Plan Review Details - Permit 18020440
Plan Review Stops For Permit 18020440
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-23 Cont ID  
Sent By scaldero Date 2018-02-23 Time 15:34 Rev Time 0.00
Received By scaldero Date 2018-02-23 Time 15:34 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By scaldero Date 2018-02-15 Time 12:26 Rev Time 0.00
Received By scaldero Date 2018-02-15 Time 12:25 Sent To I
Notes
2018-02-15 12:26:48PERMIT # 18020440
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF
 THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS.
  
 2) PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE
 MAXIMUM NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND
 RADIUS PERMITTED IN THE LISTING DATA.
  
 3) SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS
 PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE
 BRAIDED OR UNBRAIDED.
  
 4) INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-26 Cont ID  
Sent By cpuell Date 2018-02-26 Time 18:08 Rev Time 0.00
Received By cpuell Date 2018-02-20 Time 14:06 Sent To  
Notes
2018-02-21 14:06:44RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-15 Cont ID  
Sent By lmarchan Date 2018-02-15 Time 14:25 Rev Time 0.00
Received By lmarchan Date 2018-02-09 Time 09:18 Sent To  
Notes
2018-02-12 09:18:11ROUTED TO FIRE INBOX