Plan Review Details - Permit 18020385
Plan Review Stops For Permit 18020385
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-31 Cont ID  
Sent By jwitmer Date 2018-10-31 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2018-10-31 Time 07:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 14:38 Rev Time 0.00
Received By shill Date 2018-10-23 Time 14:38 Sent To  
Notes
2018-10-23 14:39:322017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020385
 ADD: 400 CLEMATIS ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-574-4968 / RACHEL MYERS
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. OCT.23
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) THE PLAN SHEET A0.1 INDICATES THIS TO BE A LEVEL 3
 ALTERATION. PLEASE NOTE THIS IS A CHANGE IN OCCUPANCY
 FROM AN A3 GYM TO A MERCANTILE. UNDER THE 2017 FBC
 EXISTING BUILDING CODE FOR A CHANGE IN OCCUPANCY FOR A
 PORTION OF A BUILDING YOU GO TO:
 2017 FBC-EXIST. SECTION 1001.2.2.1PARTIAL CHANGE OF
 OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP
 OF A PORTION OF AN EXISTING BUILDING IS CHANGED,
 SECTION 1012 SHALL APPLY. ALL OF 1012.1THROUGH 1012.8.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2-6) COMPLIED.
  
 7) SEE IMPACT FEE STATEMENT. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. ONE SET OF PLANS WILL HAVE TO BE
 TAKEN (BY THE CONTRACTOR OR REPRESENTATIVE) TO THE PALM
 BEACH COUNTY IMPACT FEE OFFICE LOCATED AT 2300 N. JOG
 RD. ROOMS 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-23 Cont ID  
Sent By jgomez Date 2018-08-22 Time 19:04 Rev Time 0.00
Received By jgomez Date 2018-08-21 Time 16:43 Sent To  
Notes
2018-08-20 17:58:34CHANGE OF OCCUPANCY ((M) , SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
  
 ORIGINAL COMMENT:
 1) CODE INFORMATION SHEET A0.1:
 CODE ANALYSIS AND PROJECT DATE INDICATES THIS IS A
 LEVEL III ALTERATION. PLEASE NOTE THIS IS A CHANGE OF
 OCCUPANCY SEE THE 2017 FBC-EXISTING BUILDING CODE
 CHAPTER 10.
 EXIST. BLDG. CODE 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP
 OF A PORTION OF AN EXISTING BUILDING IS CHANGED,
 SECTION 1012 SHALL APPLY.
  
 RESPONSE:
 THE CORRECT CLASSIFICATION OF WORK IS ALTERATION LEVEL
 3 AND CHANGE OF OCCUPANCY. SEC. 501.1 FBC-EXISTING
 BUILDING. IT IS IMPORTANT TO CLEARLY SPECIFY SCOPE OF
 WORK. TYPICALLY, ALTERATION LEVEL 3 PROJECTS REQUIRE A
 CERTIFICATE OF COMPLETION, BUT WHEN THE SCOPE OF WORK
 INVOLVES A CHANGE OF OCCUPANCY, THEN A CERTIFICATE OF
 OCCUPANCY IS REQUIRED.
 SINCE THIS IS A CHANGE OF OCCUPANCY A CERTIFICATE OF
 OCCUPANCY SHALL BE USED AS REQUIRED BY SEC. 1001.3
 FBC-EXISTING BUILDING.
  
 ORIGINAL COMMENT:
 2) SHEET S3 THE TABLE FOR PRESSURES DOES NOT STATE IT
 IS FOR 10 SQ. FT., THE TABLE DOES STATE THE PRESSURES
 ARE IN VASD. THE WALL PRESSURES FOR WALL ZONE 4 ARE 4
 PSF LOW, WE FIGURE- 49.24 PSF AND WALL ZONE 5 THE
 PRESSURES OF -60.76 TAKEN FOR A MEAN ROOF HEIGHT OF 35
 FEET. THIS BUILDING IS A MEAN ROOF HEIGHT GIVEN AT 34
 FEET MEAN ROOF HEIGHT.
  
 RESPONSE:
 THE 10% REDUCTION OF GCP VALUES IS OK (FIGURE 30.4-1
 ASCE 7-10) BUT THE HEIGHT SPECIFIED ON SHEET S3 SEEMS
 TO BE INCORRECT. IT DOESN'T MATCH HEIGHT SHOWN ON
 SHEETS A7 AND A8. REVISE AS REQUIRED. ALSO, THE DESIGN
 PRESSURES STILL DON'T CLARIFY THE EFFECTIVE WIND AREA.
 ARE THE VALUES GIVEN FOR 10PSF?. PLEASE CLARIFY.
 ACCORDING TO NOTE #4 OF FIGURE 30.4-1 EACH COMPONENT
 SHALL BE DESIGNED FOR MAXIMUM POSITIVE AND NEGATIVE
 PRESSURES. THIS IS REQUIRED FOR PROPER REVIEW OF
 PRODUCT APPROVALS SUBMITTED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A RESPONSE LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NEW COMMENTS:
 4) FLOOR PLAN LAYOUT WAS CHANGED. PRELIMINARY
 MERCHANDISE PLAN SHEET F-1P WAS NOT REVISED REFLECTING
 THE PROPOSED CHANGES. PROVIDE REVISED SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 5)FIRE SPRINKLER SHEET FP-2 WAS REVISED. NEED THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 SEC. 61G15-23.003 F.A.C. DIGITAL SIGNATURE IS ONLY FOR
 DIGITAL SUBMITTALS. THIS IS NOT A DIGITAL SUBMITTAL.
  
 6- INFORMATION ONLY: FLOOR PLAN NOTE #4 ON SHEET A1
 CALL FOR AWNING REPLACEMENT. COMPLETE DRAWINGS AND
 SPECIFICATIONS NEED TO BE SUBMITTED UNDER A SEPARATE
 PERMIT.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-01 Cont ID  
Sent By jwitmer Date 2018-03-01 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2018-02-28 Time 11:19 Sent To  
Notes
2018-03-01 10:51:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020385
 ADD: 400 CLEMATIS ST. (FIRST FLOOR)
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-574-4968 RACHAEL MYERS
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 01/ 2018
 ACTION: DENIED
  
 1) CODE INFORMATION SHEET A0.1:
  
 1A) CODE ANALYSIS AND PROJECT DATE INDICATES THIS IS A
 LEVEL III ALTERATION. PLEASE NOTE THIS IS A CHANGE OF
 OCCUPANCY SEE THE 2017 FBC-EXISTING BUILDING CODE
 CHAPTER 10.
 EXIST. BLDG. CODE 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP
 OF A PORTION OF AN EXISTING BUILDING IS CHANGED,
 SECTION 1012 SHALL APPLY.
  
 1B) THE OCCUPANT LOAD GIVEN FOR THE MERCANTILE AREA IS
 12, 290 SQ. FT. /30 = 410 OCCUPANTS. PLEASE BE AWARE OF
 A CHANGE IN THE 2017 FBC-B IN TABLE 1004.1.2. UNDER THE
 HEADING FOR MERCANTILE. THE CODE NOW USES 60 SQ. FT.
 PER OCCUPANT FOR ALL FLOORS. WHICH WILL GIVE AN
 OCCUPANT LOAD OF 205, PLEASE CORRECT.
  
 2) SHEET A0.5 THE LIFE SAFETY SHEET INDICATES UNDER THE
 HEADING EGRESS DATA FOR MERCANTILE. TRAVEL DISTANCES
 FOR NEW MERCANTILE (A) COMMON PATH OF TRAVEL 100 FT.
 PLEASE REVISE THE PLAN, SEE 2017 FBC-B TABLE 1006.2.1.
  
 3) SHEET A2 INDICATES THE PARAPET WALL HEIGHTS OF THE
 BUILDING. IN THE SOUTHWEST CORNER OF THE BUILDING THE
 SOUTH SIDE PARAPET SECTION LABELED 21 IS 28 INCHES
 HIGH, THE WEST SIDE OF THE BUILDING LABELED 22 IS 32
 INCHES HIGH, JUST THE NORTHWEST CORNER 68 INCHES HIGH
 AND IN THE NORTHWEST CORNER IDENTIFIED AS 24 IS 33
 INCHES HIGH. NOT UNTIL YOU GET TO THE NORTHEAST CORNER
 OF THE BUILDING IS THE PARAPET 40 INCHES HIGH ? OF THE
 NORTH PARAPET IS 36 INCHES OR LESS. WITH THIS BEING
 SAID THE ROOF PRESSURES IN ROOF ZONE 3 WILL BE ZONE 3
 PRESSURES NOT THE ROOF ZONE 2 AS WOULD BE THE CASE WITH
 A MINIMUM OF 3 FOOT PARAPET ALL THE WAY AROUND THE
 BUILDING. SHEET S3 THE ROOF ZONE 3 PRESSURES ARE THE
 SAME IN ROOF ZONES 2 AND 3.
  
 4) SHEET S3 THE TABLE FOR PRESSURES DOES NOT STATE IT
 IS FOR 10 SQ. FT., THE TABLE DOES STATE THE PRESSURES
 ARE IN VASD. THE WALL PRESSURES FOR WALL ZONE 4 ARE 4
 PSF LOW, WE FIGURE- 49.24 PSF AND WALL ZONE 5 THE
 PRESSURES OF -60.76 TAKEN FOR A MEAN ROOF HEIGHT OF 35
 FEET. THIS BUILDING IS A MEAN ROOF HEIGHT GIVEN AT 34
 FEET MEAN ROOF HEIGHT.
  
 5) PROVISO: RATHER THAN REQUIRE A RESIDENT INSPECTOR
 SINCE THE WELDED AND BOLTED CONNECTIONS IS VERY LIMITED
 PLEASE PROVIDE COMPLIANCE WITH:
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 6) PLEASE REVIEW FIRE CHIEF LEDUC COMMENT ABOUT NOT
 ENOUGH EXIT AND EXIT DIRECTIONAL SIGNAGE SEE SHEETS
 A0.5 & E3 AND COMPLIANCE WITH:
 2017 FBC-B SECTION 1013.1 WHERE REQUIRED. EXITS AND
 EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED EXIT
 SIGN READILY VISIBLE FROM ANY DIRECTION OF EGRESS
 TRAVEL. THE PATH OF EGRESS TRAVEL TO EXITS AND WITHIN
 EXITS SHALL BE MARKED BY READILY VISIBLE EXIT SIGNS TO
 CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL IN
 CASES WHERE THE EXIT OR THE PATH OF EGRESS TRAVEL IS
 NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS. INTERVENING
 MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE MARKED BY
 EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT ACCESS CORRIDOR OR EXIT PASSAGEWAY IS
 MORE THAN 100 FEET (30 480 MM) OR THE LISTED VIEWING
 DISTANCE FOR THE SIGN, WHICHEVER IS LESS, FROM THE
 NEAREST VISIBLE EXIT SIGN.
  
 7) SHEET S2 SHOWS 2 DOOR CUT SECTIONS 4/S4 AND 7/S4
 BOTH USING A C1 TYPE COLUMN AND A HSS6X6 3/8 INCH STEEL
 BOX BEAM, THE DETAILS DO NOT PROVIDE THE WELD
 CONNECTION TO THE VERTICAL COLUMN C1. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 8) SHEET A6 DETAIL # 9 & 10 SHOWS A REFRIGERANT LINE
 CHASE (WALL) DETAIL. PLEASE NOTE TO HAVE A CHASE AND
 NOT A SHAFT THE FLOOR PENETRATIONS THROUGH THE FLOOR
 WILL NEED TO PROVIDE THROUGH THE FLOOR/ CEILING
 ASSEMBLIES IN COMPLIANCE WITH:
 2017 FBC-B 714.4 HORIZONTAL ASSEMBLIES
 FBC-B 714.4.1 THROUGH PENETRATIONS.
 FBC-B 714.4.1.1 INSTALLATION. THROUGH PENETRATIONS
 SHALL BE INSTALLED AS TESTED IN THE APPROVED FIRE-
 RESISTANCE-RATED ASSEMBLY.
 714.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER (2.49 PA). THE SYSTEM SHALL HAVE AN F RATING/T
 RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED.
 SHEETS A23 NOR A24 SHOW A FLOOR/ CEILING THROUGH
 PENETRATION AND FIRE STOPPING SYSTEM.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-09-28 Cont ID  
Sent By jpearson Date 2018-09-28 Time 11:04 Rev Time 0.00
Received By jpearson Date 2018-09-28 Time 11:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By jpearson Date 2018-08-09 Time 17:16 Rev Time 0.00
Received By jpearson Date 2018-08-09 Time 15:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 13:34 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 11:40 Sent To  
Notes
2018-03-16 13:34:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
 2. PROVIDE DETAILS OF THE EXISTING SERVICE LATERAL AND
 GROUNDING ELECTRODE SYSTEM TO VERIFY SIZES ARE CORRECT
 FOR SERVICE. FBC 107.2.1; NEC 215.2, 215.5
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. FIRE REVIEWER NOTED 7 LOCATIONS ON PLAN FOR EXIT
 LIGHTS IN THE PATH OF TRAVEL, WHICH NEED TO BE ADDED TO
 LIGHTING PLAN. PROVIDE PER FIRE COMMENTS. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-08-09 Cont ID  
Sent By jpearson Date 2018-08-09 Time 17:15 Rev Time 0.00
Received By jpearson Date 2018-08-09 Time 17:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-19 Cont ID  
Sent By pleduc Date 2018-09-19 Time   Rev Time 0.00
Received By pleduc Date 2018-09-18 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-13 Cont ID  
Sent By pleduc Date 2018-07-13 Time   Rev Time 0.00
Received By pleduc Date 2018-07-13 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-13 Cont ID  
Sent By pleduc Date 2018-02-13 Time   Rev Time 0.00
Received By pleduc Date 2018-02-13 Time 11:21 Sent To  
Notes
2018-02-13 13:36:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEETS A 0.5 & E 3 - THERE DOES NOT APPEAR TO BE
 SUFFICIENT EXIT SIGNS IN THE PATH OF TRAVEL. ENSURE
 THERE IS PROPER EXIT SIGNAGE CLEARLY VISIBLE INDICATING
 AND LEADING TO THE EXIT ALONG THE PATH OF TRAVEL.
  
  
  
 2) SHEET E 1.1 - THERE IS INDICATION OF A FIRE ALARM
 SYSTEM BY CVS. ENSURE THAT THE FIRE ALARM SYSTEM IS
 TIED INTO THE EXISITNG BUILDING SYSTEM.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-31 Cont ID  
Sent By cpuell Date 2018-10-31 Time 10:20 Rev Time 0.00
Received By cpuell Date 2018-10-29 Time 14:31 Sent To  
Notes
2018-10-30 14:31:15RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 14:39 Rev Time 0.00
Received By shill Date 2018-09-13 Time 16:07 Sent To  
Notes
2018-09-14 16:07:23C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-23 Cont ID  
Sent By jgomez Date 2018-08-22 Time 19:04 Rev Time 0.00
Received By jgomez Date 2018-07-06 Time 10:47 Sent To I
Notes
2018-07-11 10:47:19C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-28 Cont ID  
Sent By cpuell Date 2018-03-28 Time 17:46 Rev Time 0.00
Received By cpuell Date 2018-02-08 Time 14:42 Sent To  
Notes
2018-02-09 14:42:35C33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2018-11-15 Cont ID  
Sent By skennedy Date 2018-11-15 Time 09:21 Rev Time 0.00
Received By skennedy Date 2018-11-15 Time 09:21 Sent To  
Notes
2018-11-15 09:22:24REVIEWED BY PBC. NO FEES WERE ASSESSED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2018-10-31 Cont ID  
Sent By jwitmer Date 2018-10-31 Time 08:24 Rev Time 0.00
Received By jwitmer Date 2018-10-31 Time 08:24 Sent To  
Notes
2018-10-31 08:25:08BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2018-10-23 Time   Rev Time 0.00
Received By   Date 2018-10-23 Time   Sent To  
Notes
2018-10-31 08:24:52BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By jgomez Date 2018-08-21 Time 08:54 Rev Time 0.00
Received By jgomez Date 2018-08-21 Time 08:54 Sent To  
Notes
2018-08-21 08:55:32IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-01 Cont ID  
Sent By jwitmer Date 2018-03-01 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2018-02-28 Time 11:20 Sent To  
Notes
2018-03-01 09:42:08BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-05 Cont ID  
Sent By ccole Date 2018-10-05 Time 08:59 Rev Time 0.00
Received By ccole Date 2018-10-04 Time 08:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-07-31 Cont ID  
Sent By ccole Date 2018-07-31 Time 12:13 Rev Time 0.00
Received By ccole Date 2018-07-31 Time 10:34 Sent To  
Notes
2018-07-31 12:52:312ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18020385
 7/31/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED AC CALCULATIONS FROM THE EOR INDICATE
 THAT THE HP SYSTEMS 1-5, AS SHOWN IN THE SCHEDULES ON
 SHEET M3, ARE OVERSIZED IN COOLING AND HEATING
 CAPACITIES- SEE SECTION C403.2.2 FBC EC. MISSING FROM
 THE CALCULATIONS ARE THE MINI-SPLIT SYSTEMS 6, 7, & 8.
  
 2) THE SUBMITTED COMCHECK ENERGY COMPLIANCE CERTIFICATE
 SHOWS CAPACITIES FOR COOLING AND HEATING THAT DON'T
 MATCH THE CAPACITIES IN THE SCHEDULES. PLEASE NOTE THAT
 THE EFFICIENCY RATING OF 12.30 EER FOR SYSTEM #3 DOES
 NOT MATCH THE SCHEDULE WHICH INDICATES 11.9 EER.
  
 3) M1.1: VERIFY MIMIMUM 10' CLEARANCE EXISTS FROM THE
 NEW O/A INTAKE LOUVER TO THE STREET- SECTION 401.4 FBC
 M.
  
 4) SHEET P1.1: THE CONDENSATE FROM AHU-7 & 8 SHALL NOT
 DRAIN INTO THE CITY SANITARY PER SECTION 90-126 CITY OF
 WPB CODE OF ORDINANCES. PLEASE PROVIDE AN APPROVED
 LOCATION SUCH AS A STORM DRAIN OR PERMEABLE GROUND.
  
 5) REQUIRED SUBMITTALS: NOA'S OR PRODUCT APROVALS FOR
 THE LOUVERS AND AC STANDS, ERV, DUCT SMOKE DETECTORS,
 C02 SENSORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-12 Cont ID  
Sent By ccole Date 2018-03-12 Time 15:23 Rev Time 0.00
Received By ccole Date 2018-03-12 Time 14:25 Sent To  
Notes
2018-03-12 16:39:301ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18020385
 3/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 2) SHEET M3: THE MINIMUM O/A SCHEDULE SHOWS THE NUMBER
 OF OCCUPANTS IN THE RETAIL AREAS TO BE NOT IN
 COMPLIANCE WITH TABLE 403.1.1. BASED ON THE TABLE THE
 NUMBER OF OCCUPANTS SHALL BE: (AHU-1 53 PERSONS) AHU-2
 (31 PERSONS), AND AHU-3 (47 PERSONS). PLEASE REVISE THE
 CALCULATIONS AND PLANS ACCORDINGLY.
  
 3) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 SYSTEMS OF AHU'S 1, 2, & 3- SECTION 606.2.1.
  
 4) M1 & A4: PLEASE SHOW THE LOCATIONS OF THE DIFFUSERS
 AND RETURN GRILLS IN THE REFLECTIVE CEILING PLAN.
  
 5) M2: PROVIDE A GUARD ALONG THE ROOF EDGE IN THE AREA
 OF HP 1 & 2 OR PLACE A NOTE TO INDICATE THE EXISTING
 PARAPET IS A MINIMUM 42" HIGH ABOVE THE FINISHED ROOF
 SURFACE- SEE SECTION 304.11
  
 6) M2: PROVIDE WIND LOAD ENGINEERING FOR INSTALLTION OF
 THE NEW ROOFTOP STANDS AND CONDENSING UNITS- SECTION
 301.15. PLEASE INCLUDE THE WIND DESIGN CRITERIA IN
 ACCORDANCE WITH SECTION1609 FBC-17 BUILDING, AND SUBMIT
 THE MIAMI-DADE NOA FOR THE CONDENSER STANDS WITH
 MARKUPS AND APPROVAL STAMP BY THE EOR.
  
 7) M3: THE EQUIPMENT SCHEDULE FOR THE MINI-SPLIT SYSTEM
 IS INCOMPLETE. PLEASE PROVIDE THE COOLING AND HEATING
 CAPACITIES OF THE SYSTEM.
  
 8) PROVIDE A FLORIDA PRODUCT APPROVAL AND/OR A
 MIAMI-DADE NOA FOR THE O/A LOUVER, AND A SUBMITTAL FOR
 THE O/A AIR MOTORIZED DAMPERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-10 Cont ID  
Sent By gjohnson Date 2018-10-10 Time 12:56 Rev Time 0.00
Received By gjohnson Date 2018-10-10 Time 12:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-20 Cont ID  
Sent By gjohnson Date 2018-08-20 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2018-08-20 Time 10:28 Sent To  
Notes
2018-08-20 11:34:092ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHEET P1.1: THE CONDENSATE FROM AHU-7 & 8 SHALL NOT
 DRAIN INTO THE CITY SANITARY PER SECTION 90-126 CITY OF
 WPB CODE OF ORDINANCES. PLEASE PROVIDE AN APPROVED
 LOCATION SUCH AS A STORM DRAIN OR PERMEABLE GROUND.
  
 2. SHT. P1.1 - P2 THE SINK IN THE PHARMACY S1 SHALL
 CONNECT TO THE BUILDING DRAIN DOWN STREAM OF THE
 BATHROOM GROUP. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-20 Cont ID  
Sent By gjohnson Date 2018-03-20 Time 08:40 Rev Time 0.00
Received By gjohnson Date 2018-03-20 Time 08:40 Sent To  
Notes
2018-03-20 09:43:241ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
  
 3.PLEASE SHOW THE CLEAR FOOR SPACE WITH DIMENSIONS ,
 FOR THE TOILET AND LAVATORY. PER FBC ACC 604.3.1, 606.2
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2
 LOCATION.THE WATER CLOSET SHALL BE POSITIONED WITH A
 WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION. IT APPEARS THAT THE DIMENSION MAY HAVE BEEN
 SHOWN BUT IT DID NOT LINE UP WITH THE TOILET.
  
 5. SHT P4 DETAIL #7 THE WALL DRAIN BOX WHEN CONNECTED
 TO THE STORM DRAINAGE SHALL HAVE A BACKWATER VALVE. PER
 FBC PL 1101.9
  
 6. SHT P4 DETAIL # 2 THE REQUIRED TEMPERED WATER AT THE
 LAVATORY IN THE BATHROOM SHALL BE DELIVERED THROUGH A
 WATER TEMPERATURE LIMITING DEVISE THAT MEETS ASSE 1070
 OR CSA B125.3 THE TEMPERING VALVE SPARCO 102C LISTED ON
 DETAIL #2 DOES NOT COMPLY. THE REQUIREMENT FOR TEMPERED
 WATER ONLY ONLY APPLIES TO THE LAVATORY'S IN THE
 BATHROOMS . PER FBC PL 416.5
  
 7. PLEASE SHOW THAT THE 19 GAL WATER HEATER IS LARGE
 ENOUGH TO SUPPLY THE 5 SINKS WITH HOT OR TEMPERED WATER
 YOU CAN REFERENCE APPENDIX E OF THE FBC PL OR
 MANUFACTURE SIZING. PER WPB AMEND FBC AMEND TO FBC
 107.2.1
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-15 Cont ID  
Sent By aaponte Date 2018-08-15 Time 13:13 Rev Time 0.00
Received By aaponte Date 2018-08-15 Time 13:13 Sent To  
Notes
2018-08-15 13:18:53PROVISO: 1. AWNING IS NOT INCLUDED INTHIS PERMIT.
 2. SHEET F-1P SHALL BE REPLACED TO REFLECT NEW DOOR ON
 DIXIE HWAY AND CHANGES ON COOLERS.
 3. PACKAGE SALES ARE NOT PERMITTED UNTIL CODE AMENDMENT
 IS APPROVED.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-03-28 Cont ID  
Sent By AA Date 2018-03-28 Time 15:07 Rev Time 0.00
Received By aaponte Date 2018-03-28 Time 15:07 Sent To  
Notes
2018-03-28 15:16:351. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH ACTIVE USE REQUIREMENT ALONG DIXIE HWAY.
 2. PLEASE PROVIDE INFORMAITON TO CONFIRM COMPLIANCE
 WITH TRANSPARENCY REQUIREMENT ALONG DIXIE HWAY.
 PROPOSAL IS BLOCKING EXISTING WINDOWS ALONG THIS
 FRONTAGE.
 3. ALCOHOL SALES FOR CONSUMPTION OFF OF PREMISE IS NOT
 CURRENTLY PERMITTED. PLEASE REMOVE REFERENCE TO IT IN
 THE SUBMITTED DRAWINGS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.