Plan Review Details - Permit 18020313
Plan Review Stops For Permit 18020313
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-13 Cont ID  
Sent By skennedy Date 2018-08-13 Time 15:48 Rev Time 0.00
Received By skennedy Date 2018-08-13 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 11:42 Rev Time 0.00
Received By shill Date 2018-04-30 Time 11:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-12 Cont ID  
Sent By cthroop Date 2018-03-12 Time 07:10 Rev Time 0.00
Received By cthroop Date 2018-03-09 Time 15:49 Sent To  
Notes
2018-03-12 07:14:34BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE WINDOW AND DOOR SCHEDULE.
 2. PROVIDE DESIGN WIND LOADS FOR PROPOSED OPENINGS.
 3. PROVIDE PRO9DUCT APPROVALS FO0R PROPOSED WINDOWS AND
 DOORS.
 4. VALUE APPEARS LOW.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By ppetty Date 2018-07-24 Time 14:27 Rev Time 0.00
Received By ppetty Date 2018-07-24 Time 14:27 Sent To  
Notes
2018-07-24 14:27:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK,.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 09:34 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 08:49 Sent To  
Notes
2018-07-24 14:22:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK,.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  
  
2018-04-30 09:19:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE SMOKE ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1 (A SMOKE ALARM IS REQUIRED ON EACH
 STORY OF THE DWELLING, NONE IS SHOWN ON THE LOWER
 LEVEL. PROVIDE CORRECTION.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE GFCI RECEPTACLE OUTLET FOR BALCONIES. NEC
 210.52(E)(3) (NOT PROVIDED. PER CODE: BALCONIES, DECKS,
 AND PORCHES THAT ARE ATTACHED TO THE DWELLING UNIT AND
 ARE ACCESSIBLE FROM INSIDE THE DWELLING UNIT SHALL HAVE
 AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE FROM THE
 BALCONY, DECK, OR PORCH. PROVIDE CORRECTION.)
 7. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902 (NOT PROVIDED.)
 8. CORRECTED.
  
 NEW COMMENT:
  
 9. GFCI RECEPTACLE OUTLET PROVIDED ON PENINSULA APPEARS
 TO BE UNDER AN OVERHANG THAT EXTENDS MORE THAN 6 INCHES
 FROM ITS SUPPORT BASE. WHILE A RECEPTACLE IS PERMITTED
 IN THIS LOCATION, IT DOES NOT FULFILL CODE REQUIREMENT
 FOR THE PENINSULA. PROVIDE CORRECTION. NEC 210.52(C)(5)
 10. PLEASE BE ADVISED THAT SOME COMMENTS HAVE NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-26 Cont ID  
Sent By jpearson Date 2018-02-26 Time 15:57 Rev Time 0.00
Received By jpearson Date 2018-02-26 Time 14:28 Sent To  
Notes
2018-02-26 15:57:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. VALUE OF WORK APPEARS LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR. FBC 109.3
 3. PROVIDE SMOKE ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
 4. PROVIDE CORRECTION FOR NOTE 18 TO INCLUDE: ?BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? NEC 210.12; FBC RE E3902.16
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE GFCI RECEPTACLE OUTLET FOR BALCONIES. NEC
 210.52(E)(3)
 7. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 8. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 10:27 Rev Time 0.00
Received By jesmith Date 2018-08-30 Time 10:27 Sent To  
Notes
2018-09-04 11:29:56APPROVED BY
 JERALD SMITH 0017-P
 PLUMBING PLANS EXAMINER
 561-805- 6711
2018-08-30 10:20:29APPROVED

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 12:11 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 12:11 Sent To  
Notes
2018-04-26 12:11:401ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. THE TANKLESS HEATER SHALL BE MOUNTED A MIN OF 4'
 FROM ANY OPENING IN BUILDING. PER MANUFACTURE SPEC
  
 3. SHOW ON THE RISER THE LENGTH OF EACH CUT SECTION OF
 PIPE FROM METER TO MOST REMOTE APPLIANCE. FBC-2017 FUEL
 GAS, SECS. 402.4.1, 402.4.2.
  
 4. THE TANKLESS WATER HEATER IS NOT SHOWN ON THE GAS
 RISER IT IS SHOWN ON SHT A-1 NEXT TO THE AC UNITS
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE SHOW METER ON THE FLOOR PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-03-03 Cont ID  
Sent By gjohnson Date 2018-03-03 Time 07:10 Rev Time 0.00
Received By gjohnson Date 2018-03-03 Time 07:10 Sent To  
Notes
2018-03-03 07:11:22GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By fmittner Date 2018-05-02 Time 13:25 Rev Time 0.00
Received By fmittner Date 2018-05-02 Time 13:25 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-02-13 Cont ID  
Sent By fmittner Date 2018-02-13 Time 15:58 Rev Time 0.00
Received By fmittner Date 2018-02-13 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 10:47 Rev Time 0.00
Received By shill Date 2018-07-11 Time 16:16 Sent To  
Notes
2018-07-12 16:16:53R15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-02 Cont ID  
Sent By cpuell Date 2018-05-02 Time 14:05 Rev Time 0.00
Received By cpuell Date 2018-04-13 Time 14:05 Sent To  
Notes
2018-04-16 14:07:16R08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-12 Cont ID  
Sent By cthroop Date 2018-03-12 Time 07:14 Rev Time 0.00
Received By cthroop Date 2018-02-07 Time 10:47 Sent To I
Notes
2018-02-08 10:47:30R02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2018-08-13 Cont ID  
Sent By skennedy Date 2018-08-13 Time 16:03 Rev Time 0.00
Received By skennedy Date 2018-08-13 Time 16:03 Sent To  
Notes
2018-08-13 16:04:42THERE IS NO MECHANICAL WORK SHOWN EXCEPT THE
 INSTALLATION OF AN ADDITIONAL CU. ANY/ALL MECHANICAL
 SHALL BE BY SEPARATE SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-17 Cont ID  
Sent By cmontell Date 2018-04-17 Time 14:08 Rev Time 0.00
Received By cmontell Date 2018-04-17 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-03-07 Cont ID  
Sent By cmontell Date 2018-03-07 Time 15:09 Rev Time 0.00
Received By cmontell Date 2018-03-07 Time 15:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 10:14 Rev Time 0.00
Received By jesmith Date 2018-08-30 Time 10:14 Sent To  
Notes
2018-09-04 11:30:57APPROVED BY
 JERALD SMITH 0017-P
 PLUMBING PLANS EXAMINER
 561-805- 6711
2018-08-30 10:17:49PLANS APPROVED FOR PERMIT, HOWEVER, THE KITCHEN SINK
 WAS INADVERTENTLY LEFT OFF OF THE SANITARY ISOMETRIC.
 PROVIDE REVISED SANITARY ISOMETRIC TO SHOW KITCHEN SINK
 AND SUBMIT
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 10:52 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 06:03 Sent To  
Notes
2018-04-26 11:41:032ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-1 THE NOTE ON THE PLUMBING RISER STATING THE
 PLUMBING LAYOUT WILL BE SUBMITTED AFTER THE
 INSTALLATION WILL NOT COMPLY IN ORDER FOR A PLUMBING
 PERMIT TO BE ISSUED A CODE COMPLIANT SANITARY ISOMETRIC
 SHALL BE SUBMITTED AND APPROVED. 107.3.5.3(12)
  
 2. SHT. A-1 THE SANITARY ISOMETRIC PLEASE CORRECT THE
 FOLLOWING
 A) THE WASTE STACK FOR THE 2ND FLOOR MASTERBATH
 LAVATORY'S, TUB AND WASHING MACHINE SHALL CONNECT TO
 THE BUILDING DRAIN SEPARATELY FROM THE POWDER ROOM BATH
 WET VENT.
 B) THE WASHING MACHINE BRANCH DRAIN SHALL CONNECT TO
 THE WASTE STACK DOWN STREAM OF THE LAVATORY'S AND TUB.
 C) THE POWDER ROOM TOILET SHALL BE VENTED BY THE
 LAVATORY STACK BEFORE CONNECTING TO THE BUILDING DRAIN.
 PER FBC RES P3108.1
  
 3. SHT. A-1 PLACE NOTE ON PLAN SHUT OFF VALVES FOR THE
 STACKABLE WASHING MACHINE SHALL BE ACCESSIBLE. PER FBC
 PL P2903.9.3
  
 4. THE PLUMBING AND GENERAL CONTRACTORS WORKMENS COMP
 INS AND LIBILITY INS NEEDS TO BE UPDATED WITH THE CITY
 OF WPB BEFORE A PERMITS CAN BE ISSUED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-03 Cont ID  
Sent By gjohnson Date 2018-03-03 Time 07:11 Rev Time 0.00
Received By gjohnson Date 2018-03-02 Time 11:00 Sent To  
Notes
2018-03-03 07:26:291ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. A CODE COMPLIANT RISER DIAGRAM IS REQUIRED ON A
 RESIDENTIAL SET OF PLANS FOR APPROVAL. PER WPB AMEND TO
 FBC 107.3.5.3(11)
  
 2.THE WATER CLOSET IN THE POWDER-ROOM IS NOT VENTED IT
 SHALL BE VENTED AS A WET VENT BY THE LAVATORY WITH A
 SEPARATE VENT THRU 2ND FLOOR OR BE INDIVIDUAL DRY VENT.
 PER FBC RES P3106.1, P3108.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By fmittner Date 2018-05-02 Time 13:25 Rev Time 0.00
Received By fmittner Date 2018-05-02 Time 13:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-02-13 Cont ID  
Sent By fmittner Date 2018-02-13 Time 15:58 Rev Time 0.00
Received By fmittner Date 2018-02-13 Time 15:58 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved