Plan Review Details - Permit 18020271
Plan Review Stops For Permit 18020271
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-22 Cont ID  
Sent By jwitmer Date 2018-09-22 Time 15:53 Rev Time 0.00
Received By shill Date 2018-09-22 Time 15:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-23 Cont ID  
Sent By jwitmer Date 2018-02-23 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2018-02-23 Time 06:02 Sent To  
Notes
2018-02-23 07:10:16BUILDING PLAN REVIEW
 W. P. B. REVISION: 18020271
 W. P. B. PERMIT: 16060021
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 23/ 2018
 ACTION: DENIED
  
 HISTORIC 2 STORY R-2 APARTMENT BUILDING
  
 1) IT WOULD APPEAR THE PLAN SUBMITTED FOR THIS REVIEW
 SHOULD HAVE A LETTER FOR SUCCESSOR ARCHITECT ATTACHED
 NOTIFYING THE ORIGINAL ARCHITECT. 61G1-18.002(2)
 PROCEDURES FOR A SUCCESSOR ARCHITECT ADOPTING AS HIS
 OWN THE WORK OF ANOTHER ARCHITECT.
  
 2) SHEET A201 & A202 HAS SEVERAL REFERENCES TO THE
 FBC-RESIDENTIAL CODE ALTHOUGH THE TITLE BLOCK INDICATES
 THIS PERMIT IS FOR RENOVATIONS TO AN APARTMENT
 BUILDING.
 2A) FLOOR PLAN NOTE 8 REFERENCES THE RESIDENTIAL CODE.
 2B) APPLICABLE CODES REFERENCES THE RESIDENTIAL CODE.
 2C) EGRESS NOTES 1 & 2 BOTH REFERENCE THE RESIDENTIAL
 CODE.
  
 3) WINDOW NOTE # 3 REFERENCES ALL SINGLE HUNG WINDOWS
 IN BEDROOMS ARE TO BE CONSIDERED FOR EGRESS WINDOWS.
 PLEASE REVIEW UNDER THE 2014 FBC-B SECTION:
 3A) 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7
 SQUARE FEET .
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR
 GRADE-FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL
 BE 5 SQUARE FEET .
  
 3B) 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET CLEAR
 OPENING HEIGHT DIMENSION SHALL BE 24 INCHES. THE
 MINIMUM NET CLEAR OPENING WIDTH DIMENSION SHALL BE 20
 INCHES. THE NET CLEAR OPENING DIMENSIONS SHALL BE THE
 RESULT OF NORMAL OPERATION OF THE OPENING.
  
