Plan Review Details - Permit 18020356
Plan Review Stops For Permit 18020356
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-22 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-20 Time 12:43 Sent To  
Notes
2018-03-21 12:44:04RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-02-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-08 Time 14:11 Sent To  
Notes
2018-02-09 14:11:26ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-22 Cont ID  
Sent By ccole Date 2018-03-22 Time 10:21 Rev Time 0.00
Received By ccole Date 2018-03-22 Time 10:21 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By ccole Date 2018-02-14 Time 08:56 Rev Time 0.00
Received By ccole Date 2018-02-14 Time 08:56 Sent To I
Notes
2018-02-14 08:57:201ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18020356
 2/14/18
  
 1) SHOW THE LOCATION OF THE CONDENSER AND PROVIDE WIND
 LOAD ENGINEERING FOR INSTALLATION- SECTION 301.15
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  