Plan Review Details - Permit 18020254
Plan Review Stops For Permit 18020254
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-05-16 Cont ID  
Sent By rmcdouga Date 2018-05-16 Time 17:54 Rev Time 0.00
Received By rmcdouga Date 2018-05-16 Time 17:13 Sent To  
Notes
2018-05-16 17:54:52APPROVED WITH EXCEPTIONS AND PROVISOS.
  
 1) ON SHEET 067-A-305 SECTION 2/A-3.05, THE 12"
 HORIZONTAL HANDRAIL EXTENSION IS REQUIRED TO RETURN TO
 A WALL, GUARD OR THE LANDING AT THE BOTTOM OF THE RAMP
 PER FBC ACCESSIBILITY SECTION 505.10.1.
  
 2) PROVISO/ DEFERRED SUBMITTAL. SUBMIT TWO SETS OF
 MANUFACTURER'S SPECIFICATIONS AND LISTING INFORMATION
 FOR REVIEW FOR THE LULA LIFT AT THE ENTRY PORT COCHERE.
  
 3) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR
 STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM,
 HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE
 DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS
 THE HARDWARE MEET COMPLIANCE WITH :
 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN
 POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND
 USABLE FROM BOTH SIDES.
  
 4) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A
 SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND
 CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 5) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) SEPARATE PERMITS REQUIRED. THE POOL, GENERATOR,
 KITCHEN HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE
 SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION
 PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT
 AND REQUIRE SEAPARTE PERMITS, PLAN REVIEWS AND FEES.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-10 Cont ID  
Sent By rmcdouga Date 2018-05-10 Time 18:32 Rev Time 0.00
Received By rmcdouga Date 2018-05-07 Time 09:03 Sent To  
Notes
2018-05-10 14:09:272017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020254
 ADD: 1675 PALM BEACH LAKES BLVD.
 CONT: STRATICON LLC
 TEL: 772-210-0200 STRATICON
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 3RD REVIEW
 DATE: WED. APRIL 04/ 2018
 ACTION: DENIED
  
 1) COMPLIED.
  
  
 1A) COMPLIED.
  
 1B) COMPLIED.
  
 1C) COMPLIED.
  
 1D) COMPLIED.
  
 1E) COMPLIED.
  
 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOB SITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 2) SHEET 042-LS-111 & 045-A-111:
  
 2A-2E) COMPLIED.
 * NEW COMMENT.
 1) THE OCCUPANT LOAD FOR THE 550 SQ.FT.EXERCISE ROOM IS
 INCORRECTLY LISTED AS 6. USING THE OCCUPANT LOAD FACTOR
 OF 50 GROSS FROM TABLE 1004.1.2 FOR EXERCISE ROOMS THE
 TOTAL OCCUPANTS WILL BE 11.
  
 2F) COMPLIED.
  
 2G-2K) COMPLIED.
  
  
 2L) SEMI-COMPLIED. THE LAUNDRY CHUTE DETAIL (6/A-5.02)
 ON SHEET 5.02 SHOWS FIRE SPRINKLER HEADS IN THE SHAFT.
 THESE ARE NOT SHOWN ON THE FIRE SPRINKLER PLANS. PLEASE
 CLARIFY. 903.2.11.2
  
 2M) COMPLIED.
  
 2N) COMPLIED.
  
 2O-Q) COMPLIED.
  
 2R) COMPLIED.
  
 2S) COMPLIED.
  
 2T) COMPLIED.
  
 2T)(2) COMPLIED.
  
 2U) PROVISO, NOTICE ONLY! POOL, GENERATOR, KITCHEN
 HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE
 SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION
 PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT
 AND ALL REQUIRE A SEPARATE REVIEW AND FEE.
  
 2V)COMPLIED.
  
 2W) PARTIAL COMPLIANCE. SHEET 005-GN-1 BUILDING CODE
 SUMMARY INDICATES THE PLANS WERE DEVELOPED A
 CONSTRUCTION TYPE II-A, THIS ONLY ALLOWS UNDER THE 2014
 CODE TABLE 503 A 4 STORY BUILDING WITH ONE STORY
 INCREASE, IT WOULD BE REQUIRED TO BE A CONSTRUCTION
 TYPE I-B . UNDER THE 2017 FBC-B TABLE 504.4 THE
 BUILDING TYPE WOULD ALSO BE REQUIRED TO BE I-B
 ALLOWABLE 12 STORIES WITH A FULL NFPA 13 SYSTEM, UNDER
 THE 2017 WITH FIRE SPRINKLERS A LL-A BUILDING IS ONLY
 ALLOWED TO BE 5 STORIES. SHEET 006-GN2 HAS TWO ERRORS
 THAT I CLOUDED IN RED.
  
