOTTOM OF SHEET A-3 IS
 INCORRECT. THERE IS NOT COMMON PATH OF EGRESS TABLE
 1014.3 AND NUMBER OF EXITS REQUIRED TABLE 1018 IN THE
 2017 FBC. SEE CHAPTER 10 OF FBC-2017 AND REVISE AS
 REQUIRED.
  
 (D)FIRE EXTINGUISHER INFORMATION SPECIFIED IN THE
 SYMBOL LEGEND DOESN'T MATCH FIRE EXTINGUISHER
 INFORMATION SHOWN AT THE BOTTOM OF SHEET A-3 AND
 INFORMATION SHOWN ON THE FLOOR PLAN. REVISE AS
 REQUIRED. SEC. 906 FBC.
  
 (E) THE SWING DIRECTION OF THE EXIT DOOR LEADING TO THE
 FOYER AREA FROM THE FACTORY AREA DOESN'T MATCH SWING
 DIRECTION SHOWN ON THE FLOOR PLAN ON SHEET A-1. REVISE
 AS REQUIRED TO MATCH. SEC. 1010.1.2.1 FBC.
  
 ORIGINAL COMMENT:
 4- EXTERIOR WALLS REQUIRE A FIRE RESISTANCE RATING OF 2
 HOURS AS REQUIRED BY SEC. 1012.6 FBC-EXISTING BUILDING
 AND TABLE 602 FBC. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE 2 HOUR FIRE
 RESISTANCE RATING.
 NOTE: CALCULATED FIRE RESISTANCE SEC. 722 FBC MAY BE
 USED BASED ON THE MATERIALS USED.
  
 RESPONSE:
 CONCRETE BLOCK DETAIL 1/A-3 ON SHEET A-2 IS FOR "NON
 RATED EXISTING MASONRY WALL". THE CHANGE OF OCCUPANCY
 FROM BUSINESS TO FACTORY REQUIRES A 2 HOUR FIRE
 RESISTANCE RATING OF THE WALL. PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR 2 HR FIRE RATED ASSEMBLY. NOTES:
 (1)ASSEMBLY SHALL BE RATED FOR EXPOSURE TO FIRE FROM
 BOTH SIDES.
  
 ORIGINAL COMMENT:
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 INTERIOR PARTITIONS. SPECIFY ALL FRAMING MEMBERS ,
 SPACING, CONNECTORS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 INTERIOR PARTITIONS ON SHEET A-2 NEED TO BE COORDINATED
 WITH FLOOR PLAN ON SHEET A-1. UL DES#U305 SPECIFIED ON
 DETAIL 2/A-3 IS NOT FOR 2 HOUR RATED PARTITION. ALSO
 WALL TYPES (WOOD OR METAL?) NEED TO BE COORDINATED WITH
 WALL TYPES SPECIFIED ON FLOOR KEY NOTES ON SHEET A-1.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 NEW COMMENTS:
 6- SHEET A-1:
 A) THE FLOOR KEY NOTES AND THE NOTES KEYED ON THE FLOOR
 PLAN NEED TO BE COORDINATED. FOR EXAMPLE KEY NOTE # 18
 IS FOR NEW WALK IN COOLER BUT IT IS POINTING TO A FIRE
 EXTINGUISHER. CORRELATE ALL KEY NOTES TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)REVISE PROJECT DATA: THE AREA ALLOWED FOR AN F-1
 OCCUPANCY FOR A TYPE VB BUILDING IS 8,500 NOT 13,000.
 SEE TABLE 506.2 FBC AND REVISE AS REQUIRED.
  
 C) THE DOOR SCHEDULE AND DOORS KEYED ON THE FLOOR PLAN
 DON'T MATCH. ALSO, COORDINATE WITH THE FLOOR KEY NOTES.
 CORRELATE ALL THE INFORMATION TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 D)PROVIDE DIMENSIONS FOR REAR TOILET ROOM. SEC. 603
 FBC-ACCESSIBILITY.
  
 E) FLOOR PLAN IS NOT CLEAR. THERE IS A PARTITION
 OVERLAPPING THE FOYER AND OFFICE AREA. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) REVISE THE WIND DESIGN NOTES:
 (1)THE ASCE-7 THAT IS REFERENCED IN THE 2017 FBC IS THE
 2010 EDITION NOT 02. REVISE AS REQUIRED. CHAPTER 553
 F.S.
 (2) THE WIND EXPOSURE IS "C" NOT "B". SEE STRUCTURAL
 DRAWINGS AND REVISE AS REQUIRED. SEC. 1609.4 FBC.
  
 G) LAST NOTE AT THE BOTTOM RIGHT OF SHEET A-1
 REFERENCES "THIS RESIDENCE". THIS DOESN'T APPLY TO THIS
 PROJECT. REVISE AS REQUIRED. SEC. 301.1 FBC.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) ENTRY DOOR. NOTE: PRODUCT APPROVAL TO INCLUDE
 INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON
 PLANS.
  
 B) SLIDING WINDOW. NOTE: PRODUCT APPROVAL TO INCLUDE
 INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON
 PLANS.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 NOTE: ADDITIONAL COMMENTS MAY ARISE BASED ON THE
 INFORMATION SUBMITTED BY THE DESIGN PROFESSIONAL TO
 ADDRESS ALL THE COMMENTS.
  
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-08 Cont ID  
Sent By jgomez Date 2018-05-07 Time 19:00 Rev Time 0.00
Received By jgomez Date 2018-05-07 Time 17:36 Sent To I
Notes
2018-05-08 17:44:52CHANGE OF OCCUPANCY, SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 1. COMPLIED.
  
 2. ORIGINAL COMMENT:
 PROVIDE THE BUILDING CONSTRUCTION TYPE AND IF IT IS
 SPRINKLERED OR UNSPRINKLERED FBC 602, FBC 107.2.1
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). TYPE OF CONSTRUCTION
 SPECIFIED ON SHEET S-1 IS IN CORRECT. THERE IS NOT
 CONSTRUCTION TYPE VI. SEE SEC. 602 FBC-BUILDING AND
 REVISE AS REQUIRED. ALSO, CLEARLY SPECIFY IF SPECIFIED
 CONSTRUCTION TYPE IS A OR B. AND, SPECIFY IF THE
 BUILDING IS SPRINKLERED OR NOT.
  
 3- ORIGINAL COMMENT:
 THE PREVIOUS OCCUPANCY ON RECORD IS FOR AUTO SALES AND
 SERVICE. THIS IS A CHANGE OF OCCUPANCY. SHOW ON THE
 PLANS THE OCCUPANCY CLASSIFICATION AND USE. SEE ALSO
 FBC 302 AND 306.2.
  
 A) EXISTING BUILDING CODE 506.1 SCOPE.
 CHANGE OF OCCUPANCY PROVISIONS APPLY WHERE THE ACTIVITY
 IS CLASSIFIED AS A CHANGE OF OCCUPANCY AS DEFINED IN
 CHAPTER 2.
  
 CHANGE OF OCCUPANCY A CHANGE IN THE USE OF THE BUILDING
 OR A PORTION OF A BUILDING. A CHANGE OF OCCUPANCY SHALL
 INCLUDE ANY CHANGE OF OCCUPANCY CLASSIFICATION, ANY
 CHANGE FROM ONE GROUP TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION OR ANY CHANGE IN USE WITHIN A
 GROUP FOR A SPECIFIC OCCUPANCY CLASSIFICATION.
  
 EXISTING BUILDING CODE 506.2 APPLICATION. CHANGES OF
 OCCUPANCY SHALL COMPLY WITH THE PROVISIONS OF CHAPTER
 10.
 THE PROVISIONS OF THE FLORIDA BUILDING CODE, EXISTING
 BUILDING SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION AND RELOCATION OF EXISTING
 BUILDINGS.
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). PLANS DON'T PROVIDE
 INFORMATION REGARDING THE CHANGE OF OCCUPANCY. NEED TO
 BE CLEAR ON THE PROPOSED USE. PLAN REVIEW CAN NOT BE
 PROPERLY PERFORMED IF THE PROPOSED USE IS NOT CLEARLY
 DEFINED. PLANS SHOW EVERYTHING AS EXISTING. THERE ARE
 NO CITY RECORDS REGARDING THE CHANGE OF USE. EVERYTHING
 NEEDS TO COMPLY FOR THE PROPOSED USE. PLANS NEED TO BE
 CLEAR ON THE PROPOSED USE AND NEED TO SHOW EVERYTHING
 AS PROPOSED.
  
  
 B)ORIGINAL COMMENT:
 CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY
 CONSERVATION CODE.
  
