Plan Review Details - Permit 18020319
Plan Review Stops For Permit 18020319
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-19 Cont ID  
Sent By ppetty Date 2018-03-19 Time 10:21 Rev Time 0.00
Received By ppetty Date 2018-03-19 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By ppetty Date 2018-02-14 Time 10:17 Rev Time 0.00
Received By ppetty Date 2018-02-14 Time 10:17 Sent To  
Notes
2018-02-14 10:18:10PLEASE SEE F/D NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By pleduc Date 2018-03-12 Time   Rev Time 0.00
Received By pleduc Date 2018-03-09 Time 15:28 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By pleduc Date 2018-02-09 Time   Rev Time 0.00
Received By pleduc Date 2018-02-09 Time 10:22 Sent To  
Notes
2018-02-09 12:41:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS FOR THIS PERMIT APPEAR TO BE
 GENERAL DOCUMENTS OF THE ENTIRE PROJECT. THE
 APPLICATION STATES FOR BUILDING # 4, 805 15TH ST;
 HOWEVER, IT APPEARS TO BE OF ALL THE BUILDINGS IN THIS
 PROJECT.
  
  
 PER NFPA 1
 1.7.12.3 THE CONSTRUCTION DOCUMENTS FOR EACH PHASE
 SHALL BE COMPLETE IN THEMSELVES, SO THAT REVIEW AND
 INSPECTION CAN PROPERLY BE MADE. PRELIMINARY PLANS OF
 THE TOTAL BUILDING SHALL BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS, AND WITH SUFFICIENT DETAIL, SO
 THAT PROPER EVALUATION CAN BE MADE. AREAS AND ITEMS NOT
 INCLUDED IN THE PHASE TO BE PERMITTED SHALL BE SHOWN AS
 NOT INCLUDED.
  
 PER NFPA 72
  
 7.4.4 SHOP DRAWINGS SHALL INCLUDE THE FOLLOWING
 INFORMATION:
 (1) NAME OF PROTECTED PREMISES, OWNER, AND OCCUPANT
 (WHERE APPLICABLE)
 (2) NAME OF INSTALLER OR CONTRACTOR
 (3) LOCATION OF PROTECTED PREMISES
  
  
 EACH SUBMITTED PLAN SHALL BE SPECIFIC TO THE BUILDING
 THAT IT REPRESENTS.
  
  
  
 2) THE SUBMITTED PLANS DO NOT INCLUDE THE CORRECT
 ADDRESS AS REFLECTED ON THE APPLICATION.
  
 THE ADDRESS ON THE APPLICATION IS 805 15TH ST. THE
 ADDRESS ON THE SUBMITTED PLANS IS 808 17TH ST.
  
 PER NFPA 72
  
 7.4.4 SHOP DRAWINGS SHALL INCLUDE THE FOLLOWING
 INFORMATION:
  
 (3) LOCATION OF PROTECTED PREMISES
  
 PLEASE PROVIDE THE CORRECT ADDRESS OF THE CORRECT
 BUILDING ON THE SUBMITTED SET OF PLANS.
  
  
  
 3) SHEET FA 1.00 - THE IS ONLY ONE FACP AND FAAP FOR
 FOUR BUILDINGS. THERE SHOULD BE ONE FACP AND 4 FAAP;
 ONE FOR EACH BUILDING.
  
 PER NFPA 72
  
 10.18.3* ANNUNCIATOR ACCESS AND LOCATION.
 10.18.3.1 ALL REQUIRED ANNUNCIATION MEANS SHALL BE
 READILY ACCESSIBLE TO RESPONDING PERSONNEL.
 10.18.3.2 ALL REQUIRED ANNUNCIATION MEANS SHALL BE
 LOCATED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION TO FACILITATE AN EFFICIENT RESPONSE TO THE
 SITUATION.
  
 10.18.5.3 WHERE THE SYSTEM SERVES MORE THAN ONE
 BUILDING, EACH BUILDING SHALL BE ANNUNCIATED
 SEPARATELY.
  
 IT IS RECOMMENDED THAT THE FAAP BE LOCATED WITHIN THE
 ELECTICAL ROOMS ON THE 1ST FLOOR OR AT ANOTHER
 ACCEPTABLE (FOYER AREA) AND AGREEABLE LOCATION.
  
  
  
 4) SHEET FA 1.00 - THERE IS AN INDICATION THAT THE
 ALARM CAN ONLY BE RESET AT THE FACP
  
 IT IS RECOMMENDED AND IF POSSIBLE, THAT THE SYSTEM CAN
 BE SILENCED AND RESET FROM EACH FAAP.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-19 Cont ID  
Sent By ppetty Date 2018-03-19 Time 10:21 Rev Time 0.00
Received By ppetty Date 2018-03-07 Time 13:09 Sent To  
Notes
2018-03-08 13:09:46RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-14 Cont ID  
Sent By hmoser Date 2018-02-14 Time 12:47 Rev Time 0.00
Received By hmoser Date 2018-02-07 Time 14:18 Sent To  
Notes
2018-02-08 14:18:55ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-02-14 Cont ID  
Sent By hmoser Date 2018-02-14 Time 12:47 Rev Time 0.00
Received By hmoser Date 2018-02-14 Time 12:46 Sent To I
Notes
***NONE***