 4) NOTICE ONLY!!!! THE ARCHITECT STATES THE
 REQUIREMENTS FOR FLOOR SOUND INSULATION, TO DATE THE
 CONTRACTOR HAS NOT SUBMITTED ACTUAL TEST REPORTS FOR
 COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-03 Cont ID  
Sent By jpearson Date 2018-09-03 Time 14:04 Rev Time 0.00
Received By jpearson Date 2018-09-03 Time 14:04 Sent To  
Notes
2018-09-03 14:02:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NOTE: NO RESPONSE WAS PROVIDED FOR ELECTRICAL COMMENTS.
 SHEETS E101 AND E102 IN SET DO NOT MATCH ANY SHEETS IN
 ORIGINAL PLAN, THEREFORE NO REVISION FOR THESE SHEETS
 IS POSSIBLE. IF A REVISION IS DESIRED, THE ORIGINAL
 SHEETS MUST BE PROVIDED WITH CHANGES TO THE PLAN
 CLOUDED AND EXPLAINED. COMMENTS FROM FIRST REVIEW BELOW
 NEED TO BE ADDRESSED.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. RISER PROVIDED ONLY SHOWS
 ONE METER CAN, BUT THERE ARE 6 UNITS AND A HOUSE PANEL
 ON THE ORIGINAL PLANS. PROVIDE ACCURATE RISER DIAGRAM.
 NEC 215.5, 230, 250.50, 250.94, 408.30
 2. CURRENT RISER PROVIDED SHOWS THE METER CAN FEEDING
 AN INTERIOR MAIN LUG ONLY PANEL. PROVIDE A MEANS OF
 DISCONNECT PER CODE, WITH A MAXIMUM OF SIX DISCONNECTS
 AT ONE LOCATION. NEC 230.70, 230.71
 3. SHOW LOCATION OF SUB-PANELS IN EACH UNIT. FBC
 107.2.1; NEC 240.24
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 5. PROVIDE ACCURATE LOAD CALCULATION FOR EACH UNIT.
 THIS SHOULD INCLUDE 2 SMALL APPLIANCE CIRCUITS AND THE
 WATER HEATER, WHICH IS NOT SHOWN. THERE IS A DRYER
 LISTED IN THE PANEL SCHEDULE, BUT I DO NOT SEE A DRYER
 ON PLAN. CLARIFY AND/OR CORRECT NEC 220; FBC 107.2.1
 6. SHOW LOCATION OF SERVICE ON FLOOR PLAN. FBC 107.2.1
 7. SHOW LOCATION OF MECHANICAL EQUIPMENT ON PLAN WITH
 REQUIRED GFCI RECEPTACLE FOR SERVICING OF EQUIPMENT.
 NEC 210.63; FBC 107.2.1
 8. RECEPTACLE OUTLETS FOR THE KITCHEN COUNTERTOP ARE
 REQUIRED TO BE ON AT LEAST TWO 20 AMP CIRCUITS AND
 THESE CIRCUITS CANNOT FEED OTHER AREAS. PROVIDE
 CORRECTION. NEC 210.11(C)(1), 210.52(B)
 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 13. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 14. PROVIDE PANEL SCHEDULE FOR EACH PANEL INCLUDING THE
 HOUSE PANEL, INDICATING ANY NEW OR ALTERED CIRCUITS,
 THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI
 OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 210.12, 215.5, 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By jpearson Date 2018-02-28 Time 15:53 Rev Time 0.00
Received By jpearson Date 2018-02-28 Time 15:53 Sent To I
Notes
2018-02-28 15:53:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. RISER PROVIDED ONLY SHOWS
 ONE METER CAN, BUT THERE ARE 6 UNITS AND A HOUSE PANEL
 ON THE ORIGINAL PLANS. PROVIDE ACCURATE RISER DIAGRAM.
 NEC 215.5, 230, 250.50, 250.94, 408.30
 2. CURRENT RISER PROVIDED SHOWS THE METER CAN FEEDING
 AN INTERIOR MAIN LUG ONLY PANEL. PROVIDE A MEANS OF
 DISCONNECT PER CODE, WITH A MAXIMUM OF SIX DISCONNECTS
 AT ONE LOCATION. NEC 230.70, 230.71
 3. SHOW LOCATION OF SUB-PANELS IN EACH UNIT. FBC
 107.2.1; NEC 240.24
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 5. PROVIDE ACCURATE LOAD CALCULATION FOR EACH UNIT.
 THIS SHOULD INCLUDE 2 SMALL APPLIANCE CIRCUITS AND THE
 WATER HEATER, WHICH IS NOT SHOWN. THERE IS A DRYER
 LISTED IN THE PANEL SCHEDULE, BUT I DO NOT SEE A DRYER
 ON PLAN. CLARIFY AND/OR CORRECT NEC 220; FBC 107.2.1
 6. SHOW LOCATION OF SERVICE ON FLOOR PLAN. FBC 107.2.1
 7. SHOW LOCATION OF MECHANICAL EQUIPMENT ON PLAN WITH
 REQUIRED GFCI RECEPTACLE FOR SERVICING OF EQUIPMENT.
 NEC 210.63; FBC 107.2.1
 8. RECEPTACLE OUTLETS FOR THE KITCHEN COUNTERTOP ARE
 REQUIRED TO BE ON AT LEAST TWO 20 AMP CIRCUITS AND
 THESE CIRCUITS CANNOT FEED OTHER AREAS. PROVIDE
 CORRECTION. NEC 210.11(C)(1), 210.52(B)
 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 13. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 14. PROVIDE PANEL SCHEDULE FOR EACH PANEL INCLUDING THE
 HOUSE PANEL, INDICATING ANY NEW OR ALTERED CIRCUITS,
 THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI
 OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 210.12, 215.5, 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By destabro Date 2018-08-21 Time 15:48 Rev Time 0.00
Received By destabro Date 2018-08-21 Time 15:48 Sent To I
Notes
2018-08-21 15:49:328/21/2018 - APPROVAL PROVISO - GRAY TINTED GLASS NOT
 PERMITTED; LOW-E COATING ALLOWED.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By destabro Date 2018-02-15 Time 15:00 Rev Time 0.00
Received By destabro Date 2018-02-15 Time 15:00 Sent To B
Notes
2018-02-15 15:01:012/15/2018 - STILL MEETS CONDITIONS OF HPB APPROVAL CASE
 NO.15-64. DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 15:53 Rev Time 0.00
Received By shill Date 2018-08-15 Time 14:49 Sent To  
Notes
2018-08-16 14:49:32C15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-02-28 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-07 Time 14:34 Sent To  
Notes
2018-02-08 14:34:16C20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-09-07 Cont ID  
Sent By ccole Date 2018-09-07 Time 16:22 Rev Time 0.00
Received By ccole Date 2018-09-07 Time 16:14 Sent To  
Notes
2018-09-07 16:22:33NO MECHANICAL PLANS SUBMITTED.
 CCOLE- 9/7/18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 08:55 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 08:52 Sent To  
Notes
2018-02-28 08:57:051ST REVIEW FBC-2014 MECHANICAL
 PERMIT REVISION #18020271
 MASTER # 16030064
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO REVISED MECHANICAL PLAN SHEETS WERE SUBMITTED FOR
 REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  