 RESPONSE:
 ENERGY CALCULATIONS FORM C402-2017 SUBMITTED:
 (1)THE OWNER OR OWNER'S AUTHORIZED AGENT NEED TO
 CERTIFY AT THE BOTTOM OF FORM AS REQUIRED BY SEC.
 C103.1.1.2 FBC-ENERGY CONSERVATION.
  
 (2) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
 SPECIFY OCCUPANCY TYPE; PROVIDE BUILDER'S NAME; PROVIDE
 OWNER'S NAME.
  
  
 4- FRAMING.
  
 ORIGINAL COMMENT:
 A) HEADER AND JACK STUDS NOT SHOWN. SHOW COMPLIANCE
 WITH TABLE 2308.4.1.1(1)
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). JACK STUDS ARE NOT SHOWN.
 ONLY THE KING STUDS ARE SHOWN. CRIPPLE STUDS SPACING
 SHOWN ABOVE HEADER AND BELOW WINDOW SILL ARE NOT DRAWN
 TO SCALE. CLARIFY HEADER SIZE (5)2X5 ?. FRAMING OF NEW
 2X8 STUDS TO THE EXISTING KNEE WALL IS NOT CLEAR. HOW
 ARE THE 2X8 STUDS ATTACHED TO THE EXISTING KNEE WALL?.
 WHAT IS THE KNEE WALL CONSTRUCTED OF?. SEC. 1609.1
 FBC-BUILDING.
  
 B) COMPLIED.
  
 5- COMPLIED.
  
 6. ORIGINAL COMMENT:
 PROVIDE PRODUCT APPROVALS FOR AIR INTAKE VENT.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 RESPONSE:
 PROVIDE 2 COPIES. ONLY ONE WAS PROVIDED. AND, NEED THE
 APPROVAL OF THE DESIGNER OF RECORD. NOTE: ENGINEER TO
 PLEASE PLACE THE REVIEW STAMP ON THE FRONT OF THE COVER
 PAGE OR ANY OTHER FRONT PAGE NOT ON THE BACK. THIS IS
 REQUIRED FOR PROPER RECORDS RETENTION. STAMPS ON THE
 BACK OF THE PAGE DON'T GET SCANNED.
  
 7. COMPLIED.
  
 8. ORIGINAL COMMENT:
 PERMIT VALUE IS TOO LOW.
  
 RESPONSE:
 VALUE WAS UPDATED TO $42,000 STILL TOO LOW. VALUE TO
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT (EVEN IF PLANS
 CALL FOR EXISTING EQUIPMENT. IT WAS NEVER PERMITTED),
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES.
  
 9. IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 10. OTHER ITEMS NOT PROVIDE IN THE PLAN.
 ORIGINAL COMMENT:
 A. COMPLIANCE WITH FLORIDA ACCESSIBILITY CODE.
  
 RESPONSE:
 MAIN ENTRANCE TO THE BUILDING AND ENTRY AREA RESTROOM
 NEED TO COMPLY WITH THE FLORIDA ACCESSIBILITY CODE
 ALSO. DOORS NEED TO COMPLY WITH THE MANEUVERING
 REQUIREMENTS AND RESTROOMS NEED TO COMPLY WITH DOORS
 MANEUVERING AND FIXTURES CLEARANCES, ETC.
 SEC. 202.4 FBC ACCESSIBILITY. SEC. 404 FBC
 ACCESSIBILITY. SEC. 603 AND 604 FBC ACCESSIBILITY.
 NOTE; THERE ARE NO CITY RECORDS FOR ANY WORK DONE BY
 THE ENTRY AREA. THE LAST PERMIT (ELECTRICAL PERMIT
 03061436 TO INSTALL 2 EMERGENCY LIGHTS) SHOWING THE
 INTERIOR LAYOUT ONLY SHOWS AN OFFICE AT THE FRONT LEFT
 SIDE OF THE BUILDING. IT IS UNKNOWN WHEN THE ENTRY AREA
 WAS BUILT.
  
  
 ORIGINAL COMMENT:
 B. LIFE SAFETY PLAN NOT PROVIDED.
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). NO SAFETY PLAN WAS
 SUBMITTED. PROVIDE PLAN SHOWING ALL THE PROPOSED
 EQUIPMENT (REMEMBER: PROPOSED USE IS NOT CLARIFIED).
 CLEARLY DEFINED ALL ROOM AREAS. PROVIDE COMPLETE
 EQUIPMENT, TABLES, FURNITURE REQUIRED FOR THE PROPOSED
 USE (SEC. 1001.4 FBC). PROVIDE OCCUPANT LOAD (SEC. 1004
 FBC), SHOW EGRESS PATH AND TRAVEL DISTANCES, DOORS
 SIZES, EXIT SIGNS, FIRE EXTINGUISHERS (SEC. 906 FBC),
 ETC.
  
 ORIGINAL COMMENT:
 C. PROVIDE ADDITIONAL INFORMATION REGARDING THE USE OF
 THIS SPACE SEE ALSO FBC 304.1 FOOD PROCESSING
 FACILITIES ESTABLISHMENTS AND COMMERCIAL KITCHENS.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS.
 SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA.
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). NOT ADDRESSED.
  
 NEW COMMENTS:
 11- FLOOR PLANS SHOW EXISTING WALL EXHAUST FANS ON THE
 NORTH AND SOUTH SIDE. OPENINGS ARE NOT ALLOWED. SEE
 SEC. 705.8 FBC. AND REVISE AS REQUIRED.
  
 12- EXTERIOR WALLS REQUIRE A FIRE RESISTANCE RATING OF
 2 HOURS AS REQUIRED BY SEC. 1012.6 FBC-EXISTING
 BUILDING AND TABLE 602 FBC. PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE 2 HOUR
 FIRE RESISTANCE RATING.
  
 13- SHEET S-2:
 A)CLARIFY WHY STRUCTURAL NOTE #1 SPECIFIES CATEGORY
 III, WHILE THE WIND LOADS AT THE BOTTOM OF NEXT COLUMN
 SPECIFIES CATEGORY II. CLARIFY AS REQUIRED. IS THIS THE
 RISK CATEGORY?. IF SO, THEN SEE TABLE 1604.5 FBC AND
 REVISE AS REQUIRED.
  
 B) WIND LOADS INFORMATION: CLARIFY WHY ITEM "G"
 COMPONENT & CLADDING HEIGHT IS DIFFERENT THAN ITEM "H"
 MRH?. SEE BUILDING FOR CORRECT MEAN ROOF HEIGHT AND
 REVISE AS REQUIRED, INCLUDING THE DESIGN PRESSURES.
 SEC. 1609 FBC.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 INTERIOR PARTITIONS. SPECIFY ALL FRAMING MEMBERS ,
 SPACING, CONNECTORS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: ADDITIONAL COMMENTS MAY ARISE BASED ON THE
 INFORMATION SUBMITTED BY THE DESIGN PROFESSIONAL TO
 ADDRESS ALL THE COMMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By jgomez Date 2018-02-16 Time 14:19 Rev Time 0.00
Received By aclange Date 2018-02-15 Time 13:17 Sent To  
Notes
2018-02-16 14:17:50****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL
 BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH
 EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY
 CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE
 REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE.
  
 2. PROVIDE THE BUILDING CONSTRUCTION TYPE AND IF IT IS
 SPRINKLERED OR UNSPRINKLERED FBC 602, FBC 107.2.1
  
 3. THE PREVIOUS OCCUPANCY ON RECORD IS FOR AUTO SALES
 AND SERVICE. THIS IS A CHANGE OF OCCUPANCY. SHOW ON THE
 PLANS THE OCCUPANCY CLASSIFICATION AND USE. SEE ALSO
 FBC 302 AND 306.2.
  
 A) EXISTING BUILDING CODE 506.1 SCOPE.
 CHANGE OF OCCUPANCY PROVISIONS APPLY WHERE THE ACTIVITY
 IS CLASSIFIED AS A CHANGE OF OCCUPANCY AS DEFINED IN
 CHAPTER 2.
  
 CHANGE OF OCCUPANCY A CHANGE IN THE USE OF THE BUILDING
 OR A PORTION OF A BUILDING. A CHANGE OF OCCUPANCY SHALL
 INCLUDE ANY CHANGE OF OCCUPANCY CLASSIFICATION, ANY
 CHANGE FROM ONE GROUP TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION OR ANY CHANGE IN USE WITHIN A
 GROUP FOR A SPECIFIC OCCUPANCY CLASSIFICATION.
  
 EXISTING BUILDING CODE 506.2 APPLICATION. CHANGES OF
 OCCUPANCY SHALL COMPLY WITH THE PROVISIONS OF CHAPTER
 10.
 THE PROVISIONS OF THE FLORIDA BUILDING CODE, EXISTING
 BUILDING SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION AND RELOCATION OF EXISTING
 BUILDINGS.
  
 B) CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY
 CONSERVATION CODE.
  
 4. FRAMING.
  
 A) HEADER AND JACK STUDS NOT SHOWN. SHOW COMPLIANCE
 WITH TABLE 2308.4.1.1(1)
  
 B) SHOW FRAMING DETAIL FOR LOUVER OPENING AT REAR OF
 BUILDING.
  
 5. PROVIDE TWO LAYERS OF A WATER RESISTIVE BARRIER OVER
 WALL SHEATHING.
  
 FBC 2510.6 WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION 1404.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF WATER-RESISTIVE BARRIER
 COMPLYING WITH ASTM E2556, TYPE I. THE INDIVIDUAL
 LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH THAT EACH
 LAYER PROVIDES A SEPARATE CONTINUOUS PLANE AND ANY
 FLASHING (INSTALLED IN ACCORDANCE WITH SECTION 1405.4)
 INTENDED TO DRAIN TO THE WATER-RESISTIVE BARRIER IS
 DIRECTED BETWEEN THE LAYERS.
  
 6. PROVIDE PRODUCT APPROVALS FOR AIR INTAKE VENT.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 7. PROVIDE SPECIFICATIONS FOR OVENS. FBC 107.2.1
  
 8. PERMIT VALUE IS TOO LOW.
  
 VALUATION
  
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 9. IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 10. OTHER ITEMS NOT PROVIDE IN THE PLAN.
  
 A. COMPLIANCE WITH FLORIDA ACCESSIBILITY CODE.
  
 B. LIFE SAFETY PLAN NOT PROVIDED.
  
 C. PROVIDE ADDITIONAL INFORMATION REGARDING THE USE OF
 THIS SPACE SEE ALSO FBC 304.1 FOOD PROCESSING
 FACILITIES ESTABLISHMENTS AND COMMERCIAL KITCHENS.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS.
 SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-08-09 Cont ID  
Sent By ppetty Date 2018-08-09 Time 10:58 Rev Time 0.00
Received By ppetty Date 2018-08-09 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-01 Cont ID  
Sent By jpearson Date 2018-05-01 Time 16:01 Rev Time 0.00
Received By jpearson Date 2018-05-01 Time 15:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-18 Cont ID  
Sent By jpearson Date 2018-02-18 Time 10:11 Rev Time 0.00
Received By jpearson Date 2018-02-18 Time 10:11 Sent To  
Notes
2018-02-18 10:11:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. ESTIMATED SHORT CIRCUIT CALCULATION IS NOT
 ACCEPTABLE. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 FOR EACH PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE SHOW WINDOW OUTLET FOR NEW WINDOW. NEC
 210.62
 5. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC EC 405.2.4
 6. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 7. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 8. ALL RECEPTACLES IN KITCHEN AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8(B)(2)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-09-14 Cont ID  
Sent By scaldero Date 2018-09-14 Time 11:33 Rev Time 0.00
Received By scaldero Date 2018-09-14 Time 11:30 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-25 Cont ID  
Sent By scaldero Date 2018-07-25 Time 11:15 Rev Time 0.00
Received By scaldero Date 2018-07-25 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-23 Cont ID  
Sent By scaldero Date 2018-04-23 Time 11:56 Rev Time 0.00
Received By scaldero Date 2018-04-23 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By scaldero Date 2018-02-15 Time 11:55 Rev Time 0.00
Received By scaldero Date 2018-02-15 Time 11:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 16:25 Rev Time 0.00
Received By gjohnson Date 2018-08-15 Time 16:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 12:49 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 12:49 Sent To  
Notes
2018-05-02 13:00:263RD REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHALL COMPLY WITH GAS COMMENTS ON 2ND REVIEW DONE BY
 TIM LARGE.
  
 2. THERE ARE NO RECORDS OF THE EXISTING EXHAUST FANS ON
 THE SOUTH SIDE OF THE BUILDING AN INSPECTOR WAS SENT TO
 PROPERTY AND REPORTED THAT THE EXHAUST FANS LOOKED NEW
 AND THIS BEING A CHANGE OF OCCUPANCY THEY WILL NEED TO
 COMPLY WITH FBC TABLE 705.8 WHICH STATES THERE ARE NO
 OPENINGS ALLOWED IN AN EXTERIOR WALL THAT IS LESS THAN
 3' FROM THE PROPERTY LINE. PROVIDE SURVEY SHOWING THE
 SET BACK OF THE BUILDING FROM THE PROPERTY LINE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-20 Cont ID  
Sent By tklarge Date 2018-03-20 Time 12:40 Rev Time 0.00
Received By tklarge Date 2018-03-20 Time 12:37 Sent To  
Notes
2018-03-20 12:40:371) THE SUBMITTED GAS PLAN IS A COPY OF A SIGNED AND
 SEALED PLAN BY AN ENGINEER.PLANS BEARING AND ENGINEER'S
 TITLE BLOCK SHALL ALSO HAVE AN ORIGINAL SIGNATURE AND
 SEAL PER THE FL. ADMIN. CODE 61G15-23.001. SUBMIT TWO
 COPIES OF THE GAS PLAN BEARING THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER.
 2) SHOW THE LOCATION OF THE METAL LOUVERS THAT ARE
 BEING INSTALLED FOR THE COMBUSTION AIR. THE LOUVERS
 CANNOT BE LOCATED IN AN EXTERIOR WALL THAT IS FIRE
 RATED AS THE FIRE RATING OF THE WALL MUST BE
 MAINTAINED.
 3) THE LOUVERS ARE NOT PERMITTED IN AN EXTERIOR WALL
 WITH A FIRE SEPARATION DISTANCE OF LESS THAN 3 FEET
 PERR 2017 FBC-BUILDING TABLE 705.8.NOTE THE TYPE OF
 CONSTRUCTION OF THE BUILDING ON THE PLANS AND WHETHER
 OR NOT THE BUILDING IS SPRINKLERED AS LISTED IN TABLE
 705.8 OF 2017 FBC-BUILDING.SUBMIT ALL REQUIRED
 INFORMATION. SUBMIT A SITE PLAN SHOWING THE DISTANCE OF
 ALL EXTERIOR WALLS TO ADJACENT PROPERTY LINES. WPB
 AMEND. TO FBC SEC.107.2.1.
 4) SHOW THE SIZE OF THE LOUVER(S) ON THE PLANS.
 5) THIS PLAN SHALL BE TAKEN TO THE ENGINEER OF RECORD
 TO BE SIGNED AND SEALED AND SUBMITTED AS CORRECTIONS
 ALONG WITH ALL OTHER CORRECTIONS UNDER THE MASTER
 PERMIT NUMBER 18020521. THIS GAS PERMIT CANNOT BE
 ISSUED UNTIL THE MMASTER PERMIT HAS BEEN APPROVED.
 6) COPIES OF EQUIPMENT SPECIFICATIONS HAVE BEEN
 SUBMITTED FOR TWO DIFFERENT PIECES OF EQUIPMENT BY TWO
 DIFFERENT MANUFACTURERS. THE PLANS SHOW A ROTATING RACK
 OVEN BUT SPECS HAVE ALSO BEEN PROVIDED FOR A DOUBLE
 RACK OVEN. WHICH ONE IS BEING INSTALLED? CLARIFY.
  
 NOTE: THIS GAS REVIEW STEP WAS INITIALLY DONE UNDER
 PERMIT APPLICATION #18020012 BY T.LARGE. I HAVE ADDED
 THIS GAS REVIEW BECAUSE THE GAS COMMENTS NEED TO BE
 ADDRESSED UNDER BOTH PERMIT REVIEWS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By gjohnson Date 2018-02-28 Time 12:17 Rev Time 0.00
Received By gjohnson Date 2018-02-28 Time 12:17 Sent To  
Notes
2018-02-28 12:24:421ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE. PER FBC FG 408.4
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL
 GAS CODE SEC. 502 THRU 505.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-09-24 Cont ID  
Sent By shill Date 2018-09-24 Time 14:54 Rev Time 0.00
Received By shill Date 2018-09-20 Time 12:17 Sent To  
Notes
2018-09-21 12:17:53RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-14 Cont ID  
Sent By cpuell Date 2018-09-14 Time 13:27 Rev Time 0.00
Received By cpuell Date 2018-09-11 Time 15:05 Sent To  
Notes
2018-09-11 15:16:07EDDIE (OWNER) SUBMITTED NEW DRAWINGS A1, A2 AND A3.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-20 Cont ID  
Sent By jgomez Date 2018-08-20 Time 17:46 Rev Time 0.00
Received By jgomez Date 2018-07-16 Time 10:03 Sent To I
Notes
2018-07-18 10:03:39B07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-08 Cont ID  
Sent By jgomez Date 2018-05-08 Time 17:45 Rev Time 0.00
Received By jgomez Date 2018-04-18 Time 10:33 Sent To  
Notes
2018-04-19 10:33:47B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-08 Cont ID  
Sent By ajones Date 2018-03-08 Time 17:05 Rev Time 0.00
Received By ajones Date 2018-02-01 Time 09:50 Sent To  
Notes
2018-02-14 09:50:45B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2018-09-24 Cont ID  
Sent By shill Date 2018-09-24 Time 14:53 Rev Time 0.00
Received By shill Date 2018-09-24 Time 14:53 Sent To  
Notes
2018-09-24 14:54:05NO FEES DUE, PLAN STAMPED
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-08-20 Cont ID  
Sent By jgomez Date 2018-08-20 Time 17:37 Rev Time 0.00
Received By jgomez Date 2018-08-20 Time 17:37 Sent To  
Notes
2018-08-20 17:37:54IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-05-08 Cont ID  
Sent By jgomez Date 2018-05-08 Time 07:31 Rev Time 0.00
Received By jgomez Date 2018-05-08 Time 07:31 Sent To  
Notes
2018-05-08 07:31:27IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By aclange Date 2018-02-16 Time 10:24 Rev Time 0.00
Received By aclange Date 2018-02-16 Time 10:24 Sent To  
Notes
2018-02-16 10:24:23IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-09-05 Cont ID  
Sent By ccole Date 2018-08-22 Time 11:27 Rev Time 0.00
Received By ccole Date 2018-07-30 Time 09:32 Sent To  
Notes
2018-07-30 11:38:53MECHANICAL PROVISOS:
  
 1) PER BAXTER OVEN SPECIFICATIONS- "A FACTORY
 TECHNICIAN OR FACTORY AUTHORIZED INSTALLATION
 TECHNICIAN MUST SUPERVISE AND APPROVE ANY
 INSTALLATION."
  
 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE OVENS SHALL BE ONISTE AT TIME OF
 INSTALLATION.
  
 3) ENGINEERING FOR TIE-DOWN OF THE ROOF VENT SHALL BE
 ONISTE AT TIME OF INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-02 Cont ID  
Sent By ccole Date 2018-04-27 Time 15:06 Rev Time 0.00
Received By ccole Date 2018-04-27 Time 15:06 Sent To  
Notes
2018-05-02 13:30:512ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18020521
 5/2/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE EXHAUST FANS IN THE WALL THAT ARE LABELED AS
 EXISTING MAY HAVE BEEN INSTALLED WITHOUT A PERMIT, AND
 ALSO MAY NOT BE ALLOWED BY CODE DUE TO THEIR RESPECTIVE
 CLEARANCE DISTANCES TO THE ADJOINING PROPERTY LINES.
 THE MECHANICAL APPROVAL FOR THE PROPOSED PLANS ARE ON
 HOLD PENDING RESOLUTION OF THE ISSUE. PLEASE SEE THE
 BUILDING AND PLUMBING RVIEW COMMENTS.
  
 2) THE COMBUSTION AIR CALCULATIONS USING "FAN ASSISTED
 APPLIANCES" DO NOT APPEAR APPLICAGBLE TO THE OVENS
 WHICH DO NOT APPEAR TO HAVE FANS. PLEASE PROVIDE
 FURTHER INFORMATION IN THE FORM OF A PRODUCT DATA SHEET
 FOR THE OVENS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By ccole Date 2018-02-16 Time 17:12 Rev Time 0.00
Received By ccole Date 2018-02-16 Time 17:12 Sent To  
Notes
2018-02-16 17:34:191ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES.
 PERMIT #18020521
 2/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROPOSED PROJECT HAS BEEN DETERMINED TO BE A
 "CHANGE OF OCCUPANCY" AS DEFINED IN SECTION 202 FBC-17
 EXISTING BUILDING CODE. PLEASE REFER TO BUILDING REVIEW
 COMMENTS FOR FURTHER INFORMATION AND REQUIRED DESIGN
 CRITERIA UPDATES.
  
 2) REFER TO SECTION C505.1 FBC-17 ENERGY CONSERVATION
 AND SUBMIT AN ENERGY COMPLIANCE REPORT IN ACCORDANCE
 WITH SECTION C101.5.1.
  
 3) SHEET M-1: THE LARGE OPEN SPACE WHERE THE OVENS ARE
 SHOWN APPEARS TO BE A KITCHEN. PLEASE IDENTIFY AND
 INCLUDE THIS AREA IN THE MINIMUM VENTILATION
 CALCULATIONS AS REQUIRED IN TABLE 403.1.1,
  
 4) M-1: PROVIDE EQUIPMENT SCHEDULES FOR THE OVENS AND
 EXHAUST FLUES AND SUBMIT MANUFACTURER'S SPECIFICATIONS.
 PROVIDE MAKEUP AIR CALCULATIONS FOR THE OVENS AND/OR
 COMBUSTION AIR CALULATIONS IF THE OVENS ARE GAS-FIRED-
 SECTION 304 FBC-17 FUEL GAS.
  
 5) PROVIDE A ROOF PLAN SHOWING THE TERMINATION
 LOCATIONS OF THE OVEN VENTS.
  
 6) SUBMIT THE MIAMI-DADE NOA# 15-1109.04 FOR THE
 LOUVER.
  
 7) M-1: THE AC CLOSET LOUVERED DOOR SHALL BE
 NON-COMBUSTIBLE PER SECTION C403.2.9.2 FBC-17 ENERGY
 CONSERVATION.
  
 8) M-1: SHOW THE AIR HANDLER CONDENSATE DISPOSAL RUN
 AND TERMINATION LOCATION- SECTION 307.2.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2018-08-15 Time 14:14 Sent To  
Notes
2018-08-15 16:25:16PROVISO; SEE NOTES ON SHEET A-2
  
 1. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 2. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.PER FBC ACC 604.3.1
 3. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.PER
 FBC ACC 604.5.1
 4. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
 5. A 30?X48? CLEAR FLOOR SPACE POSITIONED FOR A FORWARD
 APPROACH AND KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED AT LAVATORY. PER FBC ACC 606.2
 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER
 FBC ACC 606.3
  
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 09:58 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 09:58 Sent To  
Notes
2018-05-02 10:07:241ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE MOP SINK SHALL DISCHARGE THRU THE GREASE TRAP
 YOUR SIZING CALCULATION INCLUDE THE MOP SINK BUT THE
 SANITARY ISOMETRIC DOES NOT SHOW IT CONNECTING TO THE
 GREASE TRAP. PER FBC PL 1003.1
  
 2. SHT. S-3 THE FLOOR PLAN OF THE BATHROOM DOES NOT
 SHOW THE NEW EXTENDED WALLS PLEASE PROVIDE A FLOOR PLAN
 OF THE BATHROOM SHOWING THE NEW EXTENDED WALLS AND THE
 CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY.
 PER FBC ACC 604.3.1, 606.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By gjohnson Date 2018-02-28 Time 11:28 Rev Time 0.00
Received By gjohnson Date 2018-02-28 Time 11:28 Sent To  
Notes
2018-02-28 11:37:341ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. S-1 SHOWS THE EXISTING RESTROOM TO BE ENLARGED
 THE MEP SHEETS DO NOT SHOW THE HE ENLARGED BATHROOM
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE PLAN IS REFERENCING 2014 FBC WHICH STARTING JAN.
 1 CHANGED TO THE CURRENT CODE OF FBC 2017 PLEASE CHANGE
 ALL CODE LISTINGS TO REFLECT THE CURRENT CODE CYCLE OF
 2017.
  
 3. AS THIS IS A CHANGE OF OCCUPANCY THE EXPANDED
 BATHROOM WILL HAVE TO COMPLY WITH FBC EXISTING 1006.1
  
 4. THE EXPANDED BATHROOM SHALLL COMPLY WITH FBC ACC CH
 6 PLEASE PROVIDE THE FOLLOWING DIMENSIONS AND SHOW
 CLEAR FLOOR SPACES. PER WPB AMEND TO FBC 107.2.1
  
 A) 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 B) 604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL.
  
 C) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19
 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
  
 E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
  
 F) 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR.
  
 G) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 H) 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
  
 5. THE 3 COMPARTMENT SINK SHAL BE INDIRECT WASTE. PER
 FBC PL 802.1.1
  
 6. THE GREASE INTERCEPTOR AND HAND SINK SHALL CONNECT
 TO THE BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP
 WET VENT PER FBC PL 912.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-03-08 Cont ID  
Sent By AV Date 2018-03-08 Time 17:05 Rev Time 0.00
Received By ajones Date 2018-03-06 Time 17:21 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy