Plan Review Details - Permit 18020359
Plan Review Stops For Permit 18020359
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By jwitmer Date 2018-11-14 Time 07:42 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2018-11-14 07:43:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020359
 ADD: 319 CLEMATIS ST. SUITE: 100
 CONT: GERALD CONTRACTING
 TEL: 561-832-9785
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. 11/14/2018
 ACTION: BUILDING PROVISO
  
 1) THE EGRESS DOOR (PAIR OF DOORS) SHALL COMPLY WITH:
 2018 FBC-ACCESSIBILITY CODE SECTION 404.2.5 THRESHOLDS.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES
 IN LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 EXCEPTION: EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19
 MM) HIGH MAXIMUM THAT HAVE A BEVELED EDGE ON EACH
 SIDE WITH A SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE
 REQUIRED TO COMPLY WITH 404.2.5.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-03-28 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2018-03-28 Time 09:01 Sent To  
Notes
2018-03-28 09:31:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020359
 ADD: 319 CLEMATIS ST. SUITE: 100
 CONT: GERALD CONTRACTING
 TEL: 561-832-9785
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. 28/2018
 ACTION: BUILDING PROVISO
  
 1) THE EGRESS DOOR (PAIR OF DOORS) SHALL COMPLY WITH:
 2018 FBC-ACCESSIBILITY CODE SECTION 404.2.5 THRESHOLDS.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES
 IN LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 EXCEPTION: EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19
 MM) HIGH MAXIMUM THAT HAVE A BEVELED EDGE ON EACH
 SIDE WITH A SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE
 REQUIRED TO COMPLY WITH 404.2.5.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-02-16 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2018-02-16 Time 17:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-11-05 Cont ID  
Sent By jpearson Date 2018-11-05 Time 17:37 Rev Time 0.00
Received By jpearson Date 2018-11-05 Time 17:37 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-05-15 Cont ID  
Sent By jpearson Date 2018-05-15 Time 12:12 Rev Time 0.00
Received By jpearson Date 2018-05-15 Time 11:16 Sent To  
Notes
2018-05-15 12:11:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED
 2. CORRECTED
 3. CORRECTED.
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By ppetty Date 2018-04-02 Time 09:36 Rev Time 0.00
Received By ppetty Date 2018-04-02 Time 09:36 Sent To  
Notes
2018-04-02 09:36:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CORRECTED
 2. CORRECTED
 3. PROVIDE LOAD CALCULATION FOR EXISTING PANEL, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF PANEL IS
 ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-27 Cont ID  
Sent By jpearson Date 2018-02-27 Time 11:26 Rev Time 0.00
Received By jpearson Date 2018-02-27 Time 09:56 Sent To  
Notes
2018-02-27 11:26:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 1 AND NOTE 17 SPECIFY THE 2011 NEC. THE NEC
 SPECIFIED FOR DESIGN IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. A CONFLICT EXIST BETWEEN PANEL SCHEDULE AND RISER
 DIAGRAM. PANEL SCHEDULE SHOWS # 8 WIRE ON A 60 AMP
 BREAKER FEEDING SUB-PANEL IN SUITE 100. RISER SHOWS (3)
 1/0 CONDUCTORS FEEDING THE SAME PANEL. THE # 8 WIRE IS
 NOT RATED FOR 60 AMPS, AND THE 1/0 WIRE WOULD NOT FIT
 ON A 60 AMP BREAKER. PROVIDE CORRECTION. NEC 110.3,
 215.2, 310.15
 3. PROVIDE LOAD CALCULATION FOR EXISTING PANEL, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF PANEL IS
 ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-29 Cont ID  
Sent By pleduc Date 2018-03-29 Time   Rev Time 0.00
Received By pleduc Date 2018-03-29 Time 09:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-14 Cont ID  
Sent By pleduc Date 2018-02-14 Time   Rev Time 0.00
Received By pleduc Date 2018-02-13 Time 15:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-12-11 Cont ID  
Sent By gjohnson Date 2018-12-11 Time 16:56 Rev Time 0.00
Received By gjohnson Date 2018-11-30 Time 16:56 Sent To  
Notes
2018-12-03 13:06:52RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-11-14 Cont ID  
Sent By cpuell Date 2018-11-14 Time 09:13 Rev Time 0.00
Received By cpuell Date 2018-10-29 Time 16:05 Sent To  
Notes
2018-10-30 16:06:03RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-22 Cont ID  
Sent By gjohnson Date 2018-05-22 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2018-05-10 Time 13:30 Sent To  
Notes
2018-05-14 13:30:28RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-09 Cont ID  
Sent By gjohnson Date 2018-04-09 Time 10:25 Rev Time 0.00
Received By gjohnson Date 2018-03-26 Time 15:33 Sent To  
Notes
2018-03-27 15:33:27B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-06 Cont ID  
Sent By lcrespo Date 2018-03-06 Time 15:58 Rev Time 0.00
Received By lcrespo Date 2018-02-08 Time 16:22 Sent To  
Notes
2018-02-09 16:22:50B18

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2018-12-12 Cont ID  
Sent By ccole Date 2018-12-12 Time 15:24 Rev Time 0.00
Received By ccole Date 2018-12-12 Time 15:24 Sent To  
Notes
2018-12-12 15:29:44MECHANICAL PROVISO
 12/12/18
  
 1) A REVISION IS REQUIRED TO PROVIDE A NEW AC SYSTEM TO
 CONDITION THE NEW SUITE #100.
  
 2) THE MAIN SUPPLY AND RETURN DUCT TRUNKS FROM THE
 EXISTING AC SYSTEM SHALL NOT PENETRATE THE DEMISING
 WALL OR PROVIDE CONDITIONING TO SUITE #100.
  
 CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2018-12-11 Cont ID  
Sent By ccole Date 2018-12-11 Time 10:43 Rev Time 0.00
Received By ccole Date 2018-12-11 Time 10:43 Sent To P
Notes
2018-12-11 11:17:564TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18020359
 12/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET MEP-1: THE EXISTING AC #1 SYSTEM CANNOT
 CONDITION THE AIR IN BOTH SUITES 100 AND 110. SUITES
 100 AND 110 ARE SEPARATE TENANT SPACES AND SEPARATE
 ZONES AS DEFINED IN SECTION 202 FBC EC, AND THEREFORE
 REQUIRE INDIVIDUAL AND SEPARATE THERMOSTATIC CONTROLS
 PER SECTION C403.2.4.1 FBC EC. TYPICALY, SEPARATE AC
 SYSTEMS MUST BE PROVIDED FOR EACH ZONE.
  
 2) MEP-1: THE REVISED PLAN INDICATES A MOTORIZED
 "JUMPER" IN THE MAIN SUPPLY DUCT WHICH APPEARS TO BE A
 MISPRINT FOR "MOTORIZED DAMPER". PLEASE NOTE THAT O/A
 BY MANUFACTURER'S SPECIFICATIONS MUST BE INTRODUCED
 INTO THE RETURN AIR SYSTEMS SO THAT IT CAN BECOME
 CONDITIONED AND DEHUMIDIFIED SUPPLY AIR.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-11-07 Cont ID  
Sent By ccole Date 2018-11-07 Time 09:40 Rev Time 0.00
Received By ccole Date 2018-11-07 Time 09:08 Sent To B
Notes
2018-11-07 10:03:113RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18020359
 11/7/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MEP-1: THE UPDATED PLANS SHOW A NEW TENANT
 BUILD-OUT. REFER TO SECTION 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) MEP-1: THE CURRENT PLAN APPEARS TO SHOW THE AIR
 DISTRIBUTION SYSTEM FOR THE NEW TENANT SPACE CONNECTED
 TO A SYSTEM OUTSIDE OF THE TENANT SPACE. PLEASE CLARIFY
 HOW THE SYSTEM IN THE NEW TENANT SPACE WILL BE
 CONTROLLED, AND HOW ACCESS FOR SERVICE AND FOR
 EMERGENCY SHUTDOWN OF THE SYSTEM WILL BE PROVIDED.
  
 IN ADDITION TO THE COMMENTS ABOVE, PLEASE ANSWER THESE
 QUESTIONS CLEARLY ON THE PLAN AND ALSO IN A RESPONSE
 NARRATIVE FROM THE EOR- TWOMEY.
  
 A) INDICATE HOW O/A IS BEING PROVIDED TO THE SPACE AND
 HOW IS IS BEING CONTROLLED- TABLE 403.3.1.1 FBC M, AND
 SECTION C403.2.4.2 FBC EC.
  
 B) SHOW THE LOCATION OF THE THERMOSTAT THAT IS
 CONTOLLING THE TEMPERATURE IN THE NEW SPACE- SECTION
 C403.2.4.1 FBC EC.
  
 C) THE PLAN INDICATES RETURN AIR VIA A PLENUM CEILING.
 PLEASE PLACE A NOTE PURSUANT TO SECTION 606.2.1
 REGARDING ALLOWABLE MATERIALS IN THE PLENUM SPACE.
  
 D) SHOW THE RETURN AIR PATH FROM THE NEW TENANT SPACE
 BACK TO THE AIR HANDLER- SECTION 601.6 FBC M.
  
 3) MEPP-1: PROVIDE AN ENLARGED DETAIL SHOWING THE
 TRANSITION DUCT AND THE 16 ROUND DUCT CONNECTIONS TO
 THE EXISTING FIRE DAMPER- SECTION 607.5.3 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-05-21 Cont ID  
Sent By ccole Date 2018-05-21 Time 15:06 Rev Time 0.00
Received By ccole Date 2018-05-21 Time 15:01 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By skennedy Date 2018-04-09 Time 10:15 Rev Time 0.00
Received By skennedy Date 2018-04-09 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-22 Cont ID  
Sent By ccole Date 2018-02-22 Time 12:39 Rev Time 0.00
Received By ccole Date 2018-02-22 Time 12:37 Sent To  
Notes
2018-02-22 13:04:26MECHANICAL PROVISOS:
 CCOLE- 2/22/18
  
 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPER SHALL BE ONSITE AT
 TIME OF INSPECTION.
  
 2) SEPARATE PERMIT FOR TENANT BUILD-OUT REQUIRED.

Review Stop P PLUMBING
Rev No 5 Status P Date 2018-12-11 Cont ID  
Sent By gjohnson Date 2018-12-11 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2018-12-11 Time 16:55 Sent To  
Notes
2018-12-11 16:56:12PLUMBING PROVISO: SHALL COMPLY PRIOR TO 1ST ROUGH
 INSPECTION.
  
 1. PROVIDE TEMPERED WATER AT THE LAVATORY.
 FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 FBC PL 607.1 HOT OR TEMPERED WATER WHERE REQUIRED. IN
 NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED
 FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR BUILDING
 MAINTENANCE PURPOSES. IN NONRESIDENTIAL OCCUPANCIES,
 HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED FOR
 BATHING AND WASHING PURPOSES.
 2. FBC ACC 604.7 TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
 3. FBC ACC 609.4 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 4. A WATER FOUNTAIN AND SERVICE SINK ARE REQUIRED PER
 FBC PL TABLE 403.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2018-11-06 Cont ID  
Sent By gjohnson Date 2018-11-06 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2018-11-06 Time 14:01 Sent To  
Notes
2018-11-06 14:03:274TH REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE TEMPERED WATER AT THE LAVATORY. AND HAND
 SINK. HOT WATER AT A SERVICE SINK.
 FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 FBC PL 607.1 HOT OR TEMPERED WATER WHERE REQUIRED. IN
 NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED
 FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR BUILDING
 MAINTENANCE PURPOSES. IN NONRESIDENTIAL OCCUPANCIES,
 HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED FOR
 BATHING AND WASHING PURPOSES.
 2. FBC ACC 604.7 TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
 3. FBC ACC 609.4 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 4. A WATER FOUNTAIN AND SERVICE SINK ARE REQUIRED PER
 FBC PL TABLE 403.1
  
 NEW COMMENT:
  
 1. THE ADDTIONAL HAND SINK SHALL CONNECT TO BUILDING
 DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL
 912.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-22 Cont ID  
Sent By gjohnson Date 2018-05-22 Time 13:14 Rev Time 0.00
Received By gjohnson Date 2018-05-22 Time 13:09 Sent To  
Notes
2018-05-22 13:17:15PLUMBING PROVISO: SHALL COMPLY PRIOR TO 1ST ROUGH
 INSPECTION.
  
 1. PROVIDE TEMPERED WATER AT THE LAVATORY.
 FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 FBC PL 607.1 HOT OR TEMPERED WATER WHERE REQUIRED. IN
 NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED
 FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR BUILDING
 MAINTENANCE PURPOSES. IN NONRESIDENTIAL OCCUPANCIES,
 HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED FOR
 BATHING AND WASHING PURPOSES.
 2. FBC ACC 604.7 TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
 3. FBC ACC 609.4 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 4. A WATER FOUNTAIN AND SERVICE SINK ARE REQUIRED PER
 FBC PL TABLE 403.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By gjohnson Date 2018-04-09 Time 10:05 Rev Time 0.00
Received By gjohnson Date 2018-04-09 Time 09:28 Sent To  
Notes
2018-04-09 10:25:04PLUMBING PROVISO:
  
 1. PROVIDE TEMPERED WATER AT THE LAVATORY.
 FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 FBC PL 607.1 HOT OR TEMPERED WATER WHERE REQUIRED.
 IN NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE
 SUPPLIED FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR
 BUILDING MAINTENANCE PURPOSES. IN NONRESIDENTIAL
 OCCUPANCIES, HOT WATER OR TEMPERED WATER SHALL BE
 SUPPLIED FOR BATHING AND WASHING PURPOSES.
 1. FBC ACC 604.7
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
 2. FBC ACC 609.4 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-06 Cont ID  
Sent By lcrespo Date 2018-03-06 Time 15:58 Rev Time 0.00
Received By lcrespo Date 2018-03-06 Time 15:58 Sent To  
Notes
2018-03-06 16:00:34DENIED
 1. AIR ADMITTANCE VALVE MUST BE AN APPROVED DEVICE THAT
 MEETS THE POSITIVE AND NEGATIVE PRESSURE ON A FIVE OR
 MORE MULTI-STORY BUILDING, IF NOT APPROVE IT CANNOT BE
 USED ON THE FIRST FLOOR IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE MANUFACTURES SPECIFICATION UNLESS
 WILLING TO PAY THE COST OF THE DEVICE THAT MEETS THOSE
 REQUIREMENTS. FBC P 918.2 INSTALLATION AND FBC P
 918.3.1 HORIZONTAL BRANCHES.
 2. HOT WATER DEVICE NOT SHOWN, PLEASE PROVIDE DETAIL
 AND SIZING FBC P 607.1 WHERE REQUIRED.
 3. TEMPERED WATER REQUIRED AND DETAILS OF A TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 FBC P
 607.1.2 TEMPERED WATER TEMPERATURE CONTROL.
 4. ADA DETAIL OF HEIGHTS AND DIMENSION NOT SHOWN,
 PLEASE PROVIDE DETAIL DRAWINGS PER 2017 FBC
 ACCESSIBILITY CODE.
 5. THERE IS NO CLEAN OUT AT THE 4? CONNECTION OF THE
 BUILDING 2017 FBC P 708.1.3 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION.
 6. PLEASE DARKEN DIMENSION FOR TOILET ROOM PAGE A-1,
 THEY ARE ILLEGIBLE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 7. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
 8. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA
 EXISTING BUILDING CODE 301.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  