Plan Review Details - Permit 18020254
| Plan Review Stops For Permit 18020254 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-16 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-16 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2018-05-16 17:54:52 | APPROVED WITH EXCEPTIONS AND PROVISOS. | | | | | | 1) ON SHEET 067-A-305 SECTION 2/A-3.05, THE 12" | | | HORIZONTAL HANDRAIL EXTENSION IS REQUIRED TO RETURN TO | | | A WALL, GUARD OR THE LANDING AT THE BOTTOM OF THE RAMP | | | PER FBC ACCESSIBILITY SECTION 505.10.1. | | | | | | 2) PROVISO/ DEFERRED SUBMITTAL. SUBMIT TWO SETS OF | | | MANUFACTURER'S SPECIFICATIONS AND LISTING INFORMATION | | | FOR REVIEW FOR THE LULA LIFT AT THE ENTRY PORT COCHERE. | | | | | | 3) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR | | | STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM, | | | HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE | | | DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS | | | THE HARDWARE MEET COMPLIANCE WITH : | | | 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE. | | | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE | | | PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4. | | | OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES | | | MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN | | | POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND | | | USABLE FROM BOTH SIDES. | | | | | | 4) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A | | | SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND | | | CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION | | | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE | | | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 5) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 6) SEPARATE PERMITS REQUIRED. THE POOL, GENERATOR, | | | KITCHEN HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE | | | SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION | | | PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT | | | AND REQUIRE SEAPARTE PERMITS, PLAN REVIEWS AND FEES. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-05-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-10 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-07 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2018-05-10 14:09:27 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 18020254 | | | ADD: 1675 PALM BEACH LAKES BLVD. | | | CONT: STRATICON LLC | | | TEL: 772-210-0200 STRATICON | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | | | | 3RD REVIEW | | | DATE: WED. APRIL 04/ 2018 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | | | | 1A) COMPLIED. | | | | | | 1B) COMPLIED. | | | | | | 1C) COMPLIED. | | | | | | 1D) COMPLIED. | | | | | | 1E) COMPLIED. | | | | | | 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING | | | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE | | | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND | | | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED | | | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM | | | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOB SITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING | | | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT | | | THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 2) SHEET 042-LS-111 & 045-A-111: | | | | | | 2A-2E) COMPLIED. | | | * NEW COMMENT. | | | 1) THE OCCUPANT LOAD FOR THE 550 SQ.FT.EXERCISE ROOM IS | | | INCORRECTLY LISTED AS 6. USING THE OCCUPANT LOAD FACTOR | | | OF 50 GROSS FROM TABLE 1004.1.2 FOR EXERCISE ROOMS THE | | | TOTAL OCCUPANTS WILL BE 11. | | | | | | 2F) COMPLIED. | | | | | | 2G-2K) COMPLIED. | | | | | | | | | 2L) SEMI-COMPLIED. THE LAUNDRY CHUTE DETAIL (6/A-5.02) | | | ON SHEET 5.02 SHOWS FIRE SPRINKLER HEADS IN THE SHAFT. | | | THESE ARE NOT SHOWN ON THE FIRE SPRINKLER PLANS. PLEASE | | | CLARIFY. 903.2.11.2 | | | | | | 2M) COMPLIED. | | | | | | 2N) COMPLIED. | | | | | | 2O-Q) COMPLIED. | | | | | | 2R) COMPLIED. | | | | | | 2S) COMPLIED. | | | | | | 2T) COMPLIED. | | | | | | 2T)(2) COMPLIED. | | | | | | 2U) PROVISO, NOTICE ONLY! POOL, GENERATOR, KITCHEN | | | HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE | | | SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION | | | PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT | | | AND ALL REQUIRE A SEPARATE REVIEW AND FEE. | | | | | | 2V)COMPLIED. | | | | | | 2W) PARTIAL COMPLIANCE. SHEET 005-GN-1 BUILDING CODE | | | SUMMARY INDICATES THE PLANS WERE DEVELOPED A | | | CONSTRUCTION TYPE II-A, THIS ONLY ALLOWS UNDER THE 2014 | | | CODE TABLE 503 A 4 STORY BUILDING WITH ONE STORY | | | INCREASE, IT WOULD BE REQUIRED TO BE A CONSTRUCTION | | | TYPE I-B . UNDER THE 2017 FBC-B TABLE 504.4 THE | | | BUILDING TYPE WOULD ALSO BE REQUIRED TO BE I-B | | | ALLOWABLE 12 STORIES WITH A FULL NFPA 13 SYSTEM, UNDER | | | THE 2017 WITH FIRE SPRINKLERS A LL-A BUILDING IS ONLY | | | ALLOWED TO BE 5 STORIES. SHEET 006-GN2 HAS TWO ERRORS | | | THAT I CLOUDED IN RED. | | | | | | 2X) COMPLIED. R-1 TRANSIENT A STAY30 DAYS OR LESS, SEE | | | FBC-B 310.3 & 310.4. | | | | | | 2Y)3RD REQUEST. SHEETS 042-ALS-111 NOR SHEET | | | 045-A-111-A SHOW THE LOCATION OF THE FIRE PUMP | | | LOCATION. SHEET E-101 SHOWS THE FIRE PUMP IN THE | | | MECHANICAL/ ELECTRICAL ROOM 127. PLEASE SHOW COMPLIANCE | | | WITH: | | | 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL | | | BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH | | | SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS. | | | FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED | | | FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE | | | BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR | | | 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE | | | WITH SECTION 711, OR BOTH. | | | EXCEPTIONS: | | | 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY | | | 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED | | | IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE | | | PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | | 903.3.1.1 OR 903.3.1.2. | | | | | | 3) SHEET 046-A-111-B: | | | | | | 3A) 3RD REQUEST. THE COVERED ENTRY PORT COCHERE SHOWS | | | THE USE OF A LULA LIFT, PLEASE PROVIDE CONFIRMATION THE | | | LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION | | | ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1 | | | REFERENCED STANDARDS. NOTE: MANUFACTURER'S | | | SPECIFICATIONS AND LISTING INFORMATION WILL HAVE TO BE | | | SUBMITTED FOR REVIEW. | | | | | | 3B) COMPLIED.(SUBJECT TO FIRE DEPARTMENT AND ELECTRICAL | | | APPROVAL) 2ND REQUEST. SHEET 046-A-111-B SHOWS A NEW | | | FIRE COMMAND ROOM. | | | [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND | | | EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY | | | WITH SECTIONS 403.4.1 THROUGH 403.4.8. | | | | | | 3C) [F]403.4.1 SMOKE DETECTION. SMOKE DETECTION SHALL | | | BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.1. | | | | | | 3D) [F]403.4.2 FIRE ALARM SYSTEM. A FIRE ALARM SYSTEM | | | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13. | | | | | | 3E) [F]403.4.3 STANDPIPE SYSTEM. A HIGH-RISE BUILDING | | | SHALL BE EQUIPPED WITH A STANDPIPE SYSTEM AS REQUIRED | | | BY SECTION 905.3. | | | | | | 3F) [F]403.4.4 EMERGENCY VOICE/ALARM COMMUNICATION | | | SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM | | | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2. | | | | | | 3G) [F]403.4.5 EMERGENCY RESPONDER RADIO COVERAGE. | | | EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN | | | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. | | | | | | 3H) [F]403.4.6 FIRE COMMAND. A FIRE COMMAND CENTER | | | COMPLYING WITH SECTION 911 SHALL BE PROVIDED IN A | | | LOCATION APPROVED BY THE FIRE DEPARTMENT. | | | | | | 3I) COMPLIED, (SUBJECT TO FIRE DEPARTMENT AND | | | MECHANICAL APPROVAL). 2ND REQUEST. 403.4.7 SMOKE | | | REMOVAL. TO FACILITATE SMOKE REMOVAL IN POST-FIRE | | | SALVAGE AND OVERHAUL OPERATIONS, BUILDINGS AND | | | STRUCTURES SHALL BE EQUIPPED WITH NATURAL OR MECHANICAL | | | VENTILATION FOR REMOVAL OF PRODUCTS OF COMBUSTION IN | | | ACCORDANCE WITH ONE OF THE FOLLOWING: | | | 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR | | | PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF | | | EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM) | | | INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL | | | BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR | | | FEET (15 240 MM) OF PERIMETER. | | | | | | EXCEPTIONS: | | | 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE | | | HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE | | | PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA | | | IN LIEU OF THE AREA SPECIFIED IN ITEM 1. | | | 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT | | | GLAZING CAN BE CLEARED BY FIRE FIGHTERS. | | | 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE | | | EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA | | | INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED | | | DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER | | | PORTIONS OF THE BUILDING. | | | 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE | | | EQUIVALENT RESULTS. | | | | | | 3J) COMPLIED. | | | | | | 3K) COMPLIED. | | | | | | 4A-D) COMPLIED. MATRIX PROVIDING THE TOTAL AMOUNT OF | | | SLEEPING ROOMS ACCESSIBILITY. | | | *NEW COMMENTS: | | | 1) ON SHEETS A-121 AND A-131 THE TOTAL OF REQUIRED | | | COUNT OF ROOMS WITH MOBILITY FEATURES IS LISTED AS 2 IN | | | THE ACCESSIBLE ROOM MATRIX. BASED ON THE ROOMS THAT ARE | | | LISTED, THE TOTAL WOULD BE 9 RATHER THAN 2. ACTUALLY, | | | ACCORDING TO TABLE 224.2 FOR 151 TO 200 ROOMS IN A | | | TRANSIENT LODGING FACILITY THE MINIMUM NUMBER OF GUEST | | | ROOMS WITH MOBILITY FEATURES IS A TOTAL OF 8. SIX (6) | | | ROOMS WITHOUT ROLL-IN SHOWERS AND TWO (2) WITH ROLL-IN | | | SHOWERS. | | | 2) 224.6.3 BUILDINGS, STRUCTURES, OR FACILITIES | | | LICENSED AS A HOTEL, MOTEL, OR CONDOMINIUM PURSUANT TO | | | CHAPTER 509, F.S. ALL BUILDINGS, STRUCTURES, OR | | | FACILITIES LICENSED AS A HOTEL, MOTEL, OR CONDOMINIUM | | | PURSUANT TO CHAPTER 509, F.S., A NUMBER OF ROOMS | | | EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS MINUS | | | THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS | | | REQUIRED BY TABLE 224.2 SHALL PROVIDE SPECIAL | | | ACCESSIBILITY FEATURES OF 806.4. | | | 806.4 HOTEL, MOTEL AND CONDOMINIUM SPECIAL | | | ACCESSIBILITY FEATURES. THIS SECTION DOES NOT RELIEVE | | | THE OWNER OF THE RESPONSIBILITY OF PROVIDING ACCESSIBLE | | | ROOMS IN CONFORMANCE WITH SECTION 224 AND 806 OF THIS | | | CODE. IN ALL BUILDINGS, STRUCTURES AND FACILITIES | | | LICENSED AS A HOTEL, MOTEL OR RESORT CONDOMINIUM | | | PURSUANT TO CHAPTER 509, F.S., A NUMBER OF ROOMS | | | EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS MINUS | | | THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS | | | REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING | | | ADDITIONAL SPECIAL ACCESSIBILITY FEATURES: | | | (I)GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH | | | COMPLY WITH SECTION 604.5. | | | (II)ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL | | | BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT | | | DEVICES. | | | (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4. | | | 190 GUEST ROOMS MINUS 8 REQUIRED ACCESSIBLE ROOMS | | | EQUALS 182 ROOMS. FIVE (5) PERCENT OF 182 EQUALS 9.1. | | | THEREFORE, IN ADDITION TO THE 8 REQUIRED ACCESSIBLE | | | ROOMS, 10 ROOMS ARE REQUIRED TO HAVE THE SPECIAL | | | ACCESSIBILITY FEATURES OF 806.4. | | | | | | 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 & | | | 051-A-122: | | | | | | 5A-F) COMPLIED. | | | *NEW COMMENT. ON SHEET 044-LS-131 THE COMMON PATH OF | | | TRAVEL IS NOT SHOWN CORRECTLY FOR GUEST ROOMS 322 THRU | | | 922 AND 302 THRU 902. COMMON PATH OF EGRESS TRAVEL IS | | | MEASURED FROM THE MOST REMOTE POINT IN THE ROOM TO A | | | POINT WHERE THE OCCUPANT HAS A CHOICE OF TWO SEPARATE | | | AND DISTINCT PATHS TO THE TWO EXITS. | | | | | | 6-7) COMPLIED. | | | * NEW COMMENT. | | | 1) ON SHEET 067-A-305 SECTION 3/A-3.05, THE STAIR | | | HANDRAIL EXTENSION IS INCORRECT. 1014.6 HANDRAIL | | | EXTENSIONS. HANDRAILS SHALL RETURN TO A WALL, GUARD OR | | | THE WALKING SURFACE OR SHALL BE CONTINUOUS TO THE | | | HANDRAIL OF AN ADJACENT FLIGHT OF STAIRS OR RAMP RUN. | | | WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE | | | HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12 | | | INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO | | | SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM | | | RISER. | | | 2) ON SHEET 067-A-305 SECTION 2/A-3.05, THE HANDRAIL | | | EXTENSION IS MISSING FROM THE RAMP. 1014.6 HANDRAIL | | | EXTENSIONS. AT RAMPS WHERE HANDRAILS ARE NOT CONTINUOUS | | | BETWEEN RUNS, THE HANDRAILS SHALL EXTEND HORIZONTALLY | | | ABOVE THE LANDING 12 INCHES (305 MM) MINIMUM BEYOND THE | | | TOP AND BOTTOM OF RAMP RUNS. THE EXTENSIONS OF | | | HANDRAILS SHALL BE IN THE SAME DIRECTION OF THE FLIGHTS | | | OF STAIRS AT STAIRWAYS AND THE RAMP RUNS AT RAMPS. | | | | | | | | | 8) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR | | | STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM, | | | HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE | | | DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS | | | THE HARDWARE MEET COMPLIANCE WITH : | | | 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE. | | | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE | | | PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4. | | | OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES | | | MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN | | | POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND | | | USABLE FROM BOTH SIDES. | | | | | | 9) COMPLIED. | | | | | | 10) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A | | | SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND | | | CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION | | | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE | | | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 11) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 12) 3RD REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE | | | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY | | | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS | | | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF | | | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE | | | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE | | | CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-04-04 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-04-04 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2018-04-04 08:22:51 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 18020254 | | | ADD: 1675 PALM BEACH LAKES BLVD. | | | CONT: STRATICON LLC | | | TEL: 772-210-0200 STRATICON | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | | | | 2ND REVIEW | | | DATE: WED. APRIL 04/ 2018 | | | ACTION: DENIED | | | | | | 1) 2ND REQUEST. THRESHOLD BUILDING / FL S. S. 553.71(7) | | | ?THRESHOLD BUILDING". | | | THE RESPONSE IS THAT THE THRESHOLD DOCUMENTS WERE | | | SUBMITTED UNDER THE BUCK HOIST PERMIT. PLEASE NOTE THE | | | SUBMITTED FORMS DATED MARCH 29, 2017 WERE NOT COMPLETE | | | IN REQUIRED SIGNATURES. | | | THE CERTIFIED INSPECTION CO. LINE IS LEFT BLANK, NO | | | NOTARY WORK, CONTRACTOR SIGNATURE WITH NO NOTARY WORK, | | | MISSING THE ARCHITECT AND ENGINEERS SIGNATURE AND SEAL | | | AND NOTARY WORK, YOU SHOULD UPDATE YOUR SITE INSPECTOR | | | INFORMATION WHO IS STILL WITH THE COMPANY, MIKE ADAIR | | | IS NOW A CITY INSPECTOR. | | | | | | | | | THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. PLEASE | | | UPDATE FILES SINCE THEIR MAYBE ADDITIONAL PERSONNEL TO | | | ACT AS THE JOBSITE INSPECTOR. | | | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 1A)2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | | | | 1C)COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 1D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. | | | | | | 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING | | | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE | | | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND | | | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED | | | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM | | | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING | | | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT | | | THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | | | | | | | | | | 2) SHEET 042-LS-111 & 045-A-111: | | | | | | 2A-2E) COMPLIED. | | | | | | 2F) PROVISO: PLEASE NOTE WITH BOTH EXIT PASSAGE WAYS | | | 119 & 120 THE ONLY ALLOWABLE PENETRATIONS ARE THOUGH | | | ALLOWED UNDER SECTION FBC-B 1024.6 PENETRATIONS INTO OR | | | THROUGH AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR | | | EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT | | | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, | | | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION | | | AND ELECTRICAL RACEWAY SERVING THE EXIT PASSAGEWAY AND | | | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE | | | INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED | | | IN ACCORDANCE WITH SECTION 714. THERE SHALL NOT BE | | | PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS. | | | | | | 2G-2K) COMPLIED. | | | | | | | | | 2L) 2ND REQUEST. SEMI-COMPLIED. THE RESPONSE INDICATES | | | NEW UPDATES FOR WALL TYPE L & L1 ON SHEET A5.02. PLEASE | | | NOTE THIS SHEET IS NOT IN ORDER, FOUND IT LATER IN THE | | | REVIEW. | | | | | | 2M) COMPLIED. | | | | | | 2N) SHEET A-407 NOTICE ONLY!!! SHEET A4.07 MENS STALL | | | STILL 7 FEET. SHEET A-4.08 WOMENS STALL CORRECTED 7 | | | FOOT 1 INCH. | | | 1ST REVIEW COMMENT. THE ENLARGED MENS & WOMENS RESTROOM | | | ON SHEET A407 & A-408 MEASURE 7-0 OVERALL. THE LAYOUT | | | JUST BARELY MEETS THE REQUIREMENT FOR THE CLEAR FLOOR | | | SPACE UNDER THE ACCESSIBILITY CODE SECTION 604.3.1. | | | DEPENDING ON THE SIZE LAV TO BE INSTALLED THE CLEAR | | | FLOOR SPACE MAY NOT BE ACHIEVED!!! | | | | | | 2O-Q) COMPLIED. | | | | | | 2R) 2ND REQUEST. SHEET 042-LS-111 THE FLOOR PLAN SHOWS | | | A DINING AND BAR AREA, PLEASE PROVIDE COMPLIANCE WITH | | | THE 2017 ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES | | | ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT | | | LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING | | | SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. | | | | | | 2S) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND | | | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE | | | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING | | | DINING SURFACES AND WORK SURFACES. | | | | | | 2T) 2ND REQUEST. 206.2.5 206.2.5 RESTAURANTS AND | | | CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN | | | ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS, | | | INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR | | | DINING AREAS. | | | 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY | | | WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING | | | SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, | | | LUNCH COUNTERS, AND BOOTHS. | | | 2T)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 2T)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING | | | SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM | | | AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 2U) PROVISO, NOTICE ONLY! POOL, GENERATOR, KITCHEN | | | HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE | | | SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION | | | PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT | | | AND ALL REQUIRE A SEPARATE REVIEW AND FEE. | | | | | | 2V)COMPLIED. | | | | | | 2W) 2ND REQUEST. SHEET 005-GN-1 BUILDING CODE SUMMARY | | | INDICATES THE PLANS WERE DEVELOPED A CONSTRUCTION TYPE | | | II-A, THIS ONLY ALLOWS UNDER THE 2014 CODE TABLE 503 A | | | 4 STORY BUILDING WITH ONE STORY INCREASE, IT WOULD BE | | | REQUIRED TO BE A CONSTRUCTION TYPE I-B . UNDER THE 2017 | | | FBC-B TABLE 504.4 THE BUILDING TYPE WOULD ALSO BE | | | REQUIRED TO BE I-B ALLOWABLE 12 STORIES WITH A FULL | | | NFPA 13 SYSTEM, UNDER THE 2017 WITH FIRE SPRINKLERS A | | | LL-A BUILDING IS ONLY ALLOWED TO BE 5 STORIES. . | | | | | | 2X) COMPLIED. R-1 TRANSIENT A STAY30 DAYS OR LESS, SEE | | | FBC-B 310.3 & 310.4. | | | | | | 2Y)2ND REQUEST. SHEETS 042-ALS-111 NOR SHEET | | | 045-A-111-A SHOW THE LOCATION OF THE FIRE PUMP | | | LOCATION. SHEET E-101 SHOWS THE FIRE PUMP IN THE | | | MECHANICAL/ ELECTRICAL ROOM 127. PLEASE SHOW COMPLIANCE | | | WITH: | | | 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL | | | BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH | | | SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS. | | | FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED | | | FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE | | | BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR | | | 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE | | | WITH SECTION 711, OR BOTH. | | | EXCEPTIONS: | | | 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY | | | 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED | | | IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE | | | PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | | 903.3.1.1 OR 903.3.1.2. | | | | | | 3) SHEET 046-A-111-B: | | | | | | 3A) 2ND REQUEST. THE COVERED ENTRY PORT COCHERE SHOWS | | | THE USE OF A LULA LIFT, PLEASE PROVIDE CONFIRMATION THE | | | LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION | | | ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1 | | | REFERENCED STANDARDS. | | | | | | 3B) 2ND REQUEST. SHEET 046-A-111-B SHOWS A NEW FIRE | | | COMMAND ROOM. | | | [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND | | | EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY | | | WITH SECTIONS 403.4.1 THROUGH 403.4.8. | | | | | | 3C)) 2ND REQUEST. [F]403.4.1 SMOKE DETECTION. SMOKE | | | DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH SECTION | | | 907.2.13.1. | | | | | | 3D) 2ND REQUEST. [F]403.4.2 FIRE ALARM SYSTEM. A FIRE | | | ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH | | | SECTION 907.2.13. | | | | | | 3E) 2ND REQUEST. [F]403.4.3 STANDPIPE SYSTEM. A | | | HIGH-RISE BUILDING SHALL BE EQUIPPED WITH A STANDPIPE | | | SYSTEM AS REQUIRED BY SECTION 905.3. | | | | | | 3F)) 2ND REQUEST. [F]403.4.4 EMERGENCY VOICE/ALARM | | | COMMUNICATION SYSTEM. AN EMERGENCY VOICE/ALARM | | | COMMUNICATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE | | | WITH SECTION 907.5.2.2. | | | | | | 3G) 2ND REQUEST. [F]403.4.5 EMERGENCY RESPONDER RADIO | | | COVERAGE. EMERGENCY RESPONDER RADIO COVERAGE SHALL BE | | | PROVIDED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION | | | CODE. | | | | | | 3H)SEMI-COMPLIED. [F]403.4.6 FIRE COMMAND. A FIRE | | | COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE | | | PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT. | | | | | | 3I) 2ND REQUEST. 403.4.7 SMOKE REMOVAL. TO FACILITATE | | | SMOKE REMOVAL IN POST-FIRE SALVAGE AND OVERHAUL | | | OPERATIONS, BUILDINGS AND STRUCTURES SHALL BE EQUIPPED | | | WITH NATURAL OR MECHANICAL VENTILATION FOR REMOVAL OF | | | PRODUCTS OF COMBUSTION IN ACCORDANCE WITH ONE OF THE | | | FOLLOWING: | | | 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR | | | PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF | | | EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM) | | | INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL | | | BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR | | | FEET (15 240 MM) OF PERIMETER. | | | | | | EXCEPTIONS: | | | 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE | | | HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE | | | PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA | | | IN LIEU OF THE AREA SPECIFIED IN ITEM 1. | | | 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT | | | GLAZING CAN BE CLEARED BY FIRE FIGHTERS. | | | 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE | | | EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA | | | INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED | | | DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER | | | PORTIONS OF THE BUILDING. | | | 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE | | | EQUIVALENT RESULTS. | | | | | | 3J) 2ND REQUEST. [F]403.4.8 STANDBY AND EMERGENCY | | | POWER. A STANDBY POWER SYSTEM COMPLYING WITH SECTION | | | 2702 AND SECTION 3003 SHALL BE PROVIDED FOR THE STANDBY | | | POWER LOADS SPECIFIED IN SECTION 403.4.8.3. AN | | | EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702 | | | SHALL BE PROVIDED FOR THE EMERGENCY POWER LOADS | | | SPECIFIED IN SECTION 403.4.8.4. | | | | | | 3K) 2ND REQUEST. [F]403.4.8.1 EQUIPMENT ROOM. IF THE | | | STANDBY OR EMERGENCY POWER SYSTEM INCLUDES A GENERATOR | | | SET INSIDE A BUILDING, THE SYSTEM SHALL BE LOCATED IN A | | | SEPARATE ROOM ENCLOSED WITH 2-HOUR FIRE BARRIERS | | | CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR | | | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 711, OR BOTH. SYSTEM SUPERVISION WITH MANUAL | | | START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE | | | FIRE COMMAND CENTER. | | | | | | 4A-D) COMPLIED. MATRIX PROVIDING THE TOTAL AMOUNT OF | | | SLEEPING ROOMS ACCESSIBILITY. | | | | | | 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 & | | | 051-A-122: | | | 5A-F) COMPLIED. | | | | | | 6-7) COMPLIED. | | | | | | 8) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR | | | STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM, | | | HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE | | | DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS | | | THE HARDWARE MEET COMPLIANCE WITH : | | | 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE. | | | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE | | | PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4. | | | OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES | | | MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN | | | POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND | | | USABLE FROM BOTH SIDES. | | | | | | 9) COMPLIED. | | | | | | 10) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A | | | SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND | | | CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION | | | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE | | | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 11) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 12) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE | | | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY | | | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS | | | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF | | | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE | | | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE | | | CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-02-15 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-02-13 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2018-02-15 16:22:01 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 18020254 | | | ADD: 1675 PALM BEACH LAKES BLVD. | | | CONT: STRATICON LLC | | | TEL: 772-210-0200 STRATICON | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | | | | 1ST REVIEW | | | DATE: WED. FEB. 14/ 2018 | | | ACTION: DENIED | | | | | | 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. | | | PLEASE UPDATE FILES SINCE THEIR MAYBE ADDITIONAL | | | PERSONNEL TO ACT AS THE JOBSITE INSPECTOR. | | | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. | | | | | | 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. | | | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 1F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE | | | E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, | | | THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED | | | AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, | | | TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) | | | FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK | | | & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES | | | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER | | | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE | | | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR | | | WALLS AND CEILINGS. | | | | | | | | | | | | | | | 2) SHEET 042-LS-111 & 045-A-111: | | | | | | 2A) THE LIFE SAFETY PLAN SHOWS THE EGRESS DOOR | | | CAPACITIES AT 36 INCHES/ .2 = 180 OCCUPANT LOAD. PLEASE | | | REDUCE ALL OPENINGS BY 2 INCHES FOR THE CLEAR WIDTH OF | | | THE DOOR WHEN OPEN 90 DEGREES TO THE DOOR JAMB. | | | 2017 FBC-B 1010.1.1 SIZE OF DOORS. THE REQUIRED | | | CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR | | | THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM | | | CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS | | | WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE | | | OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 | | | DEGREES. PLEASE CORRECT ALL DOORWAYS ON ALL FLOORS. | | | | | | 2B) IN THE LIFE SAFETY PLAN ONLY DISTANCES ARE GIVEN | | | FOR THE MEANS OF EGRESS. SOME OF THE AREAS SHOW THE | | | OCCUPANT LOAD #1 ASSEMBLY DINING 116 TOTAL OCC. LOAD. | | | IS THE KITCHEN LOAD FIGURED IN THIS CALCULATION? | | | THE SAME WITH THE EMPLOYEES BREAK ROOM, LAUNDRY AND OR | | | EMPLOYEES WORK AREA. WHERE THE PLAN SETS A POINT AS THE | | | START OF A MEANS OF EGRESS THE PLANS SHOULD SHOW AN | | | OCCUPANT LOAD AND ALONG THE PATH OF TRAVEL THE AMOUNT | | | OF OCCUPANTS BEING ADDED AND THE NEW SUBTOTAL. IN THIS | | | WAY THE OCCUPANT LOAD IS KNOWN FOR EACH DOOR, RAMP OR | | | STAIR. | | | 2017 FBC-B 1003.6 MEANS OF EGRESS CONTINUITY. | | | | | | THE PATH OF EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL | | | NOT BE INTERRUPTED BY A BUILDING ELEMENT OTHER THAN A | | | MEANS OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER. | | | THE MINIMUM WIDTH OR REQUIRED CAPACITY OF A MEANS OF | | | EGRESS SYSTEM SHALL NOT BE DIMINISHED ALONG THE PATH OF | | | EGRESS TRAVEL. | | | | | | 2C) THE LIFE SAFETY PLAN SHOWS THE 2 VERTICAL EXITS AS | | | 2 HOUR RATED BUT THE EXIT CORRIDOR 119 & 120 ARE SHOWN | | | AS A 1 HOUR FIRE RATED CORRIDOR. PLEASE NOTE THESE | | | CORRIDORS ARE IDENTIFIED WRONG, THEY ARE EXIT | | | PASSAGEWAYS. | | | 2017 FBC-B PLEASE REFER TO 1024 .3. 1024.3 | | | CONSTRUCTION. EXIT PASSAGEWAY ENCLOSURES SHALL HAVE | | | WALLS, FLOORS AND CEILINGS OF NOT LESS THAN A 1-HOUR | | | FIRE-RESISTANCE RATING, AND NOT LESS THAN THAT REQUIRED | | | FOR ANY CONNECTING INTERIOR EXIT STAIRWAY OR RAMP ( 2 | | | HOUR STAIR ENCLOSURE/ 2 HOUR EXIT PASSAGEWAY). EXIT | | | PASSAGEWAYS SHALL BE CONSTRUCTED AS FIRE BARRIERS IN | | | ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES | | | CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. | | | PLEASE UPDATE ALL WALL IDENTIFICATION TAGS, F1 RATED | | | WALLS TO F2, D RATED WALLS SHOWING NO RATING, INCLUDING | | | THE 2 HOUR RATED STAIR ENCLOSURES AND IN THE DRY | | | STORAGE ROOM 114 A NON-RATED WALL C WHICH GOES THROUGH | | | A RATED WALL. | | | | | | 2D) SHEET A-111 IN THE EXIT PASSAGEWAY 119 & 120. | | | PLEASE NOTE UNDER THE 2017 FLORIDA BUILDING CODE | | | EXISTING BUILDING CODE TABLE 1012.4 MEANS OF EGRESS | | | HAZARD CATEGORIES THIS BUILDING WAS A BUSINESS | | | OCCUPANCY. UNDER THE CHANGE OF OCCUPANCY TO A R1 THIS | | | IS A HIGH RELATIVE HAZARD UNDER TABLE 1012.4. | | | EXIST. BUILD. CODE 1012.4.1 MEANS OF EGRESS FOR CHANGE | | | TO HIGHER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY | | | CLASSIFICATION IS MADE TO A HIGHER HAZARD CATEGORY | | | (LOWER NUMBER) AS SHOWN IN TABLE 1012.4, THE MEANS OF | | | EGRESS SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 | | | OF THE FLORIDA BUILDING CODE, BUILDING. THE 2017 FBC-B | | | STATES IN 1024.1 EXIT PASSAGEWAYS. AN EXIT PASSAGEWAY | | | SHALL NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS | | | OF EGRESS AND A CIRCULATION PATH. THE 2012 IBC CODE | | | COMMENTARY STATES THE ONLY OPENINGS THAT ARE PERMITTED | | | IN THE FIRE RESISTANCE RATED EXIT PASSAGEWAY ARE DOORS | | | THAT LEAD EITHER FROM NORMALLY OCCUPIED SPACES, FROM | | | THE ENCLOSURE FOR THE EXIT STAIRWAY AND DOORS LEADING | | | TO THE OUTSIDE. | | | | | | PLEASE ALSO REVIEW SECTION 1023 2017 FBC-B INTERIOR | | | EXIT & STAIRWAYS& RAMPS, 1023.11 TERMINATION AND | | | EXTENSIONS. EXCEPTION 1 ALLOWS FOR OPENINGS IN THE EXIT | | | PASSAGEWAY SERVING A SMOKEPROOF ENCLOSURE ARE PERMITTED | | | WHERE THE EXIT PASSAGEWAY IS PROTECTED AND PRESSURIZED | | | IN THE SAME MANNER AS THE SMOKEPROOF ENCLOSURE, AND | | | OPENINGS ARE PROTECTED AS REQUIRED FOR ACCESS FROM | | | OTHER FLOORS. | | | | | | PLEASE ALSO REVIEW SECTION 1024.7 VENTILATION FOR EXIT | | | PASSAGEWAYS PROVIDE WHICH OF THE 3 METHODS WILL | | | INSTALLED. | | | | | | 2E) PLEASE ALSO REVIEW IN THE 2 HOUR FIRE RATED EXIT | | | PASSAGEWAY 119 DOOR 116 AND SIDELIGHT, IN THE 2017 | | | FBC-B TABLE 716.5 FOR A 2 HOUR WALL ONLY ALLOWS A 100 | | | SQ. IN. VISION PANEL IN THE DOOR AND SIDELIGHT OR | | | TRANSOM NOT PERMITTED. | | | | | | 2F) PLEASE NOTE WITH BOTH EXIT PASSAGE WAYS 119 & 120 | | | THE ONLY ALLOWABLE PENETRATIONS ARE THOUGH ALLOWED | | | UNDER SECTION FBC-B 1024.6 PENETRATIONS INTO OR THROUGH | | | AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT | | | AND DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION, | | | SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR | | | FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY | | | SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL | | | BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH | | | SECTION 714. THERE SHALL NOT BE PENETRATIONS OR | | | COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT, | | | BETWEEN ADJACENT EXIT PASSAGEWAYS. | | | | | | 2G) PLEASE REVIEW SHEET M-101 AND THE DUCTWORK THAT IS | | | RUNNING THROUGH THE EXIT PASSAGEWAY. SHOW HOW | | | COMPLIANCE WITH SECTION FBC-B 1024.7 IS TO BE ACHIEVED. | | | 1024.7 VENTILATION. | | | EQUIPMENT AND DUCTWORK FOR EXIT PASSAGEWAY VENTILATION | | | AS PERMITTED BY SECTION 1024.6 SHALL COMPLY WITH ONE OF | | | THE FOLLOWING: | | | 1. THE EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR | | | TO THE BUILDING AND SHALL BE DIRECTLY CONNECTED TO THE | | | EXIT PASSAGEWAY BY DUCTWORK ENCLOSED IN CONSTRUCTION AS | | | REQUIRED FOR SHAFTS. | | | 2. WHERE THE EQUIPMENT AND DUCTWORK IS LOCATED WITHIN | | | THE EXIT PASSAGEWAY, THE INTAKE AIR SHALL BE TAKEN | | | DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE | | | DISCHARGED DIRECTLY TO THE OUTDOORS, OR THE AIR SHALL | | | BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS | | | REQUIRED FOR SHAFTS. 2017 FLORIDA BUILDING CODE W 2017 | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION 105.1.1. PERMIT | | | REQUIRED. | | | 3. WHERE LOCATED WITHIN THE BUILDING, THE EQUIPMENT AND | | | DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE | | | BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH | | | CONSTRUCTION AS REQUIRED FOR SHAFTS. | | | IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED | | | CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR | | | MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY | | | OPENING PROTECTIVES IN ACCORDANCE WITH SECTION 716 FOR | | | SHAFT ENCLOSURES. | | | EXIT PASSAGEWAY VENTILATION SYSTEMS SHALL BE | | | INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS. | | | | | | 2H) PLEASE NOTE AS MEASURED FOR THE EXITS AND | | | REMOTENESS, SPRINKLERED BUILDING 1/3 RD. THE OVERALL | | | DISTANCE CENTER OF DOOR LINE TO CENTER OF DOOR LINE. | | | 2017 FBC-B 1007.1.1 EXCEPTION 1 & 2. | | | | | | 1ST FLOOR SHEET 047-A-112 THE OVERALL DIAGONAL DISTANCE | | | 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT DOOR 133 | | | THROUGH CENTERLINE OF RATED CORRIDOR TO CENTERLINE EXIT | | | DOOR 135 IS 42 FT. DOES NOT MEET REMOTENESS. | | | | | | 2ND FLOOR SHEET 051-A-122 THE OVERALL DIAGONAL DISTANCE | | | 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT DOOR 233 | | | THROUGH CENTERLINE OF RATED CORRIDOR TO CENTERLINE EXIT | | | DOOR 235 IS 42 FT. DOES NOT MEET | | | REMOTENESS. | | | | | | 3RD-9TH FLOORS SHEET 054-A-1.32 THE OVERALL DIAGONAL | | | DISTANCE 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT | | | DOOR 333 THROUGH CENTERLINE OF RATED CORRIDOR TO | | | CENTERLINE EXIT DOOR 335 IS 48.16 FT. DOES MEET | | | REMOTENESS TEST. | | | | | | 2I) SHEET P-106 THE EXIT PASSAGE WAY LISTED ON THE | | | ARCHITECTURAL AND MECHANICAL SHEETS AS 119 AND 120 IS | | | LISTED HERE AS EXIT CORRIDOR 121. PLEASE REMOVE ALL ? | | | INCH, 3 INCH AND 4 INCH COLD WATER AS WELL AS 1 ? INCH | | | HOT WATER PIPING FROM THE 2 HOUR FIRE RATED EXIT | | | PASSAGEWAY. SEE FBC-B SECTION 1024.6 PENETRATIONS. | | | | | | PENETRATIONS INTO OR THROUGH AN EXIT PASSAGEWAY ARE | | | PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY | | | FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, | | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT | | | COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT | | | PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT EXCEEDING | | | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE | | | PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL | | | NOT BE PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS. | | | | | | 2J) SHEET E-106 THE EXIT PASSAGE WAY LISTED ON THE | | | ARCHITECTURAL AND MECHANICAL SHEETS AS 119 AND 120 IS | | | LISTED HERE AS EXIT CORRIDOR 121. THE SHEET INDEX LIST | | | SHEET E-105 AS THE 1ST FLOOR OVERALL LIGHTING PLAN, | | | THERE SEEMS TO BE A DISCREPANCY IN PLANS. IN EITHER | | | CASE SHOW COMPLIANCE WITH FBC-B SECTION 1024.6 | | | PENETRATIONS. PENETRATIONS INTO OR THROUGH AN EXIT | | | PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT AND | | | DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION, | | | SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR | | | FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY | | | SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL | | | BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH | | | SECTION 714. THERE SHALL NOT BE PENETRATIONS OR | | | COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT, | | | BETWEEN ADJACENT EXIT PASSAGEWAYS. | | | | | | 2K) LS-111 AND A-111A BOTH SHOW WITHIN THE 2 HOUR EXIT | | | PASSAGE WAY 120 TAKING PART OF THE OCCUPANTS FROM THE 2 | | | HOUR ENCLOSURE OUT THROUGH DOOR 124 IN FRONT OF THE | | | ELEVATOR LOBBY ON THE 1ST FLOOR, OUT THROUGH THE | | | GENERAL LOBBY AND OUT THE FRONT DOORS. THE DOOR 124 IS | | | A OUTSWING DOOR AND DIRECTLY IN FRONT | | | IS DOOR 125 ALSO A OUTSWING DOOR THAT WOULD IMPEDE THE | | | EXITING FROM THE VERTICAL EXIT STAIRWAY. NOTE THE DOOR | | | SWING DOES NOT CUT THE REQUIRED EGRESS WIDTH IN HALF. | | | | | | 2L) LS-111 AND A-111A PLEASE REVIEW LAUNDRY CHUTE | | | SHAFT. THE LIFE SAFETY PLAN DOES NOT INDICATE THE | | | LAUNDRY SHAFT AS RATED. THE A-111A SHEET SHOWS THE | | | RATING ON THE LAUNDRY SHAFT WALLS AS F1 ONE HOUR FIRE | | | RATED WALL UL 448, NOT EVEN SHAFT WALL CONSTRUCTION. | | | SHAFT WALL CONSTRUCTION SHALL BE 2 HOURS WHEN | | | CONNECTING 4 STORIES OR MORE. FBC-B 713.4. FIRE | | | RESISTANCE RATING. THE PLANS WILL NEED TO BE UPDATES | | | SHOWING A 2 HOUR SHAFT AND MEETING ALL OF THE | | | REQUIREMENTS OF FBC-B 713.13.1-4 AND 713.13.6. | | | | | | 2M) THE PLANS SHOW A SPACE THAT IS VOID, ENCLOSED ON | | | THE KITCHEN, LAUNDRY SHAFT AND EXIT PASSAGE WAY 120, | | | WHAT IS SPACE TO BE USED FOR? 107.2.1.3 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 2N) SHEET A-407 NOTICE ONLY!!! THE ENLARGED MENS & | | | WOMENS RESTROOM ON SHEET A407 & A-408 MEASURE 7-0 | | | OVERALL. THE LAYOUT JUST BARELY MEETS THE REQUIREMENT | | | FOR THE CLEAR FLOOR SPACE UNDER THE ACCESSIBILITY CODE | | | SECTION 604.3.1. DEPENDING ON THE SIZE LAV TO BE | | | INSTALLED THE CLEAR FLOOR SPACE MAY NOT BE ACHIEVED!!! | | | | | | 2O) SHEET A-407 & A-408 THE MIRRORS IN THE VANITY | | | ELEVATION ARE DIMENSIONED WITH THE DIMENSION OF 3 FOOT | | | 4 ? INCHES TO THE BOTTOM OF THE MIRROR FRAME. THE 2017 | | | FBC-ACCESSIBILITY CODE REQUIRES A MAXIMUM OF 40 INCHES | | | TO THE REFLECTIVE SURFACE TO FINISH FLOOR AS A MAXIMUM | | | HEIGHT. SEE 603.3. | | | | | | 2P) SHEET A-111 EMPLOYEE RESTROOM SHOWS A ACCESSIBLE | | | SHOWER. THIS PLAN DOES NOT REFERENCE ANY DETAILS FOR | | | THE ACCESSIBLE SHOWER, WHEN MEASURED THE SHOWER IS 3X3 | | | FEET. THERE IS A SEAT WITHIN THE SHOWER BUT THE SEAT | | | FALL SHORT OF COMPLYING WITH 2017 ACC. CODE 610.3. | | | 610.3.2 L-SHAPED SEATS. | | | THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES | | | MAXIMUM AND THE FRONT EDGE 15 INCHES MINIMUM AND 16 | | | INCHES MAXIMUM FROM THE SEAT WALL. PLEASE PROVIDE GRAB | | | BARS FOR A TRANSFER SHOWER IN COMPLIANCE WITH 608.3.1. | | | | | | 2Q) SHEET A-112 THE EMPLOYEE RESTROOM SHOWS A OVERALL | | | DIMENSION OF THE RESTROOM BUT NOT THE CLEAR FLOOR SPACE | | | REQUIRED FOR THE WATER CLOSET. SEE ACC. CODE 604.3.1. | | | SIZE. | | | | | | 2R) SHEET 042-LS-111 THE FLOOR PLAN SHOWS A DINING AND | | | BAR AREA, PLEASE PROVIDE COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES ARE | | | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST | | | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT | | | THE DINING SURFACES SHALL COMPLY WITH 902. | | | | | | 2S) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES | | | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED | | | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING | | | SURFACES AND WORK SURFACES. | | | | | | 2T) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN | | | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL | | | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR | | | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. | | | 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY | | | WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING | | | SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, | | | LUNCH COUNTERS, AND BOOTHS. | | | 2T)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 2T)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 2U) POOL, GENERATOR, KITCHEN HOODS, SUPPRESSION, GAS, | | | FENCES, SIGNS, FIRE SPRINKLERS, FIRE ALARMS, | | | LANDSCAPING, IRRIGATION PERMITS ARE NOT REVIEWED UNDER | | | THE MAIN BUILDING PERMIT AND ALL REQUIRE A SEPARATE | | | REVIEW AND FEE. | | | | | | 2V) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE | | | PLANS WERE DEVELOPED UNDER THE 2014 FBC-B BROUGHT IN | | | AFTER DEC. 31/ 2017 WHICH WAS THE ADOPTION DATE OF THE | | | 2017 FBC-B. | | | | | | 2W) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE | | | PLANS WERE DEVELOPED A CONSTRUCTION TYPE II-A, THIS | | | ONLY ALLOWS UNDER THE 2014 CODE TABLE 503 A 4 STORY | | | BUILDING WITH ONE STORY INCREASE, IT WOULD BE REQUIED | | | TO BE A CONSTRUCTION TYPE I-B . UNDER THE 2017 FBC-B | | | TABLE 504.4 THE BUILDING TYPE WOULD ALSO BE REQUIRED TO | | | BE I-B. | | | | | | 2X) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE | | | HOTEL AS A R-2 HOTEL TRANSIENT, PLEASE NOTE R-1 IS | | | CONSIDERED TRANSIENT A STAY30 DAYS OR LESS, R-2 IS | | | CONSIDERED NON-TRANSIENT OR STAYS OVER 30 DAYS. SEE | | | FBC-B 310.3 & 310.4. | | | | | | 2Y) SHEETS 042-ALS-111 NOR SHEET 045-A-111-A SHOW THE | | | LOCATION OF THE FIRE PUMP LOCATION. SHEET E-101 SHOWS | | | THE FIRE PUMP IN THE MECHANICAL/ ELECTRICAL ROOM 127. | | | PLEASE SHOW COMPLIANCE WITH: | | | 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL | | | BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH | | | SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS. | | | FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED | | | FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE | | | BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR | | | 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE | | | WITH SECTION 711, OR BOTH. | | | EXCEPTIONS: | | | 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY | | | 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED | | | IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE | | | PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | | 903.3.1.1 OR 903.3.1.2. | | | | | | 3) SHEET 046-A-111-B: | | | 3A) THE COVERED ENTRY PORT COCHERE SHOWS THE USE OF A | | | LULA LIFT, PLEASE PROVIDE CONFIRMATION THE | | | LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION | | | ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1 | | | ?REFERENCED STANDARDS?. | | | | | | 3B) SHEET 046-A-111-B SHOWS A NEW FIRE COMMAND ROOM. | | | [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND | | | EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY | | | WITH SECTIONS 403.4.1 THROUGH 403.4.8. | | | | | | 3C) [F]403.4.1 SMOKE DETECTION. SMOKE DETECTION SHALL | | | BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.1. | | | | | | 3D) [F]403.4.2 FIRE ALARM SYSTEM. A FIRE ALARM SYSTEM | | | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13. | | | | | | 3E) [F]403.4.3 STANDPIPE SYSTEM. A HIGH-RISE BUILDING | | | SHALL BE EQUIPPED WITH A STANDPIPE SYSTEM AS REQUIRED | | | BY SECTION 905.3. | | | | | | 3F) [F]403.4.4 EMERGENCY VOICE/ALARM COMMUNICATION | | | SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM | | | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2. | | | | | | 3G) [F]403.4.5 EMERGENCY RESPONDER RADIO COVERAGE. | | | EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN | | | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. | | | | | | 3H)SEMI-COMPLIED. [F]403.4.6 FIRE COMMAND. A FIRE | | | COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE | | | PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT. | | | | | | 3I) 403.4.7 SMOKE REMOVAL. TO FACILITATE SMOKE REMOVAL | | | IN POST-FIRE SALVAGE AND OVERHAUL OPERATIONS, BUILDINGS | | | AND STRUCTURES SHALL BE EQUIPPED WITH NATURAL OR | | | MECHANICAL VENTILATION FOR REMOVAL OF PRODUCTS OF | | | COMBUSTION IN ACCORDANCE WITH ONE OF THE FOLLOWING: | | | 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR | | | PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF | | | EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM) | | | INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL | | | BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR | | | FEET (15 240 MM) OF PERIMETER. | | | | | | EXCEPTIONS: | | | 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE | | | HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE | | | PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA | | | IN LIEU OF THE AREA SPECIFIED IN ITEM 1. | | | 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT | | | GLAZING CAN BE CLEARED BY FIRE FIGHTERS. | | | 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE | | | EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA | | | INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED | | | DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER | | | PORTIONS OF THE BUILDING. | | | 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE | | | EQUIVALENT RESULTS. | | | | | | 3J) [F]403.4.8 STANDBY AND EMERGENCY POWER. A STANDBY | | | POWER SYSTEM COMPLYING WITH SECTION 2702 AND SECTION | | | 3003 SHALL BE PROVIDED FOR THE STANDBY POWER LOADS | | | SPECIFIED IN SECTION 403.4.8.3. AN EMERGENCY POWER | | | SYSTEM COMPLYING WITH SECTION 2702 SHALL BE PROVIDED | | | FOR THE EMERGENCY POWER LOADS SPECIFIED IN SECTION | | | 403.4.8.4. | | | | | | 3K) [F]403.4.8.1 EQUIPMENT ROOM. IF THE STANDBY OR | | | EMERGENCY POWER SYSTEM INCLUDES A GENERATOR SET INSIDE | | | A BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE | | | ROOM ENCLOSED WITH 2-HOUR FIRE BARRIERS CONSTRUCTED IN | | | ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES | | | CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. | | | SYSTEM SUPERVISION WITH MANUAL START AND TRANSFER | | | FEATURES SHALL BE PROVIDED AT THE FIRE COMMAND CENTER. | | | | | | 4) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 & | | | 051-A-122: | | | 4A) THIS STATEMENT IS GOING TO BE A COMMON STATEMENT | | | FOR ALL FLOORS CONTAINING SLEEPING ROOMS. THE PLANS | | | WILL NEED TO PROVIDE A MATRIX PROVIDING THE TOTAL | | | AMOUNT OF SLEEPING ROOMS. IT APPEARS THERE ARE 168 | | | SLEEPING ROOMS. A-4.05A INDICATES THE STYLE OF ROOM FOR | | | A ADA DOUBLE QUEEN AND SHEET A-406-A SHOWS THE ADA KING | | | PLEASE PROVIDE A MATRIX WHICH UNITS ARE ACCESSIBLE. | | | PLEASE USE TABLE 224.2 OF THE 2017 ACCESS. CODE TO | | | PROVIDE THE NUMBER OF UNITS WITH ROLL-IN SHOWER, NUMBER | | | OF ROOMS WITHOUT THE ROLL IN SHOWER AND TOTAL NUMBER OF | | | REQUIRED ROOMS. | | | | | | 4B) ACCESS. CODE SHOW 224.5 DISPERSION. GUEST ROOMS | | | REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH | | | 806.2 AND GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION | | | FEATURES COMPLYING WITH 806.3 SHALL BE DISPERSED AMONG | | | THE VARIOUS CLASSES OF GUEST ROOMS, AND SHALL PROVIDE | | | CHOICES OF TYPES OF GUEST ROOMS, NUMBER OF BEDS, AND | | | OTHER AMENITIES COMPARABLE TO THE CHOICES PROVIDED TO | | | OTHER GUESTS. WHERE THE MINIMUM NUMBER OF GUEST ROOMS | | | REQUIRED TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW | | | FOR COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED | | | IN THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF | | | BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED | | | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH | | | 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED | | | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS | | | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING | | | WITH 806.3. | | | | | | 4C) ACCESS. CODE SHOW COMPLIANCE WITH: 224.1.2 GUEST | | | ROOM DOORS AND DOORWAYS. ENTRANCES, DOORS, AND DOORWAYS | | | PROVIDING USER PASSAGE INTO AND WITHIN GUEST ROOMS THAT | | | ARE NOT REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING | | | WITH 806.2 SHALL COMPLY WITH 404.2.3. | | | | | | 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL PROVIDE A | | | CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM. CLEAR | | | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE | | | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, | | | WITH THE DOOR OPEN 90 DEGREES. | | | | | | | | | 806.2.3 SLEEPING AREAS. AT LEAST ONE SLEEPING AREA | | | SHALL PROVIDE A CLEAR FLOOR SPACE COMPLYING WITH 305 ON | | | BOTH SIDES OF A BED. THE CLEAR FLOOR SPACE SHALL BE | | | POSITIONED FOR PARALLEL APPROACH TO THE SIDE OF THE | | | BED. EXCEPTION: WHERE A SINGLE CLEAR FLOOR SPACE | | | COMPLYING WITH 305 POSITIONED FOR PARALLEL APPROACH IS | | | PROVIDED BETWEEN TWO BEDS, A CLEAR FLOOR OR GROUND | | | SPACE SHALL NOT BE REQUIRED ON BOTH SIDES OF A BED. | | | | | | | | | 806.2.4 TOILET AND BATHING FACILITIES. AT LEAST ONE | | | BATHROOM THAT IS PROVIDED AS PART OF A GUEST ROOM SHALL | | | COMPLY WITH 603. NO LESS THAN ONE WATER CLOSET, ONE | | | LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH | | | APPLICABLE REQUIREMENTS OF 603 THROUGH 610. IN | | | ADDITION, REQUIRED ROLL-IN SHOWER COMPARTMENTS SHALL | | | COMPLY WITH 608.2.2 OR 608.2.3. TOILET AND BATHING | | | FIXTURES REQUIRED TO COMPLY WITH 603 THROUGH 610 SHALL | | | BE PERMITTED TO BE LOCATED IN MORE THAN ONE TOILET OR | | | BATHING AREA, PROVIDED THAT TRAVEL BETWEEN FIXTURES | | | DOES NOT REQUIRE TRAVEL BETWEEN OTHER PARTS OF THE | | | GUEST ROOM. | | | | | | | | | 806.2.4.1 VANITY COUNTER TOP SPACE. IF VANITY COUNTER | | | TOP SPACE IS PROVIDED IN NON-ACCESSIBLE GUEST TOILET OR | | | BATHING ROOMS, COMPARABLE VANITY COUNTER TOP SPACE, IN | | | TERMS OF SIZE AND PROXIMITY TO THE LAVATORY, SHALL ALSO | | | BE PROVIDED IN ACCESSIBLE GUEST TOILET OR BATHING | | | ROOMS. | | | ADVISORY 806.2.4.1 VANITY COUNTER TOP SPACE. THIS | | | PROVISION IS INTENDED TO ENSURE THAT ACCESSIBLE GUEST | | | ROOMS ARE PROVIDED WITH COMPARABLE VANITY COUNTER TOP | | | SPACE. | | | | | | 4D) PLEASE PROVIDE COMPLIANCE WITH ACCESS. CODE TABLE | | | 224.4 GUEST ROOMS WITH COMMUNICATION FEATURES, PROVIDE | | | ALSO IN MATRIX SHOWING WHAT ROOMS ARE TO COMPLY. | | | | | | 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 & | | | 051-A-122: | | | 5A) SHEET 043-LS-121 IS MISSING THE ROOM LABEL 224 AND | | | IDENTIFIED AS A WARMING KITCHEN. 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. NOTE, CANNOT EXIT THROUGH A | | | KITCHEN OR STORAGE ROOM. ALSO SEE 2017 FBC-B 1016.2(2) | | | (5) EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE | | | ROOMS, CLOSETS, OR SPACES USED FOR SIMILAR PURPOSES. | | | | | | 5B) MEETING ROOM 226, YOUR OVERALL DIAGONAL FOR THIS | | | ROOM IS 50.50 FT. 1/3RD THE OVERALL DISTANCE IS 16 FOOT | | | 10 INCHES. THE 2 EXIT DOORS MEET THIS REQUIREMENT BUT | | | THE 2 MEANS OF ACCESS CONVERGE BETWEEN THE DOOR LEADING | | | TO STAIR 233 AND DOOR 205. BETWEEN THE WALL OF THE | | | STAIR AND DOOR 205 THERE IS ONLY 12 FEET OR THE 2 EXITS | | | CONVERGE, DOES NOT MEET THE REQUIREMENT OF REMOTENESS | | | UNDER 2017 FBC-B 1007.1.1EXCEP. 2. 1/3 DISTANCE APART. | | | | | | 5C) SHEET 050-A-121 THE COMMON WALL BETWEEN THE MEETING | | | ROOM STORAGE CLOSET AND GUEST ROOM 222 IS IDENTIFIED | | | WITH WALL TAG F3. PLEASE NOTE THE WALL SCH. ON A-501 | | | DOES NOT ASSIGN A STC RATING TO THIS WALL. | | | FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 5D) PAGE 051-A-122 & LS-1.21. GUEST ROOM 220 THIS | | | COMMENT IS TO STAND FOR ALL FLOORS 2-10. THE COMMON | | | PATH OF TRAVEL IS TAKEN FROM THE DOORWAY OR THE | | | BEGINNING OF THE EXIT ACCESS CORRIDOR. PLEASE NOTE | | | COMMON PATH OF EGRESS TRAVEL, | | | DEFINITION: THAT PORTION OF THE EXIT ACCESS TRAVEL | | | DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A | | | STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE | | | AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS | | | DOORWAYS. | | | PLEASE PROVIDE THE COMMON PATH OF EGRESS TRAVEL SHOW | | | THE COMMON PATH OF EGRESS TRAVEL FROM THE MOST REMOTE | | | POINT IN THE ROOM AND AROUND FURNITURE AND ONE FOOT | | | FROM WALL LINES TO THE CLOSET VERTICAL EXIT. IT APPEARS | | | THE TRAVEL DISTANCE EXCEEDS 75 FEET. | | | | | | 5E) SHEET 050-A-121. COMMON COMMENT FOR ALL FLOORS | | | 2-10. THE LINEN CHUTE SHOWS THE SHAFT WALLS AROUND | | | IDENTIFIED WITH A WALL TAG F2. THIS WALL IS A 1 HOUR | | | RATING REQUIRES A 2 HOUR FIRE RATING PER 713.4 | | | FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL HAVE A | | | FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE | | | CONNECTING FOUR STORIES OR MORE. | | | | | | 5F) SHEET 050-A-121 COMMON COMMENT FOR ALL FLOORS 2-10. | | | THE LINEN CHUTE SHOWS THE SHAFT WALLS AROUND IDENTIFIED | | | WITH A WALL TAG F2. PLEASE ALSO PROVIDE THE CORRECT UL | | | LISTING FOR SHAFT WALL CONSTRUCTION. 713.4 | | | FIRE-RESISTANCE RATING. | | | | | | 6) SHEET 054-A-132 GUEST ROOMS 302, THIS COMMENT WILL | | | STAND FOR THIS ROOM ALL FLOORS 3-9. THE COMMON PATH OF | | | TRAVEL IS TAKEN FROM THE DOORWAY OR THE BEGINNING OF | | | THE EXIT ACCESS CORRIDOR. PLEASE NOTE COMMON PATH OF | | | EGRESS TRAVEL, | | | DEFINITION: THAT PORTION OF THE EXIT ACCESS TRAVEL | | | DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A | | | STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE | | | AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS | | | DOORWAYS. | | | PLEASE PROVIDE THE COMMON PATH OF EGRESS TRAVEL SHOW | | | THE COMMON PATH OF EGRESS TRAVEL FROM THE MOST REMOTE | | | POINT IN THE ROOM AND AROUND FURNITURE AND ONE FOOT | | | FROM WALL LINES TO THE CLOSET VERTICAL EXIT. IT APPEARS | | | THE TRAVEL DISTANCE EXCEEDS 75 FEET. | | | | | | 7) SHEET 067-A-305: | | | 7A) DETAIL 2 EXTERIOR STAIR. THE PLAN INDICATES THE | | | RISE OF 7 INCHES AND RUN OF 11 INCHES BUT DOES NOT | | | PROVIDE THE CIRCULAR AREA MADE OF THE RISE, RUN AND | | | SLOPE OF THE BOTTOM GUARDRAIL. SHOW COMPLIANCE WITH | | | 2017 FBC-B 1015.4 EXCEPTION 2. 2. THE TRIANGULAR | | | OPENINGS AT THE OPEN SIDES OF A STAIR, FORMED BY THE | | | RISER, TREAD AND BOTTOM RAIL SHALL NOT ALLOW PASSAGE OF | | | A SPHERE 6 INCHES (152 MM) IN DIAMETER. | | | | | | 7B) DETAIL 2 EXTERIOR STAIR. THE UPPER LANDING SHOWS | | | THE GUARDRAIL AT 3 FOOT 6 INCHES OF 43 INCHES. | | | THE GUARDRAIL DROPS VERTICALLY 4 INCHES AT THE FIRST | | | RISER. THE HEIGHT MEASUREMENT FOR THE GUARDRAIL IS TO | | | BE TAKEN AT THE NOSING OF THE RISER, VERTICALLY. SEE | | | 2017 FBC-B 1015.3 HEIGHT. REQUIRED GUARDS SHALL BE NOT | | | LESS THAN 42 INCHES (1067 MM) HIGH, MEASURED | | | VERTICALLY. | | | | | | 7C) THE BOTTOM OF THE GUARDRAIL DOES NOT CONTINUE DOWN | | | THE SLOPE 11 INCHES PAST THE LAST RISER, THIS IS WHERE | | | THE HORIZONTAL EXTENSION WOULD BEGIN, THAT IS ALSO THE | | | REASON ON THE STAIRS THE HANDRAIL IS 34 INCHES IN | | | HEIGHT, THE HANDRAIL ALSO DOES NOT CONTINUE 11 INCHES | | | PAST THE LAST RISER BEFORE CONTINUING THE HORIZONTAL | | | EXTENSION. 2017 FBC-B 1014.6 HANDRAIL EXTENSIONS. THE | | | HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12 | | | INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO | | | SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM | | | RISER. | | | | | | 8) SHEET A104-A-601 DOOR STYLE 20 IS A SLIDING BARN | | | DOOR AND TRACK SYSTEM, HARDWARE GROUP 11 INDICATES ADA | | | COMPLIANT PULLS. THE DOOR HAS TO MAINTAIN A 32 INCH | | | CLEAR OPENING AS WELL AS THE HARDWARE MEET COMPLIANCE | | | WITH : | | | 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE. | | | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE | | | PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4. | | | OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES | | | MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN | | | POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND | | | USABLE FROM BOTH SIDES. | | | | | | 9) WITH NOT KNOWING THE LOCATION OF THE ACCESSIBLE | | | ROOMS, THIS IS ONE OF THE CONCERNS WITH THE EGRESS DOOR | | | TO THE INDUVIAL SUITES. THIS EXAMPLE IS FOR ALL ROOMS, | | | THE ADA ROOM NEED TO COMPLY. SEE ROOM COLUMN 214 -1013. | | | THE ENTRY DOOR IS RECESSED BACK 10 INCHES FROM THE | | | REMAINDER OF THE CORRIDOR WALL. | | | SHOW COMPLIANCE WITH THE 2017 FLORIDA ACCESSIBILITY | | | CODE FOR THE ACCESSIBLE ROOMS. 404.2.4.3 RECESSED DOORS | | | AND GATES. MANEUVERING CLEARANCES FOR FORWARD APPROACH | | | SHALL BE PROVIDED WHEN ANY OBSTRUCTION WITHIN 18 INCHES | | | (455 MM) OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE | | | THAN 8 INCHES (205 MM) BEYOND THE FACE OF THE DOOR, | | | MEASURED PERPENDICULAR TO THE FACE OF THE DOOR OR GATE. | | | | | | 10) WINDOWS ARE UNDER A SEPARATE PERMITS BUT THERE WILL | | | BE OTHER COMPONENTS AND CLADDING REQUIREMENTS. 2017 | | | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 11) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-05-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-17 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-17 |
Time |
16:14 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-05-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-08 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-04 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2018-05-08 16:31:34 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | THESE ITEMS HAVE BEEN DISCUSSED WITH ENGINEER AT | | | MEETING ON 5-7-18. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. RISER DIAGRAM SHOWS 3 MAINS. IT APPEARS MAIN # 1 AND | | | 2 ARE LOCATED IN MDB AND MAIN # 3 IS IN A SEPARATE | | | LOCATION. SHOULD MDB BE LABELED MDP? THERE IS A NOTE | | | THAT THIS EQUIPMENT IS RATED FOR 12000 AMPS, PROVIDE | | | CLARIFICATION AND/OR CORRECTION. PROVIDE PANEL SCHEDULE | | | FOR THIS PANEL. ALSO, I DO NOT SEE MAIN # 3 IN THE | | | ELECTRICAL ROOM (ROOM 127). PROVIDE CLARIFICATION AND | | | NAMES FOR EACH MAIN. WHAT IS THE RATING OF MAIN #1? | | | ALSO, FOR PANEL ?MDB?, THERE APPEARS TO ONLY BE 17? | | | CLEARANCE FOR THIS? PROVIDE CORRECTIONS AND/OR | | | CLARIFICATIONS AS NEEDED. FBC 107.2.1; NEC 110.26, | | | 695.3 (SOME ITEMS CORRECTED. BASED ON NEW RISER | | | DIAGRAM, THERE WOULD BE 4 SERVICES TO THIS BUILDING. | | | THERE IS A 2000 AMP SERVICE AT MDP, A 600 AMP SERVICE | | | SHOWN ON RISER BUT NOT ON POWER PLAN, A SERVICE TO FIRE | | | PUMP, AND A PROPOSED 200 AMP SERVICE FOR KITCHEN. EACH | | | SERVICE NEEDS TO BE CLEARLY IDENTIFIED WITH LABELS THAT | | | STATE WHICH SERVICE IT IS AND THE LOCATION OF OTHER | | | SERVICES ON PROPERTY. EACH MAIN WITHIN EACH SERVICE | | | SHOULD ALSO BE LABELED ACCORDINGLY. PANEL A ON ROOF IS | | | SHOWS AS BEING FED FROM THE 600 AMP SERVICE, WHICH ONLY | | | HAS 198 AMPS DEMAND, SO WHY DOES THE 200 AMP SERVICE | | | NEED TO BE ADDED? PANEL A IS ALSO BEING SHOWN AS FED | | | FROM MDP AS AN 800 AMP PANEL INSTEAD OF 600 AMP AND IT | | | IS INCLUDED IN THE LOAD CALCULATION FOR PANEL MDP, | | | WHICH IS AN OBVIOUS DISCREPANCY. WHILE ADDITIONAL | | | SERVICES CAN BE ALLOWED, THERE NEEDS TO BE | | | JUSTIFICATION. PROVIDE CLARIFICATIONS.)(3RD REVIEW, | | | PLAN CURRENTLY SHOWS MORE THAN 6 MAINS WHICH VIOLATES | | | NEC 230.71. ENGINEER IS CONFIRMING THE LAYOUT OF MDP | | | AND WILL RE-LABEL PLAN WITH ACCURATE COUNT OF MAINS.) | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. SOME PANEL SCHEDULE SHOW DEMAND FACTORS | | | FOR DWELLING UNITS. THE NEC DEFINES A DWELLING UNIT AS: | | | ?A SINGLE UNIT, PROVIDING COMPLETE AND INDEPENDENT | | | LIVING FACILITIES FOR ONE OR MORE PERSONS, INCLUDING | | | PERMANENT PROVISIONS FOR LIVING, SLEEPING, COOKING, AND | | | SANITATION.? THIS DEFINITION DOES NOT MATCH THIS | | | FACILITY, SO THESE DEMAND FACTORS SHOULD NOT BE USED. | | | ALSO, PROVIDE LOAD CALCULATION FOR BUS DUCT. NEC 100, | | | 215.2, 220, 408.30 (NEED FURTHER EXPLANATION OF LOAD ON | | | SERVICE. THE FEEDERS AND OVERCURRENT PROTECTION SHOULD | | | BE SIZED TO HANDLE 100% OF THE NON-CONTINUOUS LOAD PLUS | | | 125% OF THE CONTINUOUS LOAD. THE ONLY CONTINUOUS LOAD | | | SHOWN IS FOR LIGHTING, THE LARGEST MOTOR LOAD IS NOT | | | SHOWN ON ANY SCHEDULES. ADDITIONALLY, THE RISER DIAGRAM | | | SHOWS A FUTURE POOL, BUT NO LOAD IS INCLUDED FOR THIS. | | | PROVIDE CORRECTIONS. NEC 215.2, 215.3, 220.14(C), | | | 430.24)(3RD REVIEW - SOME DATA IS NOT TRANSFERRING | | | CORRECTLY IN PANEL SCHEDULES. ENGINEER ADVISED THAT THE | | | PROBLEM WILL BE FIXED AND AN ACCURATE LOAD CALCULATION | | | PROVIDED.) | | | 7. CORRECTED. | | | 8. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE | | | CONFIRMED BY INSPECTOR. | | | 9. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE | | | CONFIRMED BY INSPECTOR. | | | 10. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE | | | CONFIRMED BY INSPECTOR. | | | 11. CORRECTED. | | | 12. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING | | | ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE | | | FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | | APPLICABLE TO COMPLY WITH CODE. IT APPEARS THAT SOME | | | SCHEDULES ARE MISSING AND SOME HAVE INFORMATION THAT IS | | | TBD. PROVIDE COMPLETED SCHEDULES. PANEL SCHEDULES | | | SHOULD INCLUDE UNIQUE IDENTIFIERS FOR CIRCUITS, SUCH AS | | | ROOM NUMBERS OR LOCATIONS. GENERAL TERMS ARE NOT | | | ACCEPTABLE. NEC 210.8, 210.12, 215.5, 408.4 (SOME | | | PANELS STILL DO NOT HAVE CLEAR LOCATIONS FOR EQUIPMENT | | | THAT IS USED IN MORE THAN ONE LOCATION. PROVIDE | | | CORRECTION.) | | | 13. THE FOLLOWING PANELS ARE SHOWN WITH A 125 MAIN | | | CIRCUIT BREAKER, BUT HAVE A LOAD THAT EXCEEDS 125 AMP: | | | PANEL EML, 4LA, 5LA, 6LA, 7LA, 8LA 9LA, 10LA. PROVIDE | | | CORRECTION. NEC 215.3 (THERE ARE STILL MANY PANELS THAT | | | ARE NOT SHOWING THE CORRECT TYPE AND SIZE. PROVIDE | | | CORRECTIONS.) | | | 14. CORRECTED. | | | 15. CORRECTED. | | | 16. IT APPEARS THE GENERATOR WILL BE OVERLOADED AS | | | PANEL EMH SHOWS A LOAD OF 330.7 KVA BEFORE CORRECTIONS | | | NOTED IN COMMENT # 14. PROVIDE CORRECTION. NEC 701.4, | | | 695.3(D)(1) (3RD REVIEW - THE GENERATOR IS STILL SHOWN | | | AS OVERLOADED. PROVIDE CORRECTIONS.) | | | 17. CORRECTED. | | | 18. CORRECTED. | | | 19. CORRECTED. | | | | | | NEW COMMENTS: | | | | | | 20. FIRE PUMP IS BEING SHOWN AS FED FROM MDP IN PANEL | | | SCHEDULE. PROVIDE CORRECTION. ALSO, DID NOT SEE A LOAD | | | FOR A JOCKEY PUMP ANYWHERE. WILL THERE BE A PRESSURE | | | MAINTENANCE PUMP WITH THIS SYSTEM, AND WHERE IS IT FED | | | FROM? FBC 107.2.1 | | | 21. DURING MEETING WITH ENGINEER, THE FAULT CURRENT FOR | | | THE MAINS WAS DISCUSSED. FAULT CALCULATIONS WILL NEED | | | TO BE PROVIDED FOR ANY MODIFICATIONS OF THE SERVICE | | | EQUIPMENT SO THAT PROPER SIZING OF EQUIPMENT CAN BE | | | CONFIRMED, AS WELL AS PROPER LABELING. PROVIDE | | | AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL | | | INCLUDING INFORMATION FROM THE POWER COMPANY STATING | | | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE | | | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE | | | EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. IF FPL IS | | | NOT ABLE TO RESPOND IN A TIMELY FASHION, WE WILL ACCEPT | | | THIS AS A DEFERRED SUBMITTAL WITH THE UNDERSTANDING | | | THAT ALL PANELS WILL NEED TO MEET OR EXCEED THE | | | CALCULATED FAULT CURRENT. NEC 110.9, 110.10 | | | 22. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-04-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-04-05 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-04-05 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2018-04-05 16:53:29 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA | | | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS | | | PRESENT. FBC 105.1, 107.2.1 (DID NOT SEE THIS NOTE | | | ADDED.) | | | 2. CORRECTED. | | | 3. RISER DIAGRAM SHOWS 3 MAINS. IT APPEARS MAIN # 1 AND | | | 2 ARE LOCATED IN MDB AND MAIN # 3 IS IN A SEPARATE | | | LOCATION. SHOULD MDB BE LABELED MDP? THERE IS A NOTE | | | THAT THIS EQUIPMENT IS RATED FOR 12000 AMPS, PROVIDE | | | CLARIFICATION AND/OR CORRECTION. PROVIDE PANEL SCHEDULE | | | FOR THIS PANEL. ALSO, I DO NOT SEE MAIN # 3 IN THE | | | ELECTRICAL ROOM (ROOM 127). PROVIDE CLARIFICATION AND | | | NAMES FOR EACH MAIN. WHAT IS THE RATING OF MAIN #1? | | | ALSO, FOR PANEL ?MDB?, THERE APPEARS TO ONLY BE 17? | | | CLEARANCE FOR THIS? PROVIDE CORRECTIONS AND/OR | | | CLARIFICATIONS AS NEEDED. FBC 107.2.1; NEC 110.26, | | | 695.3 (SOME ITEMS CORRECTED. BASED ON NEW RISER | | | DIAGRAM, THERE WOULD BE 4 SERVICES TO THIS BUILDING. | | | THERE IS A 2000 AMP SERVICE AT MDP, A 600 AMP SERVICE | | | SHOWN ON RISER BUT NOT ON POWER PLAN, A SERVICE TO FIRE | | | PUMP, AND A PROPOSED 200 AMP SERVICE FOR KITCHEN. EACH | | | SERVICE NEEDS TO BE CLEARLY IDENTIFIED WITH LABELS THAT | | | STATE WHICH SERVICE IT IS AND THE LOCATION OF OTHER | | | SERVICES ON PROPERTY. EACH MAIN WITHIN EACH SERVICE | | | SHOULD ALSO BE LABELED ACCORDINGLY. PANEL A ON ROOF IS | | | SHOWS AS BEING FED FROM THE 600 AMP SERVICE, WHICH ONLY | | | HAS 198 AMPS DEMAND, SO WHY DOES THE 200 AMP SERVICE | | | NEED TO BE ADDED? PANEL A IS ALSO BEING SHOWN AS FED | | | FROM MDP AS AN 800 AMP PANEL INSTEAD OF 600 AMP AND IT | | | IS INCLUDED IN THE LOAD CALCULATION FOR PANEL MDP, | | | WHICH IS AN OBVIOUS DISCREPANCY. WHILE ADDITIONAL | | | SERVICES CAN BE ALLOWED, THERE NEEDS TO BE | | | JUSTIFICATION. PROVIDE CLARIFICATIONS.) | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. SOME PANEL SCHEDULE SHOW DEMAND FACTORS | | | FOR DWELLING UNITS. THE NEC DEFINES A DWELLING UNIT AS: | | | ?A SINGLE UNIT, PROVIDING COMPLETE AND INDEPENDENT | | | LIVING FACILITIES FOR ONE OR MORE PERSONS, INCLUDING | | | PERMANENT PROVISIONS FOR LIVING, SLEEPING, COOKING, AND | | | SANITATION.? THIS DEFINITION DOES NOT MATCH THIS | | | FACILITY, SO THESE DEMAND FACTORS SHOULD NOT BE USED. | | | ALSO, PROVIDE LOAD CALCULATION FOR BUS DUCT. NEC 100, | | | 215.2, 220, 408.30 (NEED FURTHER EXPLANATION OF LOAD ON | | | SERVICE. THE FEEDERS AND OVERCURRENT PROTECTION SHOULD | | | BE SIZED TO HANDLE 100% OF THE NON-CONTINUOUS LOAD PLUS | | | 125% OF THE CONTINUOUS LOAD. THE ONLY CONTINUOUS LOAD | | | SHOWN IS FOR LIGHTING, THE LARGEST MOTOR LOAD IS NOT | | | SHOWN ON ANY SCHEDULES. ADDITIONALLY, THE RISER DIAGRAM | | | SHOWS A FUTURE POOL, BUT NO LOAD IS INCLUDED FOR THIS. | | | PROVIDE CORRECTIONS. NEC 215.2, 215.3, 220.14(C), | | | 430.24) | | | 7. CORRECTED. | | | 8. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE | | | CONFIRMED BY INSPECTOR. | | | 9. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE | | | CONFIRMED BY INSPECTOR. | | | 10. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE | | | CONFIRMED BY INSPECTOR. | | | 11. CORRECTED. | | | 12. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING | | | ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE | | | FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | | APPLICABLE TO COMPLY WITH CODE. IT APPEARS THAT SOME | | | SCHEDULES ARE MISSING AND SOME HAVE INFORMATION THAT IS | | | TBD. PROVIDE COMPLETED SCHEDULES. PANEL SCHEDULES | | | SHOULD INCLUDE UNIQUE IDENTIFIERS FOR CIRCUITS, SUCH AS | | | ROOM NUMBERS OR LOCATIONS. GENERAL TERMS ARE NOT | | | ACCEPTABLE. NEC 210.8, 210.12, 215.5, 408.4 | | | | | | NEW COMMENTS: | | | | | | 13. THE FOLLOWING PANELS ARE SHOWN WITH A 125 MAIN | | | CIRCUIT BREAKER, BUT HAVE A LOAD THAT EXCEEDS 125 AMP: | | | PANEL EML, 4LA, 5LA, 6LA, 7LA, 8LA 9LA, 10LA. PROVIDE | | | CORRECTION. NEC 215.3 | | | 14. PANEL EMH SHOWS A LOAD OF 400.36 AMPS ON A?, WHICH | | | EXCEEDS THE RATING OF THE PANEL AND THE CONDUCTORS | | | FEEDING THE PANEL. IN ADDITION TO THIS, THE LARGEST | | | MOTOR DEMAND AT 125% HAS NOT BEEN INCLUDED, WHICH WOULD | | | FURTHER OVERLOAD THIS PANEL AND CONDUCTORS. PROVIDE | | | CORRECTION. NEC 215.2, 215.3, 310.15(B)(16) | | | 15. PROVIDE VOLTAGE DROP CALCULATION FOR FEEDER NUMBER | | | 7 FROM GENERATOR TO TRANSFER SWITCH TO CONFIRM THE | | | CONDUCTOR SIZE IS ADEQUATE FOR CODE COMPLIANCE. PROVIDE | | | A NOTE TO INCLUDE INDICATION OF SUBMITTAL OF COMPLETION | | | DOCUMENTS PER FBC EC C405.6.4, FBC EC C405.6.3, NEC | | | 695.7 | | | 16. IT APPEARS THE GENERATOR WILL BE OVERLOADED AS | | | PANEL EMH SHOWS A LOAD OF 330.7 KVA BEFORE CORRECTIONS | | | NOTED IN COMMENT # 14. PROVIDE CORRECTION. NEC 701.4, | | | 695.3(D)(1) | | | 17. PLAN SHOWS THE FIRE PUMP CONTROLLER BEING FED FROM | | | PANEL EMH THROUGH ATS-1. THIS ATS IS REQUIRED TO BE | | | LISTED FOR USE WITH FIRE PUMP EQUIPMENT. PROVIDE SPEC | | | SHEET TO CONFIRM LISTING. NEC 110.3, 695.10 | | | 18. IF THE FIRE PUMP CONTROLLER IS FED FROM PANEL EMH | | | AS SHOWN, THIS BREAKER WILL NEED TO COMPLY WITH NEC | | | 695.4(B)(3)(B) THROUGH (E). SHOW METHOD OF COMPLIANCE. | | | 19. THE PREFERRED METHOD OF CONNECTION FROM THE | | | GENERATOR TO THE FIRE PUMP CONTROLLER PER THE NEC WOULD | | | BE A DIRECT CONNECTION WITH THE GENERATOR HAVING TWO | | | BREAKERS, ONE DEDICATED TO ATS-1 AND ONE DEDICATED TO | | | THE FIRE PUMP CONTROLLER, WHICH WOULD BE A LISTED FIRE | | | PUMP CONTROLLER WITH BUILT IN ATS. THIS IS HOW WE | | | NORMALLY SEE THIS TYPE OF INSTALLATION DESIGNED. THE | | | DESIGN SHOWN IS PERMITTED, BUT MUST COMPLY WITH | | | COMMENTS 17 AND 18 ABOVE. IF THE PREFERRED METHOD | | | MENTIONED IN THE NEC IS USED, COMMENTS 17 AND 18 DO NOT | | | APPLY. NEC 695.4(A) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-02-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-02-19 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-02-18 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2018-02-19 10:04:54 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA | | | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS | | | PRESENT. FBC 105.1, 107.2.1 | | | 2. THERE IS A SYMBOL ON THE RISER DIAGRAM SEVERAL TIMES | | | THAT LOOKS LIKE A SYMBOL FOR AN EXIT LIGHT. WHAT DOES | | | THIS SYMBOL MEAN? FBC 107.2.1 | | | 3. RISER DIAGRAM SHOWS 3 MAINS. IT APPEARS MAIN # 1 AND | | | 2 ARE LOCATED IN MDB AND MAIN # 3 IS IN A SEPARATE | | | LOCATION. SHOULD MDB BE LABELED MDP? THERE IS A NOTE | | | THAT THIS EQUIPMENT IS RATED FOR 12000 AMPS, PROVIDE | | | CLARIFICATION AND/OR CORRECTION. PROVIDE PANEL SCHEDULE | | | FOR THIS PANEL. ALSO, I DO NOT SEE MAIN # 3 IN THE | | | ELECTRICAL ROOM (ROOM 127). PROVIDE CLARIFICATION AND | | | NAMES FOR EACH MAIN. WHAT IS THE RATING OF MAIN #1? | | | ALSO, FOR PANEL ?MDB?, THERE APPEARS TO ONLY BE 17? | | | CLEARANCE FOR THIS? PROVIDE CORRECTIONS AND/OR | | | CLARIFICATIONS AS NEEDED. FBC 107.2.1; NEC 110.26, | | | 695.3 | | | 4. ELECTRICAL SCHEDULE PROVIDED ON SHEET E-401 IS | | | UNREADABLE. PROVIDE CLEAR SCHEDULE. FBC 107.2.1 | | | 5. THERE DOESN?T APPEAR TO BE THE PROPER CLEARANCE | | | BETWEEN THE FIRE PUMP CONTROLLER/ATS AND THE FIRE PUMP. | | | PROVIDE CORRECTION. NEC 110.26 | | | 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. SOME PANEL SCHEDULE SHOW DEMAND FACTORS | | | FOR DWELLING UNITS. THE NEC DEFINES A DWELLING UNIT AS: | | | ?A SINGLE UNIT, PROVIDING COMPLETE AND INDEPENDENT | | | LIVING FACILITIES FOR ONE OR MORE PERSONS, INCLUDING | | | PERMANENT PROVISIONS FOR LIVING, SLEEPING, COOKING, AND | | | SANITATION.? THIS DEFINITION DOES NOT MATCH THIS | | | FACILITY, SO THESE DEMAND FACTORS SHOULD NOT BE USED. | | | ALSO, PROVIDE LOAD CALCULATION FOR BUS DUCT. NEC 100, | | | 215.2, 220, 408.30 | | | 7. PROVIDE WIRE SIZES FOR ANY NEW FEEDERS TO BE | | | INSTALLED NEC 215.2, 215.5 | | | 8. SHEET E-102, THE 2ND FLOOR ELECTRICAL ROOM, LOCATION | | | OF THE 75 KVA TRANSFORMER DOES NOT HAVE THE PROPER | | | CLEARANCE. PROVIDE CORRECTION. NEC 110.26 | | | 9. SHEET E-103, THE 3RD FLOOR TO 9TH FLOOR ELECTRICAL | | | ROOMS, LOCATION OF THE 75 KVA TRANSFORMER DOES NOT HAVE | | | THE PROPER CLEARANCE. PROVIDE CORRECTION. NEC 110.26 | | | 10. SHEET E-104, THE 10TH FLOOR ELECTRICAL ROOM, | | | LOCATION OF THE 75 KVA TRANSFORMER DOES NOT HAVE THE | | | PROPER CLEARANCE. PROVIDE CORRECTION. NEC 110.26 | | | 11. SHEET E-105, PROVIDE GFCI PROTECTED OUTLET FOR | | | SERVICING OF A/C EQUIPMENT PER CODE. NEC 210.63 | | | 12. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING | | | ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE | | | FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | | APPLICABLE TO COMPLY WITH CODE. IT APPEARS THAT SOME | | | SCHEDULES ARE MISSING AND SOME HAVE INFORMATION THAT IS | | | TBD. PROVIDE COMPLETED SCHEDULES. PANEL SCHEDULES | | | SHOULD INCLUDE UNIQUE IDENTIFIERS FOR CIRCUITS, SUCH AS | | | ROOM NUMBERS OR LOCATIONS. GENERAL TERMS ARE NOT | | | ACCEPTABLE. NEC 210.8, 210.12, 215.5, 408.4 | | | | | | BECAUSE OF MISSING INFORMATION ON THE PLANS SUBMITTED, | | | FURTHER COMMENTS ARE POSSIBLE. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-05-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-05-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-05-17 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2018-05-17 12:57:45 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE EXIT PATH FROM THE SERVICE COURTYARD GOES THRU A | | | DOUBLE GATE. THE GATE SHALL BE ACCESSIBLE AND FUNCTION | | | AS AN EXIT DOOR AT ALL TIMES. | | | CLOSE COORDINATION WITH THE OFFICE OF FIRE MARSHAL FOR | | | EXIT FUNCTIONALITY IS REQUIRED. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-03-28 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-03-28 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-03-28 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-02-13 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-02-13 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-02-13 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2018-02-13 14:21:05 | PERMIT # 18020254 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED PROVISO: | | | | | | 1) AT A PRE-PERMIT MEETING ON JANUARY 25, 2018, IT WAS | | | STATED THAT THE PLANS WERE BEING DRAWN IN ACCORDANCE | | | WITH THE PREVIOUS EDITIONS (NOT CURRENT EDITIONS) OF | | | THE FBC AND FFC. | | | PLEASE UPDATE THE CODE LIST TO REFERENCE THE 5TH | | | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH | | | CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 | | | WITH FLORIDA AMENDMENTS. | | | IF THIS REQUEST IS NO LONGER BEING MADE, PLEASE UPDATE | | | THE CODE LIST TO REFERENCE THE 6TH EDITION OF THE | | | FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE 2015 | | | EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | 2) PER NFPA 1: 16.3.5 STANDPIPES. IN ALL NEW BUILDINGS | | | IN WHICH STANDPIPES ARE REQUIRED OR WHERE STANDPIPES | | | EXIST IN BUILDINGS BEING ALTERED OR DEMOLISHED, SUCH | | | STANDPIPES SHALL BE MAINTAINED IN CONFORMITY WITH THE | | | PROGRESS OF BUILDING CONSTRUCTION IN SUCH A MANNER THAT | | | THEY ARE ALWAYS READY FOR USE. [241:7.6] | | | | | | 3) PER NFPA 1: 13.3.2.6 * EXTERIOR ROOFS, CANOPIES, | | | PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR | | | PROJECTIONS. THE PORTE-COCHERE SHALL BE PROTECTED BY | | | THE PROVIDED FIRE SPRINKLER SYSTEM. | | | 13.3.2.6.1 : UNLESS THE REQUIREMENTS OF 13.3.2.6.2, | | | 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE | | | INSTALLED UNDER EXTERIOR ROOFS, CANOPIES, | | | PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR | | | PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. | | | [13:8.15.7.1] | | | | | | 4) PER NFPA 101: 11.8.6.2 -- THE EMERGENCY COMMAND | | | CENTER SHALL CONTAIN THE FOLLOWING: | | | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS | | | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION | | | SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER | | | SECTION OF THIS CODE | | | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION | | | PANELS | | | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS | | | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS | | | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE | | | PROVIDED IN ACCORDANCE WITH ASME A17.1/CSA B44 | | | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS | | | (8) EMERGENCY GENERATOR STATUS INDICATORS | | | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING | | | SYSTEM | | | (10) FIRE PUMP STATUS INDICATORS | | | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE PUBLIC TELEPHONE SYSTEM | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-16 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-16 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2018-05-16 15:03:24 | GAS PROVISO: | | | | | | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, | | | SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL | | | GAS CODE SEC. 502 THRU 505. SUBMIT CALCULATIONS FOR | | | COMBUSTION AIR PER THE FBC-2014 FUEL GAS CODE SEC. 304. | | | FOR BOILERS | | | | | | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. FOR BOILER AND DRYERS | | | | | | PROVIDE BEFORE ROUGH INSPECTION. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-03-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-12 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-12 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2018-03-12 12:06:35 | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS | | | INSTALLATION OR MODIFICATION OF SYSTEM. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-05-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-05-15 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-05-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-10 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-02 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-04-18 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2018-04-18 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-03-27 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-03-13 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-02-09 |
Time |
12:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-05-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-21 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-21 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2018-05-21 09:07:26 | MU-2018-17263, PAID $121,778.88 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-02-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-02-14 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2018-02-15 16:22:47 | 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-16 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-07 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2018-05-07 17:09:04 | MECHANICAL PLANS APPROVED WITH EXECEPTION AND PROVISOS. | | | 5/16/18 | | | | | | AS OF 5/16/18 THE FOLLOWING LIST OF COMMENTS FROM THE | | | 3RD REVIEW WERE NOT ADDRESSED, HOWEVER DUE TO THE | | | URGENT NEED TO HAVE THE PERMIT ISSUED, THE CURRENT | | | MECHANICAL PLANS AND DOCUMENTS ARE APPROVED WITH | | | EXCEPTION, AND THE REMAINING COMMENTS LISTED BELOW ARE | | | DEEMED TO BE PROVISOS TO BE ADDRESSED BY THE DESIGN | | | PROFESSIONAL AS SOON AS POSSIBLE. | | | | | | 3RD REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | | CODE | | | PERMIT #18020254 | | | 5/7/2018 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | THIS FOLLOW-UP (3RD) REVIEW IS BASED ON THE RESUBMITTED | | | PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE | | | ENGINEER OF RECORD. | | | ALL PREVIOUS REVIEW COMMENTS NOT COMPLETELY RESOLVED | | | ARE LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER. | | | | | | 2) THE BTUH CAPACITY OF THE BOILER AS SHOWN IN THE | | | ENERGY CALCULATIONS DOES NOT MATCH THE CAPACITY IN THE | | | SCHEDULE ON SHEET M-601. | | | | | | 5) PLEASE INCLUDE IN THE SMOKE CONTROL OUTLINE A | | | NARRATIVE THAT CLARIFIES THE SEQUENCE OF OPERATION OF | | | THE SMOKE CONTROL SYSTEM DURING AN ALARM AND THAT | | | ANSWERS THESE QUESTIONS: | | | | | | A) WILL ALL PRESSURIZATION FANS ACTIVATE DURING AN | | | ALARM? | | | B) HOW WILL THE PRESSURIZATIONS IN THE STAIRWELL AND | | | ELEVATOR SHAFTS MODULATE AND BE MONITORED? WILL THE | | | SYSTEMS BE DIGITALLY CONTROLLED USING SENSORS AND A | | | DIGITAL CONTROL PANEL? I AM NOT SEEING ANY CONTROLS IN | | | THE FA DRAWINGS, OR ANY CONTROL DIAGRAMS FOR SMOKE | | | CONTROL SEQUENCING. | | | D) WHAT IS THE SEQUENCE OF OPERATION FOR THE DOA UNITS | | | DURING AN ALARM PERTAINING TO THE FLOOR OF INCIDENT AND | | | THE UNINVOLVED FLOORS ABOVE AND BELOW? | | | E) WHAT IS THE SEQUENCE OF OPERATION FOR THE FIRE/SMOKE | | | DAMPERS AT THE SHAFTS ON EACH FLOOR? | | | F) WHAT SYSTEMS WILL BE CONNECTED TO STANDBY POWER? | | | G) WHAT IS THE RESPONSE TIME OF THE FANS, DAMPERS, | | | ETC.? | | | H) WHAT WILL BE THE DURATION OF THE OPERATION? | | | I) CLARIFY HOW SMOKE REMOVAL WILL BE ACCOMPLISHED. THE | | | NARRATIVE RESPONSE TO THIS COMMENT INDICATES REMOVAL BY | | | NATURAL MEANS- OPERABLE WINDOWS IN ACCORDING WITH | | | SECTION 403.4.7 ITEM #1. PLEASE NOTE THAT THE PLANS DO | | | NOT PROVIDE A SCHEDULE FOR THE WINDOWS ON THE BUILDING | | | PERIMETER WHICH IS NEEDED TO VERIFY COMPLIANCE. | | | J) PROVIDE CONTROL DIAGRAMS ON THE PLANS SHOWING THE | | | SEQUENCE OF OPERATION FOR THE SMOKE CONTROL SYSTEM. | | | | | | 5 CONTINUED) CONCERNING THE "EXIT VESTIBULE" | | | VENTILATION, THE ENGINEER IS STATING IN THE NARRATIVE | | | THAT THE "VESTIBULES" ARE NOT REQUIRED, HOWEVER THE | | | "EXIT VESTIBULES" ARE SHOWING ON ALL THE RESIDENTIAL | | | FLOORS AT STAIRS #235-935. PLEASE REFER TO SECTION | | | 909.20.3.3 FOR VENTILATION REQUIREMENTS FOR VESTIBULES. | | | BASED ON THAT REQUIREMENT, IT SEEMS POSSIBLE THAT | | | DEFINING THESE AREAS | | | | | | AS "VESTIBULES" MAY BE INCORRECT. FURTHER, I AM NOT | | | SEEING ANY REFERENCES OR DEFINITIONS IN THE BUILDING | | | CODE FOR "EXIT VESTIBULES". | | | | | | 5 CONTINUED) SHEET M-106: CLARIFY WHY SMOKE DETECTORS | | | ARE TO BE INSTALLED ADJACENT TO THE STAIRWELL FANS. | | | WHICH CODE, STANDARD, OR ENGINEERING ANALYSIS DOES THIS | | | REQUIREMENT COME FROM? PLEASE NOTE THAT THE REQUIREMENT | | | IN SECTION 606.2.1 IS FOR AIR HANDLING SYSTEMS. | | | | | | 5 CONTINUED) SHEET M-601: NOTE #9 SPECIFYING A SECOND | | | DRIVE BELT HAS NOT BEEN ADDED TO THE NOTES UNDER EACH | | | SMOKE CONTROL FAN. CLARIFY IS THE FANS WILL BE UL 705 | | | LISTED AND LABELED AS POWER VENTILATORS. | | | | | | 5 CONTINUED) CLASS 1 MOTORIZED DAMPERS REQUIRED ON | | | STAIRWAY AND ELEVATOR RELIEF VENTS, AND ON O/A AND | | | EXHAUST DUCTS AT THE SHAFT PENETRATIONS- SECTION | | | C403.2.4.3 | | | | | | 7) SHEET M-401: PLEASE INCLUDE THE EXHAUST CLEARANCE | | | DISTANCES TO ADJOINING GRADE AND PROPERTY LINES PER | | | SECTION 501.3.1(2). | | | | | | 9) CONCERNING THE KEF INLINE FAN, PLEASE CLARIFY IF THE | | | GREASE EXHAUST DUCT IS TO BE FIRE-WRAPPED. IF SO, THE | | | FAN MUST BE IN A FIRE RATED ROOM EQUAL TO RATING OF THE | | | WRAPPING- SECTION 506.5.1.2 | | | | | | ADDITIONAL COMMENTS: | | | | | | 1) MECHANICAL ROOM DOORS #241 & 349, 449, 549, 649, | | | 749, 849, & 949 MUST BE NON-COMBUSTIBLE- SECTION | | | C403.2.9.2 & SECTION 602.2.1. | | | | | | 2) M-601: MAKEUP AIR FOR THE HOOD CANNOT BE USED AS | | | COMBUSTION AIR FOR THE COOKING APPLIANCES. THAT AIR IS | | | SOLEY FOR REPLACEMENT OF EXHAUSTED AIR- SECTION 304.9.1 | | | PLEASE SEE SECTION 304.9.3: WHERE COMBUSTION AIR IS | | | PROVIDED BY MECHANICAL VENTILATION, THE SYSTEM SHALL | | | PROVIDE THE COMBUSTION AIR RATE IN ADDITION TO THE | | | REQUIRED VENTILATION AIR. THE RATE SHALL BE 0.35 CFMS | | | PER | | | | | | 1000 BTUH. | | | | | | 3) DEFERRED SUBMITTALS: 9) THE FOLLOWING IS A LIST OF | | | DEFERRED SUBMITTALS FOR THE MECHANICAL PERMIT THAT WILL | | | REQUIRE SHOP DRAWING APPROVAL BY THE ENGINEER OF | | | RECORD: | | | | | | A) SMOKE CONTROL FANS. | | | B) FIRE AND FIRE/SMOKE DAMPERS. | | | C) BAROMETRIC DAMPERS | | | D) DUCT SMOKE DETECTORS | | | E) AC ROOF AND DUCT STANDS, WALL BRACKETS | | | F) EXHAUST AND OUTSIDE AIR LOUVERS | | | G) PIPING INSULATIONS | | | H) ACCESS PANELS | | | I) GENERATOR | | | J) COMMERCIAL CLOTHES DRYERS | | | K) COOKING APPLIANCES | | | L) DUCT FIRE WRAPPING | | | M) FIRESTOPPING AND FIRE CAULKING | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-04-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-04-12 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-04-06 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2018-04-12 09:03:16 | 2ND REVIEW FBC-2017 MECHANICAL, BUILDING, EXISTING | | | BUILDING, ENERGY CONSERVATION CODES | | | PERMIT #18020254 | | | 4/11/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | THIS FOLLOW-UP REVIEW IS BASED ON THE RESUBMITTED | | | PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE | | | ENGINEER OF RECORD. | | | ALL 1ST REVIEW COMMENTS NOT COMPLETELY RESOLVED ARE | | | LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER. | | | | | | COMMENT #2) A) THE REVISED ENERGYGAUGE COMPLIANCE FORM | | | DOES NOT LIST THE G2 SYSTEM WHICH IS LISTED IN AC | | | SCHEDULE AT 18,800 BTUH (15.74 SEER). B) THE C-1,2 | | | SYSTEMS SHOWN IN THE REPORT ARE NOT IN THE SCHEDULE. C) | | | THE COMPLIANCE DATA LISTED FOR WSHP 2-1 & 2-2 IN THE | | | REPORT DOES NOT MATCH THE SCHEDULE. | | | D) THE SEER FOR WSHP-1-5 LISTED IN THE FORM DOES NOT | | | MATCH THE SCHEDULE. | | | | | | 4) COMMISSIONING: A) THE SUBMITTED PLAN IS INDICATING | | | THAT THE CONSTRUCTION CONTRACTOR SHALL BE THE | | | RESPONSIBLE PARTY TO OVERSEE THE COMMISSIONING PROCESS, | | | HOWEVER IT IS THE RESPONSIBILITY OF THE LICENSED MEP | | | ENGINEERS OR APPROVED AGENCY TO PROVIDE EVIDENCE OF | | | SYSTEM COMMISSIONING PER SECTION C408.2. FURTHER, | | | SECTION C408.2.1 ITEM #1 SPECIFIES THAT THE LICENSED | | | ENGINEERS OR APPROVED AGENCY NAME OR SELECT THE | | | PERSONNEL INTENDED TO ACCOMPLISH EACH OF THE | | | ACTIVITIES. B) PLEASE REVIEW THE FOLLOWING CODE | | | SECTIONS PERTAINING TO COMMISSIONING AND PROVIDE MORE | | | SPECIFIC INFORMATION ON THE PROPOSED COMMISSIONING | | | PLAN: C408.2.2, C408.2.2.1, C408.2.3, C408.2.3.1, | | | C408.2.3.1, AND (C408.3- PLEASE NOTE THE SUBMITTED PLAN | | | DOES NOT PROVIDE ANY DETAILS FOR THE LIGHTING SYSTEMS | | | FUNCTIONAL TESTING.) B) ADVISORY: PLEASE REVIEW SECTION | | | C408.2.4 PERTAINING TO THE PRELIMINARY COMMISSIONING | | | REPORT TO BE COMPLETED AND CERTIFIED BY THE LICENSED | | | ENGINEER, AND THEN SUBMITTED TO THE BUILDING OWNERSHIP | | | AND THE BUILDING DEPARTMENT FOR REVIEW. | | | | | | 5) THE SMOKE CONTROL RATIONAL ANALYSIS DOES NOT ADDRESS | | | MANY OF THE COMPLIANCES LISTED UNDER SECTION 513- | | | PLEASE REVIEW SECTION 513.6.3 FBC-17 MECHANICAL: | | | PRESSURIZED STAIRWAYS AND ELEVATOR HOISTWAYS: WHERE | | | STAIRWAYS OR ELEVATOR HOISTWAYS ARE PRESSURIZED, SUCH | | | PRESSURIZATION SYSTEMS SHALL COMPLY WITH SECTION 513 AS | | | SMOKE CONTROL SYSTEMS, IN ADDITION TO THE REQUIREMENTS | | | OF SECTIONS 909.20 OF THE FLORIDA BUILDING CODE, | | | BUILDING AND THE FLORIDA FIRE PREVENTION CODE. | | | PLEASE REVIEW AND INCLUDE IN THE REPORT REQUIRED | | | INFORMATION AS OUTLINED IN SECTION 513 INCLUDING, BUT | | | NOT LIMITED TO: 513.2 GENERAL DESIGN REQUIREMENTS | | | INCLUDING APPLICABLE CODES AND STANDARDS. 513.3 SPECIAL | | | INSPECTION AND TEST REQUIREMENTS. 513.4.4 HVAC SYSTEMS. | | | 513.4.6 DURATION OF OPERATION. 513.4.7 SMOKE CONTROL | | | SYSTEM INTERACTION. 513.5 SMOKE BARRIER CONSTRUCTION. | | | 513.5.1 TOTAL LEAKAGE AREA. 513.5.2 TESTING OF LEAKAGE | | | AREA. 513.5.3 OPENING PROTECTION. 513.10 EQUIPMENT. | | | 513.10.5 FANS. 513.11 STANDBY POWER. 513.11.1 EQUIPMENT | | | ROOM. 513.12 DETECTION AND CONTROL SYSTEMS. 513.16 | | | FIREFIGHTER'S SMOKE CONTROL PANEL. | | | | | | 5) CONTINUED- CONCERNING THE REDESIGN USING VESTIBULES | | | AT STAIR #2 LOCATION ON THE RESIDENTIAL FLOORS, THE | | | CODE GIVES TWO OPTIONS FOR VENTILATION- NATURAL OR | | | MECHANICAL- SECTIONS 909.20.3 AND 909.20.4 FBC-17 | | | BUILDING. BECAUSE NATURAL VENTILATION IS NOT POSSIBLE, | | | MECHANICAL VENTILATION MUST BE PROVIDED PER SECTION | | | 909.20.4.2. PLEASE REVIEW THIS SECTION AND SECTIONS | | | 909.20.4.4 AND 909.20.5 STAIRWAY AND RAMP | | | PRESSURIZATION ALTERNATIVE. 909.20.4.4 REQUIRES A | | | DAMPERED RELIEF OPENING IN THE STAIRWAY. 909.20.5 | | | PROVIDES THE DESIGN PARAMETERS FOR PRESSURIZATION OF | | | THE STAIRWAYS. | | | | | | 5) CONTINUED- THE SELECTED SMOKE CONTROL FANS SHOWN IN | | | THE SCHEDULE ARE NOT COMPLETELY IN COMPLIANCE WITH | | | SECTION 513.10.5 WHICH REQUIRES BELTED FANS TO HAVE 1.5 | | | TIMES THE NUMBER OF BELTS FOR THE DESIGN DUTY WITH THE | | | MINIMUM NUMBER OF BELTS BEING TWO. THE FANS MUST ALSO | | | BE UL LISTED AS POWER VENTILATORS FOR SMOKE CONTROL | | | SYSTEMS. | | | | | | 5) CONTINUED- PLEASE REVIEW THE FOLLOWING CODE SECTIONS | | | THAT APPLY TO THE PRESSURIZED ELEVATOR HOISTWAYS, AND | | | REVISE THE ANALYSIS AND PLANS TO SHOW COMPLIANCE. | | | 909.21 ELEVATOR HOISTWAY PRESSURIZATION ALTERNATIVE. | | | WHERE ELEVATOR HOISTWAY PRESSURIZATION IS PROVIDED IN | | | LIEU OF REQUIRED ENCLOSED ELEVATOR LOBBIES, THE | | | PRESSURIZATION SYSTEM SHALL COMPLY WITH SECTIONS | | | 909.21.1 THROUGH 909.21.11. | | | 909.21.1 PRESSURIZATION REQUIREMENTS. | | | ELEVATOR HOISTWAYS SHALL BE PRESSURIZED TO MAINTAIN A | | | MINIMUM POSITIVE PRESSURE OF 0.10 INCH OF WATER (25 PA) | | | AND A MAXIMUM POSITIVE PRESSURE OF 0.25 INCH OF WATER | | | (67 PA) WITH RESPECT TO ADJACENT OCCUPIED SPACE ON ALL | | | FLOORS. THIS PRESSURE SHALL BE MEASURED AT THE MIDPOINT | | | OF EACH HOISTWAY DOOR, WITH ALL ELEVATOR CARS AT THE | | | FLOOR OF RECALL AND ALL HOISTWAY DOORS ON THE FLOOR OF | | | RECALL OPEN AND ALL OTHER HOISTWAY DOORS CLOSED. THE | | | PRESSURE DIFFERENTIALS SHALL BE MEASURED BETWEEN THE | | | HOISTWAY AND THE ADJACENT ELEVATOR LANDING. THE OPENING | | | AND CLOSING OF HOISTWAY DOORS AT EACH LEVEL MUST BE | | | DEMONSTRATED DURING THIS TEST. THE SUPPLY AIR INTAKE | | | SHALL BE FROM AN OUTSIDE, UNCONTAMINATED SOURCE LOCATED | | | A MINIMUM DISTANCE OF 20 FEET (6096 MM) FROM ANY AIR | | | EXHAUST SYSTEM OR OUTLET. | | | EXCEPTIONS: | | | 1. ON FLOORS CONTAINING ONLY GROUP R OCCUPANCIES, THE | | | PRESSURE DIFFERENTIAL IS PERMITTED TO BE MEASURED | | | BETWEEN THE HOISTWAY AND A DWELLING UNIT OR SLEEPING | | | UNIT. | | | 2. WHERE AN ELEVATOR OPENS INTO A LOBBY ENCLOSED IN | | | ACCORDANCE WITH SECTION 3007.6 OR 3008.6, THE PRESSURE | | | DIFFERENTIAL IS PERMITTED TO BE MEASURED BETWEEN THE | | | HOISTWAY AND THE SPACE IMMEDIATELY OUTSIDE THE DOOR(S) | | | FROM THE FLOOR TO THE ENCLOSED LOBBY. | | | 3. THE PRESSURE DIFFERENTIAL IS PERMITTED TO BE | | | MEASURED RELATIVE TO THE OUTDOOR ATMOSPHERE ON FLOORS | | | OTHER THAN THE FOLLOWING: | | | 1.THE FIRE FLOOR. | | | 2. THE TWO FLOORS IMMEDIATELY BELOW THE FIRE FLOOR. | | | 3. THE FLOOR IMMEDIATELY ABOVE THE FIRE FLOOR. | | | 4. THE MINIMUM POSITIVE PRESSURE OF 0.10 INCH OF WATER | | | (25 PA) AND A MAXIMUM POSITIVE PRESSURE OF 0.25 INCH OF | | | WATER (67 PA) WITH RESPECT TO OCCUPIED FLOORS ARE NOT | | | REQUIRED AT THE FLOOR OF RECALL WITH THE DOORS OPEN. | | | 909.21.1.1 USE OF VENTILATION SYSTEMS. | | | VENTILATION SYSTEMS, OTHER THAN HOISTWAY SUPPLY AIR | | | SYSTEMS, ARE PERMITTED TO BE USED TO EXHAUST AIR FROM | | | ADJACENT SPACES ON THE FIRE FLOOR, TWO FLOORS | | | IMMEDIATELY BELOW AND ONE FLOOR IMMEDIATELY ABOVE THE | | | FIRE FLOOR TO THE BUILDING'S EXTERIOR WHERE NECESSARY | | | TO MAINTAIN POSITIVE PRESSURE RELATIONSHIPS AS REQUIRED | | | IN SECTION 909.21.1 DURING OPERATION OF THE ELEVATOR | | | SHAFT PRESSURIZATION SYSTEM. | | | 909.21.2 RATIONAL ANALYSIS. | | | A RATIONAL ANALYSIS COMPLYING WITH SECTION 909.4 SHALL | | | BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. | | | 909.21.3 DUCTS FOR SYSTEM. | | | ANY DUCT SYSTEM THAT IS PART OF THE PRESSURIZATION | | | SYSTEM SHALL BE PROTECTED WITH THE SAME FIRE-RESISTANCE | | | RATING AS REQUIRED FOR THE ELEVATOR SHAFT ENCLOSURE. | | | 909.21.4 FAN SYSTEM. | | | THE FAN SYSTEM PROVIDED FOR THE PRESSURIZATION SYSTEM | | | SHALL BE AS REQUIRED BY SECTIONS 909.21.4.1 THROUGH | | | 909.21.4.4. | | | 909.21.4.1 FIRE RESISTANCE. | | | WHERE LOCATED WITHIN THE BUILDING, THE FAN SYSTEM THAT | | | PROVIDES THE PRESSURIZATION SHALL BE PROTECTED WITH THE | | | SAME FIRE-RESISTANCE RATING REQUIRED FOR THE ELEVATOR | | | SHAFT ENCLOSURE. | | | 909.21.4.2 SMOKE DETECTION. | | | THE FAN SYSTEM SHALL BE EQUIPPED WITH A SMOKE DETECTOR | | | THAT WILL AUTOMATICALLY SHUT DOWN THE FAN SYSTEM WHEN | | | SMOKE IS DETECTED WITHIN THE SYSTEM. | | | 909.21.4.3 SEPARATE SYSTEMS. | | | A SEPARATE FAN SYSTEM SHALL BE USED FOR EACH ELEVATOR | | | HOISTWAY. | | | 909.21.4.4 FAN CAPACITY. | | | THE SUPPLY FAN SHALL BE EITHER ADJUSTABLE WITH A | | | CAPACITY OF NOT LESS THAN 1,000 CFM (0.4719 M3/S) PER | | | DOOR, OR THAT SPECIFIED BY A REGISTERED DESIGN | | | PROFESSIONAL TO MEET THE REQUIREMENTS OF A DESIGNED | | | PRESSURIZATION SYSTEM. | | | 909.21.5 STANDBY POWER. | | | THE PRESSURIZATION SYSTEM SHALL BE PROVIDED WITH | | | STANDBY POWER IN ACCORDANCE WITH SECTION 2702. | | | 909.21.6 ACTIVATION OF PRESSURIZATION SYSTEM. | | | THE ELEVATOR PRESSURIZATION SYSTEM SHALL BE ACTIVATED | | | UPON ACTIVATION OF EITHER THE BUILDING FIRE ALARM | | | SYSTEM OR THE ELEVATOR LOBBY SMOKE DETECTORS. WHERE | | | BOTH A BUILDING FIRE ALARM SYSTEM AND ELEVATOR LOBBY | | | SMOKE DETECTORS ARE PRESENT, EACH SHALL BE | | | INDEPENDENTLY CAPABLE OF ACTIVATING THE PRESSURIZATION | | | SYSTEM. | | | 909.21.7 TESTING. | | | TESTING FOR PERFORMANCE SHALL BE REQUIRED IN ACCORDANCE | | | WITH SECTION 909.18.8. SYSTEM ACCEPTANCE SHALL BE IN | | | ACCORDANCE WITH SECTION 909.19. | | | 909.21.8 MARKING AND IDENTIFICATION. | | | DETECTION AND CONTROL SYSTEMS SHALL BE MARKED IN | | | ACCORDANCE WITH SECTION 909.14. | | | 909.21.9 CONTROL DIAGRAMS. | | | CONTROL DIAGRAMS SHALL BE PROVIDED IN ACCORDANCE WITH | | | SECTION 909.15.909.21.10 CONTROL PANEL. | | | A CONTROL PANEL COMPLYING WITH SECTION 909.16 SHALL BE | | | PROVIDED. | | | 909.21.11 SYSTEM RESPONSE TIME. | | | HOISTWAY PRESSURIZATION SYSTEMS SHALL COMPLY WITH THE | | | REQUIREMENTS FOR SMOKE CONTROL SYSTEM RESPONSE TIME IN | | | SECTION 909.17. | | | | | | 5) CONTINUED: REFER TO SECTION 403.4.7 FBC-17 BUILDING | | | SMOKE REMOVAL AND INDICATE COMPLIANCE IN THE ANALYSIS | | | AND THE PLANS. | | | | | | 6) CONCERNING THE RISERS, SHOW LOCATIONS OF THE | | | BAROMETRIC DAMPERS IN THE STAIR SHAFTS AND THE VENTS IN | | | THE HOISTWAYS, IF APPLICABLE TO THE PROPOSED SMOKE | | | CONTROL DESIGN. | | | | | | 7) AS PREVIOUSLY NOTED, THE STANDBY POWER SOURCE AND | | | ITS TRANSFER SWITCHES SHALL BE IN A ROOM SEPARATE FROM | | | THE NORMAL POWER TRANSFORMERS AND SWITCH GEAR. SHEET | | | E-401 SHOWS ATS-1 IN THE MAIN ELECTRICAL ROOM. | | | | | | 9) ADVISORY NOTES FOR THE KITCHEN EXHAUST SYSTEM: A) | | | SEPARATE PERMIT REQUIRED. B) THE GREASE DUCT SHALL HAVE | | | A MINIMUM 18" CLEARANCE TO COMBUSTIBLE CONSTRUCTION. C) | | | EXHAUST FAN MOTORS SHALL BE LOCATED OUTSIDE OF THE | | | EXHAUST AIRSTREAM. D) WHERE ENCLOSED DUCT SYSTEMS ARE | | | CONNECTED TO IN-LINE FANS NOT LOCATED OUTDOORS, THE FAN | | | SHALL BE LOCATED IN A ROOM OR SPACE HAVING THE SAME | | | FIRE-RESISTANCE RATING AS THE DUCT ENCLOSURE. E) THE | | | EXHAUST OUTLET TERMINATION AT THE SIDEWALL SHALL BE | | | LOCATED SO AS NOT TO CAUSE A PUBLIC NUISANCE OR A FIRE | | | HAZARD. F) THE TEMPERATURE DIFFERENTIAL BETWEEN THE | | | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL | | | NOT EXCEED 10 DEGREES F. | | | | | | 12) FIRE DAMPERS REQUIRED FOR THE 60X10 RA GRILL AT | | | HVAC 134. | | | | | | 13) ACKNOWLEDGED THAT MANUFACTURER'S SPECIFICATIONS FOR | | | THE COMMERCIAL DRYERS WILL BE A DEFERRED SUBMITTAL, AND | | | WILL THE SUBMITTAL WILL BEAR AND APPROVAL STAMP BY THE | | | EOR. | | | | | | 18) ACKNOWLEDGED THAT ACCESS PANELS WILL BE PROVIDED | | | FOR HEAT PUMPS ABOVE HARD CEILINGS AS SHOWN ON | | | ARCHITECTURAL RCP PLANS. PLEASE NOTE THAT THE PANELS | | | SHALL BE CONSTRUCTED WITH NON-COMBUSTIBLE MATERIALS | | | WHERE INSTALLED IN ABOVE-CEILING PLENUM SPACES, AND | | | MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED. | | | | | | 26) ACKNOWLEDGED THAN MANUFACTURER'S SPECIFICATIONS FOR | | | THE GENERATOR SHALL BE A DEFERRED SUBMITTAL WITH | | | APPROVAL STAMP BY THE EOR. PLEASE NOTE THE GENERATOR | | | SHALL MEET THE REQUIREMENTS OF UL 2200- SECTION 915.1 | | | FBC-17 MECHANICAL. | | | | | | 26) SHEET 401: PLEASE PROVIDE NOTES AND/OR DIMENSIONS | | | TO VERIFY ALL REQUIRED CLEARANCES FOR THE RADIATOR AND | | | ENGINE EXHAUST TERMINATIONS ARE IN COMPLIANCE WITH | | | SECTION 501.3.1 (2). | | | | | | 31 & 32) THE ENGINEER HAS INDICATED IN HIS RESPONSE | | | THAT THE FOLLOWING LIST OF MECHANCIAL EQUIPMENT AND | | | COMPONENTS ETC. SHALL BE DEFERRED SUBMITTALS: | | | A) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S | | | FOR THE LOUVERS, AC STANDS, WALL BRACKETS, DUCT AND | | | PIPE STANDS AND BRACKETS. | | | B) MANUFACTURER'S SPECIFICATIONS FOR THE SMOKE CONTROL | | | FANS, MOTORIZED DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE | | | DETECTORS, BOILERS AND WATER HEATERS, GENERATOR, | | | DRYERS, COOKING APPLIANCES, PLENUM-RATED ACCESS PANELS, | | | FIRE WRAPPING, FIRESTOPPING AND FIRE CAULKING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-02-26 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-02-23 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2018-02-26 15:42:42 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #18020254 | | | 2/23/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ELECTRONIC SIGNATURES ARE REQUIRED ON THE MECHANICAL | | | PLANS, AND THE FOLLOWING LIST OF DOCUMENTS: ENERGYGAUGE | | | COMPLIANCE FORM, THE AC LOAD CALCULATIONS, AND THE | | | VENTILATION CALCULATIONS- SECTIONS 61G15-23.002 AND | | | 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. | | | | | | 2) THE ENERGYGAUGE REPORT IS MISSING COMPLIANCE DATA | | | FOR OAU- 1 & 2, AND WSHP 1-3. TO HELP EXPEDITE THE | | | REVIEW, PLEASE IDENTIFY THE OTHER SYSTEMS IN THE REPORT | | | SO THEY MATCH THE IDENTIFICATIONS IN THE SCHEDULES ON | | | SHEET M-601. | | | | | | 3) AC CALCULATIONS: PLEASE CLARIFY WHY NO OUTDOOR | | | VENTILATION DATA IS PROVIDED, AND WHY THE O/A DB/WB LOW | | | TEMPS FOR THE COMMON AREAS AND KITCHEN ARE NOT | | | CONSISTENT WITH ASHRAE 183 OR ACCA MANUAL N. | | | | | | 4) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH C407 | | | FBC-17 ENERGY CONSERVATION. PLEASE NOTE THE HOTEL ROOM | | | AC SYSTEMS ARE EXEMPT FROM THE REPORT. | | | | | | 5) PLEASE REFER TO BUILDING REVIEW COMMENT # 2C: THE | | | TWO PRESSURIZED INTERIOR EXIT STAIRWAYS #111 AND 114 | | | ARE EXITING INTO COMMON CORRIDORS AND NOT INTO EXIT | | | DISCHARGES OR EXIT PASSAGEWAYS AS REQUIRED BY SECTIONS | | | 1023.2 AND 1023.11.1 FBC-17 BUILDING. IN ORDER FOR THE | | | EXISTING MEANS OF EGRESS SYSTEM TO BE IN COMPLIANCE | | | WITH THE CURRENT CODES, THE GROUND FLOOR CORRIDORS THAT | | | ARE FORMING THE PATHS OF TRAVEL TO THE EXTERIOR OF THE | | | BUILDING, MAY HAVE TO BE RE- CONSTRUCTED AS EXIT | | | PASSAGEWAYS AND BECOME EXTENSIONS OF THE SMOKEPROOF | | | ENCLOSURES- STAIRWAYS #111 AND 114. IN ADDITION THE | | | PASSAGEWAYS SHALL BE PRESSURIZED EQUALLY TO THE | | | PRESSURIZATION RATES PROVIDED FOR THE STAIRWAYS. | | | CURRENTLY THERE IS NO SMOKE CONTROL RATIONAL ANALYSIS | | | PROVIDED FOR THE PROPOSED PROJECT TO VERIFY THE CURRENT | | | SYSTEM DESIGN WILL PROVIDE A TENABLE ENVIRONMENT FOR | | | THE EVACUATION AND RELOCATION OF THE OCCUPANTS. PLEASE | | | REVIEW SECTION 513 IN ENTIRETY AND PROVIDE A RATIONAL | | | ANALYSIS REPORT THAT ENCOMPASSES ALL COMPLIANCES AS | | | OUTLINED IN THE SUB-SECTIONS. ALL MECHANICAL COMPONENTS | | | AND EQUIPMENT SUCH AS FANS, DUCTS, DAMPERS ETC. SHALL | | | CORRESPOND WITH THE SPECIFICATIONS LISTED IN THE | | | REPORT. THE REPORT SHALL INCLUDE, BUT NOT BE LIMITED TO | | | THE FOLLOWING REQUIREMENTS LISTED IN SECTION 513. | | | | | | 513.6 PRESSURIZATION METHOD. | | | THE PRIMARY MECHANICAL MEANS OF CONTROLLING SMOKE SHALL | | | BE BY PRESSURE DIFFERENCES ACROSS SMOKE BARRIERS. | | | MAINTENANCE OF A TENABLE ENVIRONMENT IS NOT REQUIRED IN | | | THE SMOKE CONTROL ZONE OF FIRE ORIGIN. | | | 513.6.1 MINIMUM PRESSURE DIFFERENCE. | | | THE MINIMUM PRESSURE DIFFERENCE ACROSS A SMOKE BARRIER | | | SHALL BE 0.05-INCH WATER GAGE (12.4 PA) IN FULLY | | | SPRINKLERED BUILDINGS. | | | IN BUILDINGS PERMITTED TO BE OTHER THAN FULLY | | | SPRINKLERED, THE SMOKE CONTROL SYSTEM SHALL BE DESIGNED | | | TO ACHIEVE PRESSURE DIFFERENCES NOT LESS THAN TWO TIMES | | | THE MAXIMUM CALCULATED PRESSURE DIFFERENCE PRODUCED BY | | | THE DESIGN FIRE. | | | 513.6.2 MAXIMUM PRESSURE DIFFERENCE. | | | THE MAXIMUM AIR PRESSURE DIFFERENCE ACROSS A SMOKE | | | BARRIER SHALL BE DETERMINED BY REQUIRED DOOR-OPENING OR | | | CLOSING FORCES. THE ACTUAL FORCE REQUIRED TO OPEN EXIT | | | DOORS WHEN THE SYSTEM IS IN THE SMOKE CONTROL MODE | | | SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, | | | BUILDING. OPENING AND CLOSING FORCES FOR OTHER DOORS | | | SHALL BE DETERMINED BY STANDARD ENGINEERING METHODS FOR | | | THE RESOLUTION OF FORCES AND REACTIONS. THE CALCULATED | | | FORCE TO SET A SIDE-HINGED, SWINGING DOOR IN MOTION | | | SHALL BE DETERMINED BY: | | | (EQUATION 5-1) | | | WHERE: | | | A = DOOR AREA, SQUARE FEET (M2). | | | D = DISTANCE FROM DOOR HANDLE TO LATCH EDGE OF DOOR, | | | FEET (M). | | | F = TOTAL DOOR OPENING FORCE, POUNDS (N). | | | FDC = FORCE REQUIRED TO OVERCOME CLOSING DEVICE, POUNDS | | | (N). | | | K = COEFFICIENT 5.2 (1.0). | | | W = DOOR WIDTH, FEET (M). | | | P = DESIGN PRESSURE DIFFERENCE, INCHES (PA) WATER GAGE. | | | | | | 513.6.3 PRESSURIZED STAIRWAYS AND ELEVATOR HOISTWAYS. | | | WHERE STAIRWAYS OR ELEVATOR HOISTWAYS ARE PRESSURIZED, | | | SUCH PRESSURIZATION SYSTEMS SHALL COMPLY WITH SECTION | | | 513 AS SMOKE CONTROL SYSTEMS, IN ADDITION TO THE | | | REQUIREMENTS OF SECTIONS 909.20 OF THE FLORIDA BUILDING | | | CODE, BUILDING AND THE FLORIDA FIRE PREVENTION CODE. | | | | | | 513.10 EQUIPMENT. | | | EQUIPMENT SUCH AS, BUT NOT LIMITED TO, FANS, DUCTS, | | | AUTOMATIC DAMPERS AND BALANCE DAMPERS SHALL BE SUITABLE | | | FOR THEIR INTENDED USE, SUITABLE FOR THE PROBABLE | | | EXPOSURE TEMPERATURES THAT THE RATIONAL ANALYSIS | | | INDICATES, AND AS APPROVED BY THE CODE OFFICIAL. | | | | | | 513.10.1 EXHAUST FANS. | | | COMPONENTS OF EXHAUST FANS SHALL BE RATED AND CERTIFIED | | | BY THE MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE | | | TO WHICH THE COMPONENTS WILL BE EXPOSED. THIS | | | TEMPERATURE RISE SHALL BE COMPUTED BY: | | | | | | (EQUATION 5-2) | | | WHERE: | | | C = SPECIFIC HEAT OF SMOKE AT SMOKE-LAYER TEMPERATURE, | | | BTU/LB F (KJ/KG K). | | | M = EXHAUST RATE, POUNDS PER SECOND (KG/S). | | | QC = CONVECTIVE HEAT OUTPUT OF FIRE, BTU/S (KW). | | | TA = AMBIENT TEMPERATURE, F (K). | | | TS = SMOKE TEMPERATURE, F (K). | | | EXCEPTION: REDUCED TS AS CALCULATED BASED ON THE | | | ASSURANCE OF ADEQUATE DILUTION AIR. | | | | | | 513.10.2 DUCTS. | | | DUCT MATERIALS AND JOINTS SHALL BE CAPABLE OF | | | WITHSTANDING THE PROBABLE TEMPERATURES AND PRESSURES TO | | | WHICH THEY ARE EXPOSED AS DETERMINED IN ACCORDANCE WITH | | | SECTION 513.10.1. DUCTS SHALL BE CONSTRUCTED AND | | | SUPPORTED IN ACCORDANCE WITH CHAPTER 6. DUCTS SHALL BE | | | LEAK TESTED TO 1.5 TIMES THE MAXIMUM DESIGN PRESSURE IN | | | ACCORDANCE WITH NATIONALLY ACCEPTED PRACTICES. MEASURED | | | LEAKAGE SHALL NOT EXCEED 5 PERCENT OF DESIGN FLOW. | | | RESULTS OF SUCH TESTING SHALL BE A PART OF THE | | | DOCUMENTATION PROCEDURE. DUCTS SHALL BE SUPPORTED | | | DIRECTLY FROM FIRE-RESISTANCE-RATED STRUCTURAL ELEMENTS | | | OF THE BUILDING BY SUBSTANTIAL, NONCOMBUSTIBLE | | | SUPPORTS. | | | EXCEPTION: FLEXIBLE CONNECTIONS, FOR THE PURPOSE OF | | | VIBRATION ISOLATION, THAT ARE CONSTRUCTED OF APPROVED | | | FIRE-RESISTANCE-RATED MATERIALS. | | | | | | 513.10.3 EQUIPMENT, INLETS AND OUTLETS. | | | EQUIPMENT SHALL BE LOCATED SO AS TO NOT EXPOSE | | | UNINVOLVED PORTIONS OF THE BUILDING TO AN ADDITIONAL | | | FIRE HAZARD. OUTDOOR AIR INLETS SHALL BE LOCATED SO AS | | | TO MINIMIZE THE POTENTIAL FOR INTRODUCING SMOKE OR | | | FLAME INTO THE BUILDING. EXHAUST OUTLETS SHALL BE SO | | | LOCATED AS TO MINIMIZE REINTRODUCTION OF SMOKE INTO THE | | | BUILDING AND TO LIMIT EXPOSURE OF THE BUILDING OR | | | ADJACENT BUILDINGS TO AN ADDITIONAL FIRE HAZARD. | | | | | | 513.10.4 AUTOMATIC DAMPERS. | | | AUTOMATIC DAMPERS, REGARDLESS OF THE PURPOSE FOR WHICH | | | THEY ARE INSTALLED WITHIN THE SMOKE CONTROL SYSTEM, | | | SHALL BE LISTED AND CONFORM TO THE REQUIREMENTS OF | | | APPROVED RECOGNIZED STANDARDS. | | | | | | 513.10.5 FANS. | | | IN ADDITION TO OTHER REQUIREMENTS, BELT-DRIVEN FANS | | | SHALL HAVE 1.5 TIMES THE NUMBER OF BELTS REQUIRED FOR | | | THE DESIGN DUTY WITH THE MINIMUM NUMBER OF BELTS BEING | | | TWO. FANS SHALL BE SELECTED FOR STABLE PERFORMANCE | | | BASED ON NORMAL TEMPERATURE AND, WHERE APPLICABLE, | | | ELEVATED TEMPERATURE. CALCULATIONS AND MANUFACTURER?S | | | FAN CURVES SHALL BE PART OF THE DOCUMENTATION | | | PROCEDURES. FANS SHALL BE SUPPORTED AND RESTRAINED BY | | | NONCOMBUSTIBLE DEVICES IN ACCORDANCE WITH THE | | | STRUCTURAL DESIGN REQUIREMENTS OF THE FLORIDA BUILDING | | | CODE, BUILDING. MOTORS DRIVING FANS SHALL NOT BE | | | OPERATING BEYOND THEIR NAMEPLATE HORSEPOWER (KILOWATTS) | | | AS DETERMINED FROM MEASUREMENT OF ACTUAL CURRENT DRAW. | | | MOTORS DRIVING FANS SHALL HAVE A MINIMUM SERVICE FACTOR | | | OF 1.15. | | | | | | 513.11 STANDBY POWER. | | | THE SMOKE CONTROL SYSTEM SHALL BE SUPPLIED WITH STANDBY | | | POWER IN ACCORDANCE WITH SECTION 2702 OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 513.11.1 EQUIPMENT ROOM. | | | THE STANDBY POWER SOURCE AND ITS TRANSFER SWITCHES | | | SHALL BE IN A ROOM SEPARATE FROM THE NORMAL POWER | | | TRANSFORMERS AND SWITCH GEAR AND VENTILATED DIRECTLY TO | | | AND FROM THE EXTERIOR. THE ROOM SHALL BE ENCLOSED WITH | | | NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED FIRE | | | BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OF | | | THE FLORIDA BUILDING CODE, BUILDING OR HORIZONTAL | | | ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711 | | | OF THE FLORIDA BUILDING CODE, BUILDING, OR BOTH. | | | | | | 513.11.2 POWER SOURCES AND POWER SURGES. | | | ELEMENTS OF THE SMOKE MANAGEMENT SYSTEM RELYING ON | | | VOLATILE MEMORIES OR THE LIKE SHALL BE SUPPLIED WITH | | | UNINTERRUPTIBLE POWER SOURCES OF SUFFICIENT DURATION TO | | | SPAN 15-MINUTE PRIMARY POWER INTERRUPTION. ELEMENTS OF | | | THE SMOKE MANAGEMENT SYSTEM SUSCEPTIBLE TO POWER SURGES | | | SHALL BE SUITABLY PROTECTED BY CONDITIONERS, | | | SUPPRESSORS OR OTHER APPROVED MEANS. | | | | | | 513.12 DETECTION AND CONTROL SYSTEMS. | | | FIRE DETECTION SYSTEMS PROVIDING CONTROL INPUT OR | | | OUTPUT SIGNALS TO MECHANICAL SMOKE CONTROL SYSTEMS OR | | | ELEMENTS THEREOF SHALL COMPLY WITH THE REQUIREMENTS OF | | | SECTION 907 OF THE FLORIDA BUILDING CODE, BUILDING. | | | SUCH SYSTEMS SHALL BE EQUIPPED WITH A CONTROL UNIT | | | COMPLYING WITH UL 864 AND LISTED AS SMOKE CONTROL | | | EQUIPMENT. | | | | | | 6) PLEASE PROVIDE STAIR AND ELEVATOR PRESSURIZATION | | | RISER DRAWINGS SHOWING THE LOCATIONS OF BAROMETRIC | | | RELIEF DAMPS AND HOISTWAY VENTS. | | | | | | 7) CONCERNING SECTION 513.11.1 LISTED ABOVE, PLEASE | | | SHOW THE LOCATION OF THE GENERATOR TRANSFER SWITCHES. | | | | | | 8) SHEET M-106: SEPARATE PERMITS ARE REQUIRED FOR THE | | | KITCHEN HOOD, FIRE SUPPRESSION SYSTEM, AND WALK IN | | | COOLER AND FREEZER, HOWEVER AN AIR BALANCE CALCULATION | | | IS REQUIRED PER SECTION 508.1.2: | | | 508.1.2AIR BALANCE. | | | DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN | | | VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM | | | INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN | | | OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND | | | REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET | | | EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR | | | AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE | | | PLUS THE NET EXFILTRATION. | | | | | | 9) M-106: AS STATED IN THE PREVIOUS COMMENT, A SEPARATE | | | PERMIT IS REQUIRED FOR THE KITCHEN HOOD AND EXHAUST | | | SYSTEM, HOWEVER IT IS IMPORTANT TO NOTE AT THIS TIME OF | | | THE MAIN PERMIT AND PLANS THAT COMPLIANCE WITH SECTION | | | C403.2.8 FBC-17 ENERGY CONSERVATION IS REQUIRED. | | | C403.2.8 KITCHEN EXHAUST SYSTEMS | | | REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST | | | HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE | | | HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR | | | DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF | | | THE FOLLOWING: | | | 1. THE VENTILATION RATE REQUIRED TO MEET THE SPACE | | | HEATING OR COOLING LOAD. | | | 2. THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER | | | AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS | | | CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT | | | REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS | | | RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION | | | OF ADJACENT SPACES. | | | WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS | | | GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A | | | FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A | | | NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE | | | WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST | | | RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY | | | WITH ONE OF THE FOLLOWING: | | | 1. NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR | | | SHALL BE TRANSFER AIR THAT WOULD OTHERWISE BE | | | EXHAUSTED. | | | 2. DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75 | | | PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS | | | THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT | | | AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY | | | TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION | | | AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE, | | | EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND | | | IDLE. | | | 3. LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT | | | RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON | | | NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW. | | | WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER | | | APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM | | | ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL | | | BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE | | | DUTY RATING UNDER THE HOOD OR HOOD SECTION. | | | EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE | | | REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE | | | EXHAUSTED. | | | | | | 10) M-101: VERIFY THAT EXHAUST HOOD GREASE DUCT IS NOT | | | TERMINATING ABOVE A WALKWAY OR ANYPLACE THAT COULD | | | CREATE A PUBLIC NUISANCE OR FIRE HAZARD- SECTION | | | 506.3.13.2. PROVIDE THE HEIGHT OF THE OUTLET ABOVE THE | | | ADJOINING GRADE. | | | | | | 11) M-101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE | | | SUPPLY TRUNKS OF WSHP-1-1 AND WSHP-1-4 PER SECTION | | | 606.2.1. PLEASE NOTE AN EXEMPTION CAN BE APPLIED TO 1-4 | | | IF MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | 12) M-101 & M-102: THE OUTSIDE AIR DUCT DOES NOT APPEAR | | | TO BE MAKING DIRECT CONNECTIONS TO WSHP-1-5, 1-6, AND | | | 1-7- PLEASE CLARIFY. | | | | | | 13) M-101: PLEASE CLARIFY HOW SUPPLY AIR TO THE LOBBY, | | | MARKET PLACE, RECEPTION AREAS ETC. IS BEING RETURNED TO | | | WSHP-1-3- SECTION 601.6. | | | | | | 14) M-101: PROVIDE DRYER EXHAUST PLANS AND DETAILS PER | | | SECTION 504, AND SUBMIT MANUFACTURER'S SPECIFICATIONS | | | FOR THE DRYERS REVIEWED AND APPROVED BY THE DESIGNER OF | | | RECORD. | | | | | | 15) M-101: THE LAUNDRY SERVICE ROOM IS MISLABELED AS | | | THE CHEF'S OFFICE. | | | | | | 16) M-101: PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL | | | GAS-FIRED KITCHEN COOKING APPLIANCES AND SUBMIT | | | EQUIPMENT CUT SHEETS REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD- SECTIONS 304 AND 623.1 FBC-17 FUEL | | | GAS. PLEASE NOTE THERE DOES NOT APPEAR TO BE FOOD | | | SERVICE PLANS INCLUDED IN THE SETS- PLEASE PROVIDE | | | THEM. | | | | | | 17) M-102: A DUCT SMOKE DETECTOR IS REQUIRED IN THE | | | SUPPLY TRUNK OF WSHP-2-2 PER SECTION 606.2.1. | | | | | | 18) M-102: FIRE DAMPERS NOT SHOWN AT A) THE O/A AND E/A | | | DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM | | | WALLS. B) THE S/A DUCT PENETRATION THROUGH THE | | | FIRE-RATED WALL AT ROOM 226/227. C) THE 8" E/A DUCT | | | PENETRATION THROUGH THE FIRE-RATED 227/231 WALL- | | | SECTION 607.5.2 & 607.5.3 | | | | | | 19) M-102: INDICATE HOW ACCESS FOR SERVICE AND | | | REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL | | | CEILINGS WILL BE PROVIDED- SECTION 306. | | | | | | 20) M-102: SHOW HOW SUPPLY AIR FROM WSHP-2-2 AND | | | WSHP-C-2 IS BEING RETURNED INTO THE MECHANICAL ROOM- | | | SECTION 601.6. | | | | | | 21) M-103: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A | | | DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM | | | WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-3 | | | PENETRATING THE FIRE-RATED 323/324/325 WALLS.- SECTION | | | 607.5.2 & 607.5.3 | | | | | | 22) M-103: INDICATE HOW ACCESS FOR SERVICE AND | | | REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL | | | CEILINGS WILL BE PROVIDED- SECTION 306. | | | | | | 23) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-3 IS BEING | | | RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6. | | | | | | 24) M-104: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A | | | DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM | | | WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-10 | | | PENETRATING THE FIRE-RATED 1023/1025 WALLS- SECTION | | | 607.5.2 & 607.5.3 | | | | | | 25) M-103: INDICATE HOW ACCESS FOR SERVICE AND | | | REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL | | | CEILINGS WILL BE PROVIDED- SECTION 306. | | | | | | 26) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-10 IS BEING | | | RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6. | | | | | | 27) M-401: PROVIDE AN ENLARGED PLAN OF THE GENERATOR | | | THAT PROVIDES DETAILS FOR THE ENGINE AND RADIATOR | | | EXHAUST SYSTEMS, AND THE ROOM VENTILATION. CLARIFY IF | | | THE GENERATOR HAS A BELLY TANK FOR DIESEL FUEL OR IF | | | THERE IS TO BE A SEPARATE TANK AND TANK ROOM PROVIDED. | | | SUBMIT MANUFACTURER'S SPECIFICATIONS REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD. | | | | | | 28) M-501: PROVIDE WSHP INSTALLATION DETAILS. | | | | | | 29) M-502: THE RTU ATTACHMENT DETAIL TO THE CURB IS FOR | | | A CARRIER UNIT, HOWEVER THE SYSTEMS SELECTED ARE TRANE- | | | PLEASE CORRECT. | | | | | | 30) M-601: PLEASE PROVIDE COMPLETE WINDLOAD ENGINEERING | | | FOR INSTALLATION OF THE OAU'S, THE ROOF AND WALL FANS, | | | THE ROOFTOP DUCTWORK, AND THE WATER PIPING. PLEASE | | | INCLUDE THE WIND LOAD DESIGN CRITERIA AND DETAILS FOR | | | ATTACHING THE CURBS AND BRACKETS TO THE ROOF STRUCTURE, | | | AND THE UNITS TO THE CURBS AND BRACKETS- SECTION | | | 301.15. | | | | | | 31) PROVIDE A CONDENSATE DISPOSAL PLAN AND RISER | | | DRAWING- SECTION 307. | | | | | | 32) PROVIDE FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE | | | NOA'S FOR ALL EXTERIOR EXHAUST AND O/A INLET LOUVERS, | | | AC STANDS AND WALL BRACKETS, DUCT AND PIPE STANDS AND | | | BRACKETS- RULE 9N-03 FAC. | | | | | | 32) REQUIRED SUBMITTALS TO BE REVIEWED AND APPROVED BY | | | THE DESIGNER OF RECORD: PRODUCT APPROVALS AND NOA?S, | | | SMOKE CONTROL FANS, FIRE AND FIRE/SMOKE DAMPERS, | | | MOTORIZED DAMPERS, DUCT SMOKE DETECTORS, BOILER AND | | | WATER HEATERS, COOKING APPLIANCES, PLENUM RATED ACCESS | | | PANELS FOR ABOVE CEILING HEAT PUMPS AND FANS, | | | GENERATOR, FIRE CAULKING AND FIRE WRAPPING. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-05-04 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-04 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-04 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-04-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-16 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-13 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2018-04-16 16:04:15 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED WITH. | | | | | | 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. | | | PER WPB AMEND TO FBC 107.2.1 | | | DESIGN MANUAL WAS NOT IN SUBMITTAL PLEASE DOWN LOAD | | | MANUAL UNDER SUPPORTING DOCUMENTS | | | | | | 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE | | | (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER | | | FBC PL 316.1.3 AND 919.1 | | | PLEASE PROVIDE DOCUMENTATION FROM THE MANUFACTURE | | | STATING THEY REVIEWED AND APPROVED YOUR DESIGN. | | | | | | 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE | | | SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US | | | FOOD CODE CH 5 AND FBC EX 1010.2 | | | COULD NOT LOCATE NOTE ON PLAN PLEASE PROVIDE SHEET | | | NUMBER SHOULD BE LOCATED ON BOTH ISOMETRIC AND FLOOR | | | PLAN AND AND PROVIDE DETAIL OF WHAT TYPE OF SHIELDING | | | OR PAN WILL BE USED. | | | | | | NEW COMMENT: | | | 1. SHT. 702 SHOWS THE CONDENSATE RECOVERY PUMP | | | DISCHARGING INTO THE SANITARY ALL CONDENSATE SHALL | | | DISCHARGE TO STORM OR TO PERMEABLE GROUND IT IS | | | PROHIBITED TO DISCHARGE TO THE SANITARY. PER CITY OF | | | WPB CODE OF ORDINANCE SEC. 90-126. (5) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-03-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-12 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-08 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2018-03-12 12:03:06 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN | | | WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON | | | THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS | | | CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED | | | 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT | | | SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD | | | CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT | | | CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED. | | | PER FBC PL 1108.1 | | | | | | 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB | | | BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE | | | GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. | | | OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE | | | CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER | | | FBC ACC 604.5.1 | | | | | | 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH | | | DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL | | | 405.3.1 | | | | | | 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB | | | BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR | | | TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN | | | MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS | | | WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL | | | DETAILS. PER FBC ACC 609.4 | | | | | | 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM | | | OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34 | | | MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3 | | | | | | 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR | | | SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1 | | | | | | 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE | | | WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3 | | | | | | 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER | | | CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1 | | | | | | 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR | | | ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54? | | | OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL | | | DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC | | | 604.5.1 | | | | | | 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE | | | SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF | | | THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE | | | CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT | | | BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC | | | 609.4 | | | | | | 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING | | | KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3 | | | | | | 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON | | | BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE | | | ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM | | | 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1? | | | WALL THICKNESS. PER FBC ENERGY C404.4 | | | | | | 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS | | | BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE | | | COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK | | | IT SHALL CONNECT TO INTAKE OF THE BOILER. PER | | | MANUFACTURE INSTALL GUIDE | | | | | | 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE | | | (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER | | | FBC PL 316.1.3 | | | | | | 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER | | | ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON | | | THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE | | | INTERCEPTOR. PER FBC PL 1003.2 | | | | | | 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON | | | BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS | | | DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM | | | CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE | | | ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK. | | | | | | 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC | | | IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE | | | SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS | | | TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN | | | AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY | | | ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO | | | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW | | | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO | | | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB | | | AMEND TO FBC 107.3.5.1.3(13) | | | | | | 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON | | | THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701, | | | 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO | | | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW | | | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO | | | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB | | | AMEND TO FBC 107.3.5.1.3(13) | | | | | | 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER | | | DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT | | | AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC | | | VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1 | | | | | | 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6 | | | | | | 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE | | | SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US | | | FOOD CODE | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN | | | WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON | | | THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS | | | CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED | | | 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT | | | SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD | | | CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT | | | CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED. | | | PER FBC PL 1108.1 | | | | | | 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB | | | BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE | | | GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. | | | OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE | | | CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER | | | FBC ACC 604.5.1 | | | | | | 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH | | | DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL | | | 405.3.1 | | | | | | 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB | | | BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR | | | TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN | | | MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS | | | WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL | | | DETAILS. PER FBC ACC 609.4 | | | | | | 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM | | | OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34 | | | MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3 | | | | | | 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR | | | SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1 | | | | | | 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE | | | WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3 | | | | | | 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER | | | CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1 | | | | | | 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR | | | ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54? | | | OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL | | | DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC | | | 604.5.1 | | | | | | 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE | | | SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF | | | THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE | | | CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT | | | BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC | | | 609.4 | | | | | | 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING | | | KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3 | | | | | | 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON | | | BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE | | | ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM | | | 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1? | | | WALL THICKNESS. PER FBC ENERGY C404.4 | | | | | | 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS | | | BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE | | | COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK | | | IT SHALL CONNECT TO INTAKE OF THE BOILER. PER | | | MANUFACTURE INSTALL GUIDE | | | | | | 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE | | | (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER | | | FBC PL 316.1.3 | | | | | | 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER | | | ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON | | | THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE | | | INTERCEPTOR. PER FBC PL 1003.2 | | | | | | 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON | | | BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS | | | DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM | | | CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE | | | ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK. | | | | | | 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC | | | IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE | | | SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS | | | TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN | | | AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY | | | ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO | | | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW | | | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO | | | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB | | | AMEND TO FBC 107.3.5.1.3(13) | | | | | | 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON | | | THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701, | | | 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO | | | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW | | | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO | | | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB | | | AMEND TO FBC 107.3.5.1.3(13) | | | | | | 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER | | | DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT | | | AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC | | | VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1 | | | | | | 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6 | | | | | | 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE | | | SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US | | | FOOD CODE | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2018-05-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-17 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-17 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2018-05-17 11:48:59 | ****PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. CIVIL SHEETS ARE NOT DIGITALLY SIGNED AND SEALED. | | | PAPER ORIGINALS MAY BE PROVIDED TO RESOLVE THIS ISSUE. | | | | | | 2. FMEP SHEETS HAVE A SIGNATURE FROM DOCUSIGN. AS | | | DISCUSSED WITH BEN ELLIS, PE, WE ARE WAITING FOR A | | | REPLY FROM FBPE. THEY WILL ADVISE AS TO WHETHER OR NOT | | | THIS MEETS THE REQUIREMENT FOR DIGITAL SIGNATURE AND | | | SEAL. AS DISCUSSED, IF THEY DETERMINE THAT IT DOES NOT, | | | A PAPER ORIGINAL CAN SERVE AS A SIGNATURE DOCUMENT. | | | | | | IF WE DO NOT RECEIVE A RESPONSE FROM FBPE, A PAPER | | | ORIGINAL IS REQUIRED FOR ALL FMEP SHEETS AND SUPPORTING | | | DOCUMENTS. | | | | | | 3. ALL OTHER SHEETS ARE DIGITALLY SIGNED AND SEALED IN | | | ACCORDANCE WITH FLORIDA STATUTE 471, 481. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-05-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-08 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-08 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2018-05-08 17:45:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. CIVIL SHEETS ARE NOT DIGITALLY SIGNED AND SEALED. | | | PAPER ORIGINALS MAY BE PROVIDED TO RESOLVE THIS ISSUE. | | | | | | 2. FMEP SHEETS HAVE A SIGNATURE FROM DOCUSIGN. AS | | | DISCUSSED WITH BEN ELLIS, PE, WE ARE WAITING FOR A | | | REPLY FROM FBPE. THEY WILL ADVISE AS TO WHETHER OR NOT | | | THIS MEETS THE REQUIREMENT FOR DIGITAL SIGNATURE AND | | | SEAL. AS DISCUSSED, IF THEY DETERMINE THAT IT DOES NOT, | | | A PAPER ORIGINAL CAN SERVE AS A SIGNATURE DOCUMENT. | | | | | | IF WE DO NOT RECEIVE A RESPONSE FROM FBPE, A PAPER | | | ORIGINAL IS REQUIRED FOR ALL FMEP SHEETS AND SUPPORTING | | | DOCUMENTS. | | | | | | 3. ALL OTHER SHEETS ARE DIGITALLY SIGNED AND SEALED IN | | | ACCORDANCE WITH FLORIDA STATUTE 471, 481. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-04-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-13 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-04-13 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2018-04-13 11:56:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. CIVIL SHEETS ARE NOT DIGITALLY SIGNED AND SEALED. | | | PAPER ORIGINALS MAY BE PROVIDED TO RESOLVE THIS ISSUE. | | | | | | 2. FMEP SHEETS HAVE A SIGNATURE FROM DOCUSIGN. AS | | | DISCUSSED WITH BEN ELLIS, PE, WE ARE WAITING FOR A | | | REPLY FROM FBPE. THEY WILL ADVISE AS TO WHETHER OR NOT | | | THIS MEETS THE REQUIREMENT FOR DIGITAL SIGNATURE AND | | | SEAL. AS DISCUSSED, IF THEY DETERMINE THAT IT DOES NOT, | | | A PAPER ORIGINAL CAN SERVE AS A SIGNATURE DOCUMENT. | | | | | | 3. ALL OTHER SHEETS ARE DIGITALLY SIGNED AND SEALED IN | | | ACCORDANCE WITH FLORIDA STATUTE 471, 481. | | | | | | | | | | | | | | 2018-02-26 15:52:37 | MECHANICAL PLANS AND SUBMITTAL DOCUMENTS NOT | | | ELECTROCNICALLY SIGNED AND SEALED. | | | CCOLE- 2/26/18 |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2018-05-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-11 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-11 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2018-05-11 07:49:36 | SPECIAL INSPECTOR AGREEMENT ORIGINAL RECEIVED | | | GFA INTERNATIONAL | | | HECTOR VERGARA, PE25764, SI0283 | | | NOEL WOODALL, BN2505 | | | CARLTON CROOK, BN3909 | | | MARK SHARMAN, BN4742 | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2018-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-04-04 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-04-04 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2018-04-04 08:23:31 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 18020254 | | | ADD: 1675 PALM BEACH LAKES BLVD. | | | CONT: STRATICON LLC | | | TEL: 772-210-0200 STRATICON | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | | | | 2ND REVIEW | | | DATE: WED. APRIL 04/ 2018 | | | ACTION: DENIED | | | | | | 1) 2ND REQUEST. THRESHOLD BUILDING / FL S. S. 553.71(7) | | | ?THRESHOLD BUILDING". | | | THE RESPONSE IS THAT THE THRESHOLD DOCUMENTS WERE | | | SUBMITTED UNDER THE BUCK HOIST PERMIT. PLEASE NOTE THE | | | SUBMITTED FORMS DATED MARCH 29, 2017 WERE NOT COMPLETE | | | IN REQUIRED SIGNATURES. | | | THE CERTIFIED INSPECTION CO. LINE IS LEFT BLANK, NO | | | NOTARY WORK, CONTRACTOR SIGNATURE WITH NO NOTARY WORK, | | | MISSING THE ARCHITECT AND ENGINEERS SIGNATURE AND SEAL | | | AND NOTARY WORK, YOU SHOULD UPDATE YOUR SITE INSPECTOR | | | INFORMATION WHO IS STILL WITH THE COMPANY, MIKE ADAIR | | | IS NOW A CITY INSPECTOR. | | | | | | | | | THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. PLEASE | | | UPDATE FILES SINCE THEIR MAYBE ADDITIONAL PERSONNEL TO | | | ACT AS THE JOBSITE INSPECTOR. | | | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 1A)2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | | | | 1C)COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 1D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. | | | | | | 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING | | | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE | | | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND | | | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED | | | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM | | | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING | | | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT | | | THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2018-02-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-02-22 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-02-22 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2018-02-22 10:37:32 | DATE: 02/22/2018 | | | ORIGINAL DOCUMENTATION THRESHOLD INSPECTION FORMS GIVEN | | | TO CAROLINE PUELL FOR DIGITAL PLANS. | | | SPECIAL INSPECTION PLANS IN STRUCTURAL DRAWINGS, SHEET | | | S.1.02. | | | COPY OF DOCUMENTS GIVEN TO KEN CONRAD. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-04-18 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2018-04-18 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-04-18 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-03-12 |
|
|
Cont ID |
|
| Sent By |
AV |
Date |
2018-03-12 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-03-12 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2018-03-12 17:10:40 | 3/12/18- APPROVED WITH THE PROVISO THAT A SEPERATE | | | PERMIT IS REQUIRED FOR THE FOLLOWING: | | | | | | 1. A SEPARATE PERMIT IS REQUIRED FOR LANDSCAPING, | | | SIGNAGE, SWIMMING POOL, FENCES/WALLS, DUMPSTER | | | ENCLOSURE. | | | 2. A SEPARATE PERMIT IS REQUIRED FOR THE SHORT TERM | | | PARKING IN THE EXISTING GARAGE. | | | | | | ANGELLA VA | | | | | | | | | 561-822-1441 | | | [email protected] |
|
|
|