| 2018-09-03 14:02:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | NOTE: NO RESPONSE WAS PROVIDED FOR ELECTRICAL COMMENTS. |
| | SHEETS E101 AND E102 IN SET DO NOT MATCH ANY SHEETS IN |
| | ORIGINAL PLAN, THEREFORE NO REVISION FOR THESE SHEETS |
| | IS POSSIBLE. IF A REVISION IS DESIRED, THE ORIGINAL |
| | SHEETS MUST BE PROVIDED WITH CHANGES TO THE PLAN |
| | CLOUDED AND EXPLAINED. COMMENTS FROM FIRST REVIEW BELOW |
| | NEED TO BE ADDRESSED. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. RISER PROVIDED ONLY SHOWS |
| | ONE METER CAN, BUT THERE ARE 6 UNITS AND A HOUSE PANEL |
| | ON THE ORIGINAL PLANS. PROVIDE ACCURATE RISER DIAGRAM. |
| | NEC 215.5, 230, 250.50, 250.94, 408.30 |
| | 2. CURRENT RISER PROVIDED SHOWS THE METER CAN FEEDING |
| | AN INTERIOR MAIN LUG ONLY PANEL. PROVIDE A MEANS OF |
| | DISCONNECT PER CODE, WITH A MAXIMUM OF SIX DISCONNECTS |
| | AT ONE LOCATION. NEC 230.70, 230.71 |
| | 3. SHOW LOCATION OF SUB-PANELS IN EACH UNIT. FBC |
| | 107.2.1; NEC 240.24 |
| | 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 5. PROVIDE ACCURATE LOAD CALCULATION FOR EACH UNIT. |
| | THIS SHOULD INCLUDE 2 SMALL APPLIANCE CIRCUITS AND THE |
| | WATER HEATER, WHICH IS NOT SHOWN. THERE IS A DRYER |
| | LISTED IN THE PANEL SCHEDULE, BUT I DO NOT SEE A DRYER |
| | ON PLAN. CLARIFY AND/OR CORRECT NEC 220; FBC 107.2.1 |
| | 6. SHOW LOCATION OF SERVICE ON FLOOR PLAN. FBC 107.2.1 |
| | 7. SHOW LOCATION OF MECHANICAL EQUIPMENT ON PLAN WITH |
| | REQUIRED GFCI RECEPTACLE FOR SERVICING OF EQUIPMENT. |
| | NEC 210.63; FBC 107.2.1 |
| | 8. RECEPTACLE OUTLETS FOR THE KITCHEN COUNTERTOP ARE |
| | REQUIRED TO BE ON AT LEAST TWO 20 AMP CIRCUITS AND |
| | THESE CIRCUITS CANNOT FEED OTHER AREAS. PROVIDE |
| | CORRECTION. NEC 210.11(C)(1), 210.52(B) |
| | 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12 |
| | 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 |
| | 13. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 14. PROVIDE PANEL SCHEDULE FOR EACH PANEL INCLUDING THE |
| | HOUSE PANEL, INDICATING ANY NEW OR ALTERED CIRCUITS, |
| | THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI |
| | OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH |
| | CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |