| Plan Review Stops For Permit 18020397 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-08 |
Time |
18:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-08 |
Time |
18:36 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-02-13 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-02-13 |
Time |
18:43 |
Sent To |
|
|
| Notes |
| 2018-02-13 18:51:15 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEER THAT IS ON THE SLAB ANCHORING PLANS, | | | RONALD H. WILSON P.E. LICENSE NO. 9710, HAS HAD HIS FL | | | ENGINEERING LICENSE REVOKED SINCE 2/28/2017. SUBMIT | | | PLANS FROM A CURRENTLY LICENSED FL ENGINEER. FS 471 | | | | | | 2) THE DATE ON THE SLAB ENGINEERING IS NOVEMBER 3, | | | 2014. PLEASE INFORM THE PERSON THAT IS PROVIDING THESE | | | OUTDATED DRAWINGS THAT THE ENGINEER'S LICENSE IS | | | REVOKED AND THEY NEED TO DISPOSE OF ANY MORE OF THESE | | | THAT ARE IN THEIR POSSESION. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-05-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-10 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-10 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-03-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-28 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-28 |
Time |
13:46 |
Sent To |
G |
|
| Notes |
| 2018-03-28 13:46:42 | SAME NOTE AS THE LAST TWO TIMES JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-07 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-07 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2018-03-07 16:38:26 | RISER DIAGRAM STILL SHOWS 38KW GENERATOR AND SUBMITALS | | | SHOW 48KW | | | | | | PLEASE CORRECT RISER TO REFLECT 48KW GENERATOR |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-15 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-02-15 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2018-02-15 10:31:27 | WHAT SIZE IS THE GENERATOR 38KW OR 48KW? | | | | | | PAPER WORK SHOWS BOTH |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2018-05-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-10 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-10 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2018-05-07 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-07 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-07 |
Time |
09:18 |
Sent To |
I |
|
| Notes |
| 2018-05-07 10:13:38 | 1) THE SUBMITTTED SIZING TABLES FOR THE GAS SYSTEM ARE | | | FROM THE 2014 FBC-FUEL GAS CODE. THE CODE IN EFFECT FOR | | | THIS PERMIT IS THE 2017 FBC-FUEL GAS.SUBMIT TWO COPIES | | | OF THE SIZING TABLES FROM THE 2017 FBC-FUEL GAS CODE. | | | 4TH REQUEST. | | | 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE | | | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE | | | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, | | | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | 3) SHOW THE DISTANCE FROM THE MEDIUM PRESSURE REGULATOR | | | FOR THE EXISTING APPLIANCES TO THE MOST REMOTE OUTLET | | | ON THE SYSTEM. | | | 4) A GAS SIZING TABLE FOR SCH. 40 METALLIC PIPE 2 PSI | | | SHOWING A 70 FEET LENGTH HAS BEEN SUBMITTED AND ALSO A | | | SIZING TABLE FOR PE PIPE AT A 2 PSI SYSTEM AT 90 FEET | | | LENGTH. WHICH IS IT? METALLIC PIPE IS NOT PERMITTED TO | | | BE UNDERGROUND PER 2017 FBC - FUEL GAS SEC. 404.11.1. | | | THE PE PIPE IS UNDERSIZED IF THE LENGTH IS 90 FEET. THE | | | MAXIMUM BTU LOAD IS 1,130,000. CLARIFY. | | | 5) SIZE THE PIPE FROM THE GAS METER TO THE FIRST TEE | | | AND ALSO FROM THE TEE FITTING TO THE MEDIUM PRESSURE | | | REGULATOR FOR THE EXISTING APPLIANCES. | | | | | | NOTE: SOMEONE FROM THE CONTRACTOR NEEDS TO COME TO THE | | | BUILDING DIVISION AND STRAIGHTEN OUT ALL THE PAPERWORK | | | INTO TWO COMPLETE PACKAGES FOR PLAN REVIEW. AS OF NOW, | | | THIS PAPERWORK IS A CONFUSING MESS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2018-03-28 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-03-28 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-03-28 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2018-03-28 14:46:48 | 03/28/2018 3RD GAS REVIEW**DENIED** PLEASE CALL AND | | | SPEAK TO TIM LARGE 561-805-6692 TO SET A MEETING DATE | | | AND TIME TO REVIEW THE PLAN DEFICIENCIES AS THIS IS THE | | | 3RD REVIEW AND ONLY 3 OF 10 COMMENTS HAVE BEEN | | | RESOLVED.DO NOT RESUBMIT WITHOUT FIRST HAVING A | | | MEETING. IT IS ADVISED YOU ALSO CONTACT THE ELECTRIC | | | PLAN REVIEW AND MEET AT THE SAME TIME. | | | | | | 1) WE ARE CURRENTLY USING THE 2017 FBC CODE 6TH ED. | | | YOUR PAPERWORK STILL REFERS TO THE 2014 FOR THE 3RD | | | TIME | | | | | | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE. YOU ARE NOT SHOWING | | | THE PIPING SIZE LEAVING THE GAS METER. 2017 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. | | | G2413.4.1, G2413.4.2. | | | | | | 3) SUBMIT FULL INSTALLATION MANUAL FOR THE GAS PRESSURE | | | REGUALTOR. FGC 410.1 | | | | | | 4) SUBMIT 2 COPIES OF SIZING TABLES FOR ALL PIPING | | | MATERIAL BEING USED. YOU SUPPLIED SCH 40 METALLIC | | | SIZING CHART BUT YOUR ISOMETRIC SHOWS YOUR RUNNING NE | | | P.E. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | | G2413.1, G2413.2, & G2413.3. | | | | | | 5) REVISE YOUR ISOMETRIC TO SHOW REQUIRED SEDIMENT TRAP | | | ON THE GENERATOR. FGC 408.3 | | | | | | 6) YOUR PLAN STILL IS SHOWING BOTH 38KW AND 48KW. | | | PLEASE REMOVE THE INCORRECT SHEETS. FBC 107.2.1 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-03-09 |
Time |
05:45 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-03-09 |
Time |
05:45 |
Sent To |
|
|
| Notes |
| 2018-03-09 05:49:56 | 03/09/2018 2ND GAS REVIEW**DENIED** | | | | | | YOU HAVE FAILED TO ANSWER ANY OF MY COMMENTS OR ADDRESS | | | ANY OF THE DRAWINGS. IF THE SUBMITTED PLANS ARE DENIED | | | ON THE NEXT REVIEW A 4X PLAN REVIEW FEE WILL BE APPLIED | | | TO THIS PERMIT PER FL STATE STATUE 553.80 (2B). IT IS | | | IN YOUR BEST INTEREST TO MEET WITH THIS PLAN REVIEWER | | | BEFORE SUBMITTING ANY OTHER PLANS EITHER FOR THIS OR | | | OTHER JOBS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1) WHAT SIZE GENERATOR IS BEING USED? PLAN SHOWS BOTH | | | 38KW AND 48KW. FBC 107.2.1 | | | | | | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413 | | | | | | 3) WHAT IS THE EXISTING SYSTEM PRESSURE? IS IT YOUR | | | INTENT TO CHANGE THE 12" WC TO 2LB SYSTEM OR IS THE | | | SYSTEM ALREADY 2 PSI. FBC 107.2.1 | | | | | | 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 | | | (37) OR 2014 FBC-RES. SEC. G2413. THE PLANS INDICATE AN | | | EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS | | | SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE | | | SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. | | | IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, | | | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, | | | G2413.2, G2413.3 | | | | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FGC SEC.410.1. | | | | | | 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4, | | | FBC-RESIDENTIAL SEC. G 2420.4. I | | | | | | 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 | | | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, | | | G2412.8, G2413.1, G2413.2, & G2413.3. | | | | | | 8) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4 | | | (28) FOR THE PROPER PIPE SIZE AND BTU LOAD | | | | | | 9) REVISE YOUR FLAT DRAWING TO SHOW THE REQUIRED | | | SEDIMENT TRAP. 2017 FBC-FUEL GAS 408.4. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-02-16 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-02-16 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-02-16 |
Time |
12:16 |
Sent To |
I |
|
| Notes |
| 2018-02-16 12:35:30 | 02/16/2018 1ST GAS REVIEW**DENIED** | | | | | | PLEASE BE ADVISED THE CURRENT CODE IN EFFECT IN THE 6TH | | | ED. 2017 FBC. SOME OF YOUR SIZING CHARTS REFERENCE THE | | | 2014 FBC | | | | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1) WHAT SIZE GENERATOR IS BEING USED? PLAN SHOWS BOTH | | | 38KW AND 48KW. FBC 107.2.1 | | | | | | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413 | | | | | | 3) WHAT IS THE EXISTING SYSTEM PRESSURE? IS IT YOUR | | | INTENT TO CHANGE THE 12" WC TO 2LB SYSTEM OR IS THE | | | SYSTEM ALREADY 2 PSI. FBC 107.2.1 | | | | | | 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 | | | (37) OR 2014 FBC-RES. SEC. G2413. THE PLANS INDICATE AN | | | EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS | | | SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE | | | SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. | | | IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, | | | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, | | | G2413.2, G2413.3 | | | | | | 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FGC SEC.410.1. | | | | | | 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4, | | | FBC-RESIDENTIAL SEC. G 2420.4. I | | | | | | 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 | | | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, | | | G2412.8, G2413.1, G2413.2, & G2413.3. | | | | | | 8) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4 | | | (28) FOR THE PROPER PIPE SIZE AND BTU LOAD | | | | | | 9) REVISE YOUR FLAT DRAWING TO SHOW THE REQUIRED | | | SEDIMENT TRAP. 2017 FBC-FUEL GAS 408.4. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-05-07 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-07 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-01 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2018-05-02 09:39:49 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-28 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-03-28 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-03-22 |
Time |
12:43 |
Sent To |
I |
|
| Notes |
| 2018-03-23 12:43:44 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-03-09 |
Time |
05:50 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-03-06 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2018-03-07 10:31:44 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-15 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-02-08 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2018-02-09 11:35:01 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-05-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-05-04 |
Time |
14:14 |
Sent To |
G |
|
| Notes |
| 2018-05-04 14:15:26 | LANDSCAPE SCREENING REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-02-13 |
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2018-02-13 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-02-13 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2018-02-13 15:13:58 | LANDSCAPE SCREENING REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|