| 2018-02-23 10:40:37 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL PANEL NOTES, NOTE #1 STATES THAT CIRCUITS |
| | SHOULD BE AFCI PROTECTED UNLESS THEY ARE GFCI |
| | PROTECTED. THIS IS IN CONFLICT WITH THE CODE, WHICH |
| | STATES: ?BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED.? SOME |
| | AREAS WILL HAVE AFCI AND GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 |
| | 2. ELECTRICAL PANEL NOTES, NOTE #15 STATES THAT |
| | LIGHTING IN CLOSETS SHALL COMPLY WITH NEC 410.8, WHICH |
| | DOES NOT APPLY TO LIGHTING IN CLOSETS. PROVIDE |
| | CORRECTION. NEC 410.16; FBC RE E4003.12 |
| | 3. RISER DIAGRAM SHOWS 2/0 WIRE TO DISCONNECT A, BUT |
| | 3/0 TO ALL OTHER PANELS AND DISCONNECTS. 3/0 IS THE |
| | CORRECT SIZE, PROVIDE CORRECTION. ALSO, RISER DOES NOT |
| | SHOW PANEL P. PROVIDE CORRECTION. NEC 215.5, |
| | 310.15(B)(7) AND (B)(15); FBC RE E3603.1, E3705.1; FBC |
| | 107.2.1 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. FBC 105.1, 107.2.1 |
| | 6. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED. |
| | PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3 |
| | 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS FOR ENTIRE SERVICE PER THE FORMAT DESCRIBED IN |
| | THE FBC RESIDENTIAL. UPSTAIRS WASHER AND DRYER ARE |
| | MISSING FROM LOAD CALCULATION, MAKE SURE ALL EQUIPMENT |
| | IS SHOWN. NEC 220; FBC RE E E3602.2 |
| | 8. DEMAND FACTORS NOT PERMITTED FOR PANEL P, IT IS LESS |
| | THAN 100 AMPS IN SIZE. PROVIDE CORRECTION. NEC 220.82; |
| | FBC RE E3602.2 |
| | 9. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN |
| | GARAGE INCLUDING GARAGE DOOR OPENER. PROVIDE |
| | CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 10. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |