| 2018-02-16 14:43:10 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18020262 |
| | ADD: 7437 RIVERWALK CIRCLE |
| | CONT: EVERKLEEN CONSTRUCTION |
| | TEL: 561-818-7082 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. FEB. 16/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) DISCREPANCY IN OCCUPANT LOAD. THE COVERSHEET STATES |
| | THERE IS 94 SEATING CAPACITY. SHEET 1.3A INDICATES A |
| | SEATING COUNT OF NON-FIXED SEATING 53 AND BENCH SEATING |
| | OF 22 TOTALING 75 SEATS. WHEN TAKING A COUNT OF ALL |
| | SEATING INCLUDING ACCESSIBLE SEATING THE COUNT IS 97 |
| | SEATED OCCUPANTS. PLEASE ALSO SEE THE DISCREPANCY IN |
| | THE RETAIL CAF? TAKEN AT 30. UNDER THE 2017 FBC-B |
| | MERCANTILE 1ST FLOOR IS NOW TO BE TAKEN AT 60 SQ. FT./ |
| | OCCUPANT (SEE 2017 FBC-B TABLE 1004.1.2.). THIS WILL |
| | DECREASE THE OCCUPANT LOAD. PLEASE PROVIDE A REVISED |
| | OCCUPANT LOAD COUNT ON THE COVERSHEET AS WELL AS ON |
| | SHEET 1.3A. |
| | |
| | 2) THE COVERSHEET UNDER THE SCOPE OF WORK INDICATES |
| | WITH NOTE # 17 TO REMOVE A PAIR OF GLASS ALUMINUM DOORS |
| | AND REPLACE WITH A NEW SINGLE IMPACT UNIT TO WITHSTAND |
| | 170 PSF. NOTE # 18 STATES TO BLOCK IN ? OF THE DOOR |
| | OPENING. SHEETS 1.1A, 1.21A NOR 1.3.A SHOW THE REMOVAL |
| | OF DOORS, NOR THE INSTALLATION OF A NEW SINGLE DOOR AND |
| | ? OF THE OLD OPENING BLOCKED IN. THERE IS NO DETAIL |
| | PROVIDING HOW THE NEW WALL SECTION WOULD BE ANCHORED |
| | INTO THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) |
| | CONTENTIOUS LOADING TO THE FOUNDATION. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. FBC-B 1609.6.3/ |
| | 1609.6.4. |
| | |
| | 3) MISSING THE WIND DESIGN CRITERIA. 2014 FBC-B |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 3.2. RISK CATEGORY. |
| | |
| | 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 4) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS, SIDELIGHTS & TRANSOMS |
| | |
| | 5) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | 6) PLEASE SHOW COMPLIANCE WITH ACCESSIBLE DINING |
| | TABLES; |
| | 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |