Plan Review Details - Permit 18020341
Plan Review Stops For Permit 18020341
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By cthroop Date 2018-03-23 Time 13:43 Rev Time 0.00
Received By cthroop Date 2018-03-23 Time 13:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By cthroop Date 2018-03-14 Time 11:46 Rev Time 0.00
Received By cthroop Date 2018-03-08 Time 09:12 Sent To  
Notes
2018-03-14 12:47:57BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT.
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 3. NOA 14-0414.04 FOR OHD HAS EXPIRED.
 4. NOA 15-0129.04 FOR FIXED WINDOWS HAS EXPIRED.
 5. PROVIDE ICC - ES REPORT FOR ICYNENE INSULATION.
 6. PROVIDE DESIGN WIND LOADS FOR WINOW AND DOOR
 OPENINGS,
 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 GAS BBQ GRILL.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW SUBMITTALS.
  
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By jpearson Date 2018-03-23 Time 10:09 Rev Time 0.00
Received By jpearson Date 2018-03-23 Time 10:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-23 Cont ID  
Sent By jpearson Date 2018-02-23 Time 10:40 Rev Time 0.00
Received By jpearson Date 2018-02-23 Time 08:18 Sent To  
Notes
2018-02-23 10:40:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PANEL NOTES, NOTE #1 STATES THAT CIRCUITS
 SHOULD BE AFCI PROTECTED UNLESS THEY ARE GFCI
 PROTECTED. THIS IS IN CONFLICT WITH THE CODE, WHICH
 STATES: ?BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED.? SOME
 AREAS WILL HAVE AFCI AND GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 2. ELECTRICAL PANEL NOTES, NOTE #15 STATES THAT
 LIGHTING IN CLOSETS SHALL COMPLY WITH NEC 410.8, WHICH
 DOES NOT APPLY TO LIGHTING IN CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 3. RISER DIAGRAM SHOWS 2/0 WIRE TO DISCONNECT A, BUT
 3/0 TO ALL OTHER PANELS AND DISCONNECTS. 3/0 IS THE
 CORRECT SIZE, PROVIDE CORRECTION. ALSO, RISER DOES NOT
 SHOW PANEL P. PROVIDE CORRECTION. NEC 215.5,
 310.15(B)(7) AND (B)(15); FBC RE E3603.1, E3705.1; FBC
 107.2.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
 6. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3
 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS FOR ENTIRE SERVICE PER THE FORMAT DESCRIBED IN
 THE FBC RESIDENTIAL. UPSTAIRS WASHER AND DRYER ARE
 MISSING FROM LOAD CALCULATION, MAKE SURE ALL EQUIPMENT
 IS SHOWN. NEC 220; FBC RE E E3602.2
 8. DEMAND FACTORS NOT PERMITTED FOR PANEL P, IT IS LESS
 THAN 100 AMPS IN SIZE. PROVIDE CORRECTION. NEC 220.82;
 FBC RE E3602.2
 9. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE INCLUDING GARAGE DOOR OPENER. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 10. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-30 Cont ID  
Sent By cthroop Date 2018-03-30 Time 13:52 Rev Time 0.00
Received By cthroop Date 2018-03-29 Time 13:22 Sent To I
Notes
2018-03-30 13:22:43RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-23 Cont ID  
Sent By cthroop Date 2018-03-23 Time 13:43 Rev Time 0.00
Received By cthroop Date 2018-03-20 Time 15:31 Sent To I
Notes
2018-03-21 15:31:27RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-14 Cont ID  
Sent By cthroop Date 2018-03-14 Time 12:48 Rev Time 0.00
Received By cthroop Date 2018-02-08 Time 11:27 Sent To I
Notes
2018-02-09 11:27:54R27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-03-30 Cont ID  
Sent By cthroop Date 2018-03-30 Time 13:51 Rev Time 0.00
Received By cthroop Date 2018-03-30 Time 13:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By cthroop Date 2018-03-14 Time 11:38 Rev Time 0.00
Received By cthroop Date 2018-03-08 Time 09:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-28 Cont ID  
Sent By cmontell Date 2018-02-28 Time 14:57 Rev Time 0.00
Received By cmontell Date 2018-02-28 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-07 Cont ID  
Sent By gjohnson Date 2018-03-07 Time 07:33 Rev Time 0.00
Received By gjohnson Date 2018-03-07 Time 07:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By cthroop Date 2018-03-23 Time 13:43 Rev Time 0.00
Received By cthroop Date 2018-03-23 Time 13:18 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By cthroop Date 2018-03-14 Time 11:36 Rev Time 0.00
Received By cthroop Date 2018-03-08 Time 16:13 Sent To  
Notes
2018-03-14 11:38:43BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM
 COMPONENTS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2018-03-02 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-28 Time 15:45 Sent To  
Notes
2018-03-02 09:45:411.) LANDSCAPE PERMIT REQUIRED PRIOR TO ISSUANCE OF C.O.
  