| Plan Review Stops For Permit 18020425 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-02-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-02-28 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-28 |
Time |
12:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-02-16 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-16 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2018-02-16 15:16:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE PRODUCT APPROVAL IS NOT COMPLETE. INCLUDE PAGES | | | WHICH ARE APPLICABLE TO ALL ASSEMBLIES, FBC 107. | | | | | | 2. PROVIDE A PLAN WHICH SUPPORTS CONTRACTOR'S ASSERTION | | | THAT THE STRUCTURE IS "OPEN". AN OPEN STRUCTURE IS ONE | | | WHICH IS OPEN ON ALL SIDES. IF ONE SIDE IS NOT OPEN, | | | THE STRUCTURE IS CONSIDERED "ENCLOSED". FBC RESIDENTIAL | | | 301. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-02-16 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-09 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
|