 2X) COMPLIED. R-1 TRANSIENT A STAY30 DAYS OR LESS, SEE
 FBC-B 310.3 & 310.4.
  
 2Y)3RD REQUEST. SHEETS 042-ALS-111 NOR SHEET
 045-A-111-A SHOW THE LOCATION OF THE FIRE PUMP
 LOCATION. SHEET E-101 SHOWS THE FIRE PUMP IN THE
 MECHANICAL/ ELECTRICAL ROOM 127. PLEASE SHOW COMPLIANCE
 WITH:
 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL
 BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH
 SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS.
 FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 711, OR BOTH.
 EXCEPTIONS:
 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY
 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE
 PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2.
  
 3) SHEET 046-A-111-B:
  
 3A) 3RD REQUEST. THE COVERED ENTRY PORT COCHERE SHOWS
 THE USE OF A LULA LIFT, PLEASE PROVIDE CONFIRMATION THE
 LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION
 ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1
 REFERENCED STANDARDS. NOTE: MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION WILL HAVE TO BE
 SUBMITTED FOR REVIEW.
  
 3B) COMPLIED.(SUBJECT TO FIRE DEPARTMENT AND ELECTRICAL
 APPROVAL) 2ND REQUEST. SHEET 046-A-111-B SHOWS A NEW
 FIRE COMMAND ROOM.
 [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND
 EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY
 WITH SECTIONS 403.4.1 THROUGH 403.4.8.
  
 3C) [F]403.4.1 SMOKE DETECTION. SMOKE DETECTION SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.1.
  
 3D) [F]403.4.2 FIRE ALARM SYSTEM. A FIRE ALARM SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.
  
 3E) [F]403.4.3 STANDPIPE SYSTEM. A HIGH-RISE BUILDING
 SHALL BE EQUIPPED WITH A STANDPIPE SYSTEM AS REQUIRED
 BY SECTION 905.3.
  
 3F) [F]403.4.4 EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 3G) [F]403.4.5 EMERGENCY RESPONDER RADIO COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 3H) [F]403.4.6 FIRE COMMAND. A FIRE COMMAND CENTER
 COMPLYING WITH SECTION 911 SHALL BE PROVIDED IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 3I) COMPLIED, (SUBJECT TO FIRE DEPARTMENT AND
 MECHANICAL APPROVAL). 2ND REQUEST. 403.4.7 SMOKE
 REMOVAL. TO FACILITATE SMOKE REMOVAL IN POST-FIRE
 SALVAGE AND OVERHAUL OPERATIONS, BUILDINGS AND
 STRUCTURES SHALL BE EQUIPPED WITH NATURAL OR MECHANICAL
 VENTILATION FOR REMOVAL OF PRODUCTS OF COMBUSTION IN
 ACCORDANCE WITH ONE OF THE FOLLOWING:
 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR
 PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF
 EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM)
 INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL
 BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR
 FEET (15 240 MM) OF PERIMETER.
  
 EXCEPTIONS:
 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE
 HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE
 PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA
 IN LIEU OF THE AREA SPECIFIED IN ITEM 1.
 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT
 GLAZING CAN BE CLEARED BY FIRE FIGHTERS.
 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE
 EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA
 INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED
 DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER
 PORTIONS OF THE BUILDING.
 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE
 EQUIVALENT RESULTS.
  
 3J) COMPLIED.
  
 3K) COMPLIED.
  
 4A-D) COMPLIED. MATRIX PROVIDING THE TOTAL AMOUNT OF
 SLEEPING ROOMS ACCESSIBILITY.
 *NEW COMMENTS:
 1) ON SHEETS A-121 AND A-131 THE TOTAL OF REQUIRED
 COUNT OF ROOMS WITH MOBILITY FEATURES IS LISTED AS 2 IN
 THE ACCESSIBLE ROOM MATRIX. BASED ON THE ROOMS THAT ARE
 LISTED, THE TOTAL WOULD BE 9 RATHER THAN 2. ACTUALLY,
 ACCORDING TO TABLE 224.2 FOR 151 TO 200 ROOMS IN A
 TRANSIENT LODGING FACILITY THE MINIMUM NUMBER OF GUEST
 ROOMS WITH MOBILITY FEATURES IS A TOTAL OF 8. SIX (6)
 ROOMS WITHOUT ROLL-IN SHOWERS AND TWO (2) WITH ROLL-IN
 SHOWERS.
 2) 224.6.3 BUILDINGS, STRUCTURES, OR FACILITIES
 LICENSED AS A HOTEL, MOTEL, OR CONDOMINIUM PURSUANT TO
 CHAPTER 509, F.S. ALL BUILDINGS, STRUCTURES, OR
 FACILITIES LICENSED AS A HOTEL, MOTEL, OR CONDOMINIUM
 PURSUANT TO CHAPTER 509, F.S., A NUMBER OF ROOMS
 EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS MINUS
 THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS
 REQUIRED BY TABLE 224.2 SHALL PROVIDE SPECIAL
 ACCESSIBILITY FEATURES OF 806.4.
 806.4 HOTEL, MOTEL AND CONDOMINIUM SPECIAL
 ACCESSIBILITY FEATURES. THIS SECTION DOES NOT RELIEVE
 THE OWNER OF THE RESPONSIBILITY OF PROVIDING ACCESSIBLE
 ROOMS IN CONFORMANCE WITH SECTION 224 AND 806 OF THIS
 CODE. IN ALL BUILDINGS, STRUCTURES AND FACILITIES
 LICENSED AS A HOTEL, MOTEL OR RESORT CONDOMINIUM
 PURSUANT TO CHAPTER 509, F.S., A NUMBER OF ROOMS
 EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS MINUS
 THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS
 REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING
 ADDITIONAL SPECIAL ACCESSIBILITY FEATURES:
 (I)GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH
 COMPLY WITH SECTION 604.5.
 (II)ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL
 BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT
 DEVICES.
 (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4.
 190 GUEST ROOMS MINUS 8 REQUIRED ACCESSIBLE ROOMS
 EQUALS 182 ROOMS. FIVE (5) PERCENT OF 182 EQUALS 9.1.
 THEREFORE, IN ADDITION TO THE 8 REQUIRED ACCESSIBLE
 ROOMS, 10 ROOMS ARE REQUIRED TO HAVE THE SPECIAL
 ACCESSIBILITY FEATURES OF 806.4.
  
 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 &
 051-A-122:
  
 5A-F) COMPLIED.
 *NEW COMMENT. ON SHEET 044-LS-131 THE COMMON PATH OF
 TRAVEL IS NOT SHOWN CORRECTLY FOR GUEST ROOMS 322 THRU
 922 AND 302 THRU 902. COMMON PATH OF EGRESS TRAVEL IS
 MEASURED FROM THE MOST REMOTE POINT IN THE ROOM TO A
 POINT WHERE THE OCCUPANT HAS A CHOICE OF TWO SEPARATE
 AND DISTINCT PATHS TO THE TWO EXITS.
  
 6-7) COMPLIED.
 * NEW COMMENT.
 1) ON SHEET 067-A-305 SECTION 3/A-3.05, THE STAIR
 HANDRAIL EXTENSION IS INCORRECT. 1014.6 HANDRAIL
 EXTENSIONS. HANDRAILS SHALL RETURN TO A WALL, GUARD OR
 THE WALKING SURFACE OR SHALL BE CONTINUOUS TO THE
 HANDRAIL OF AN ADJACENT FLIGHT OF STAIRS OR RAMP RUN.
 WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
 2) ON SHEET 067-A-305 SECTION 2/A-3.05, THE HANDRAIL
 EXTENSION IS MISSING FROM THE RAMP. 1014.6 HANDRAIL
 EXTENSIONS. AT RAMPS WHERE HANDRAILS ARE NOT CONTINUOUS
 BETWEEN RUNS, THE HANDRAILS SHALL EXTEND HORIZONTALLY
 ABOVE THE LANDING 12 INCHES (305 MM) MINIMUM BEYOND THE
 TOP AND BOTTOM OF RAMP RUNS. THE EXTENSIONS OF
 HANDRAILS SHALL BE IN THE SAME DIRECTION OF THE FLIGHTS
 OF STAIRS AT STAIRWAYS AND THE RAMP RUNS AT RAMPS.
  
  
 8) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR
 STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM,
 HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE
 DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS
 THE HARDWARE MEET COMPLIANCE WITH :
 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN
 POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND
 USABLE FROM BOTH SIDES.
  
 9) COMPLIED.
  
 10) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A
 SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND
 CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 11) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 12) 3RD REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-04 Cont ID  
Sent By jwitmer Date 2018-04-04 Time 08:21 Rev Time 0.00
Received By jwitmer Date 2018-04-04 Time 08:21 Sent To  
Notes
2018-04-04 08:22:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020254
 ADD: 1675 PALM BEACH LAKES BLVD.
 CONT: STRATICON LLC
 TEL: 772-210-0200 STRATICON
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: WED. APRIL 04/ 2018
 ACTION: DENIED
  
 1) 2ND REQUEST. THRESHOLD BUILDING / FL S. S. 553.71(7)
 ?THRESHOLD BUILDING".
 THE RESPONSE IS THAT THE THRESHOLD DOCUMENTS WERE
 SUBMITTED UNDER THE BUCK HOIST PERMIT. PLEASE NOTE THE
 SUBMITTED FORMS DATED MARCH 29, 2017 WERE NOT COMPLETE
 IN REQUIRED SIGNATURES.
 THE CERTIFIED INSPECTION CO. LINE IS LEFT BLANK, NO
 NOTARY WORK, CONTRACTOR SIGNATURE WITH NO NOTARY WORK,
 MISSING THE ARCHITECT AND ENGINEERS SIGNATURE AND SEAL
 AND NOTARY WORK, YOU SHOULD UPDATE YOUR SITE INSPECTOR
 INFORMATION WHO IS STILL WITH THE COMPANY, MIKE ADAIR
 IS NOW A CITY INSPECTOR.
  
  
 THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. PLEASE
 UPDATE FILES SINCE THEIR MAYBE ADDITIONAL PERSONNEL TO
 ACT AS THE JOBSITE INSPECTOR.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A)2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
  
 1C)COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
  
  
  
 2) SHEET 042-LS-111 & 045-A-111:
  
 2A-2E) COMPLIED.
  
 2F) PROVISO: PLEASE NOTE WITH BOTH EXIT PASSAGE WAYS
 119 & 120 THE ONLY ALLOWABLE PENETRATIONS ARE THOUGH
 ALLOWED UNDER SECTION FBC-B 1024.6 PENETRATIONS INTO OR
 THROUGH AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR
 EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT PASSAGEWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL NOT BE
 PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2G-2K) COMPLIED.
  
  
 2L) 2ND REQUEST. SEMI-COMPLIED. THE RESPONSE INDICATES
 NEW UPDATES FOR WALL TYPE L & L1 ON SHEET A5.02. PLEASE
 NOTE THIS SHEET IS NOT IN ORDER, FOUND IT LATER IN THE
 REVIEW.
  
 2M) COMPLIED.
  
 2N) SHEET A-407 NOTICE ONLY!!! SHEET A4.07 MENS STALL
 STILL 7 FEET. SHEET A-4.08 WOMENS STALL CORRECTED 7
 FOOT 1 INCH.
 1ST REVIEW COMMENT. THE ENLARGED MENS & WOMENS RESTROOM
 ON SHEET A407 & A-408 MEASURE 7-0 OVERALL. THE LAYOUT
 JUST BARELY MEETS THE REQUIREMENT FOR THE CLEAR FLOOR
 SPACE UNDER THE ACCESSIBILITY CODE SECTION 604.3.1.
 DEPENDING ON THE SIZE LAV TO BE INSTALLED THE CLEAR
 FLOOR SPACE MAY NOT BE ACHIEVED!!!
  
 2O-Q) COMPLIED.
  
 2R) 2ND REQUEST. SHEET 042-LS-111 THE FLOOR PLAN SHOWS
 A DINING AND BAR AREA, PLEASE PROVIDE COMPLIANCE WITH
 THE 2017 ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES
 ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT
 LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING
 SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2S) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 2T) 2ND REQUEST. 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS.
 2T)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2T)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2U) PROVISO, NOTICE ONLY! POOL, GENERATOR, KITCHEN
 HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE
 SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION
 PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT
 AND ALL REQUIRE A SEPARATE REVIEW AND FEE.
  
 2V)COMPLIED.
  
 2W) 2ND REQUEST. SHEET 005-GN-1 BUILDING CODE SUMMARY
 INDICATES THE PLANS WERE DEVELOPED A CONSTRUCTION TYPE
 II-A, THIS ONLY ALLOWS UNDER THE 2014 CODE TABLE 503 A
 4 STORY BUILDING WITH ONE STORY INCREASE, IT WOULD BE
 REQUIRED TO BE A CONSTRUCTION TYPE I-B . UNDER THE 2017
 FBC-B TABLE 504.4 THE BUILDING TYPE WOULD ALSO BE
 REQUIRED TO BE I-B ALLOWABLE 12 STORIES WITH A FULL
 NFPA 13 SYSTEM, UNDER THE 2017 WITH FIRE SPRINKLERS A
 LL-A BUILDING IS ONLY ALLOWED TO BE 5 STORIES. .
  
 2X) COMPLIED. R-1 TRANSIENT A STAY30 DAYS OR LESS, SEE
 FBC-B 310.3 & 310.4.
  
 2Y)2ND REQUEST. SHEETS 042-ALS-111 NOR SHEET
 045-A-111-A SHOW THE LOCATION OF THE FIRE PUMP
 LOCATION. SHEET E-101 SHOWS THE FIRE PUMP IN THE
 MECHANICAL/ ELECTRICAL ROOM 127. PLEASE SHOW COMPLIANCE
 WITH:
 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL
 BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH
 SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS.
 FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 711, OR BOTH.
 EXCEPTIONS:
 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY
 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE
 PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2.
  
 3) SHEET 046-A-111-B:
  
 3A) 2ND REQUEST. THE COVERED ENTRY PORT COCHERE SHOWS
 THE USE OF A LULA LIFT, PLEASE PROVIDE CONFIRMATION THE
 LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION
 ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1
 REFERENCED STANDARDS.
  
 3B) 2ND REQUEST. SHEET 046-A-111-B SHOWS A NEW FIRE
 COMMAND ROOM.
 [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND
 EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY
 WITH SECTIONS 403.4.1 THROUGH 403.4.8.
  
 3C)) 2ND REQUEST. [F]403.4.1 SMOKE DETECTION. SMOKE
 DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 907.2.13.1.
  
 3D) 2ND REQUEST. [F]403.4.2 FIRE ALARM SYSTEM. A FIRE
 ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 907.2.13.
  
 3E) 2ND REQUEST. [F]403.4.3 STANDPIPE SYSTEM. A
 HIGH-RISE BUILDING SHALL BE EQUIPPED WITH A STANDPIPE
 SYSTEM AS REQUIRED BY SECTION 905.3.
  
 3F)) 2ND REQUEST. [F]403.4.4 EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM. AN EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 907.5.2.2.
  
 3G) 2ND REQUEST. [F]403.4.5 EMERGENCY RESPONDER RADIO
 COVERAGE. EMERGENCY RESPONDER RADIO COVERAGE SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 3H)SEMI-COMPLIED. [F]403.4.6 FIRE COMMAND. A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 3I) 2ND REQUEST. 403.4.7 SMOKE REMOVAL. TO FACILITATE
 SMOKE REMOVAL IN POST-FIRE SALVAGE AND OVERHAUL
 OPERATIONS, BUILDINGS AND STRUCTURES SHALL BE EQUIPPED
 WITH NATURAL OR MECHANICAL VENTILATION FOR REMOVAL OF
 PRODUCTS OF COMBUSTION IN ACCORDANCE WITH ONE OF THE
 FOLLOWING:
 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR
 PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF
 EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM)
 INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL
 BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR
 FEET (15 240 MM) OF PERIMETER.
  
 EXCEPTIONS:
 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE
 HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE
 PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA
 IN LIEU OF THE AREA SPECIFIED IN ITEM 1.
 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT
 GLAZING CAN BE CLEARED BY FIRE FIGHTERS.
 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE
 EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA
 INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED
 DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER
 PORTIONS OF THE BUILDING.
 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE
 EQUIVALENT RESULTS.
  
 3J) 2ND REQUEST. [F]403.4.8 STANDBY AND EMERGENCY
 POWER. A STANDBY POWER SYSTEM COMPLYING WITH SECTION
 2702 AND SECTION 3003 SHALL BE PROVIDED FOR THE STANDBY
 POWER LOADS SPECIFIED IN SECTION 403.4.8.3. AN
 EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR THE EMERGENCY POWER LOADS
 SPECIFIED IN SECTION 403.4.8.4.
  
 3K) 2ND REQUEST. [F]403.4.8.1 EQUIPMENT ROOM. IF THE
 STANDBY OR EMERGENCY POWER SYSTEM INCLUDES A GENERATOR
 SET INSIDE A BUILDING, THE SYSTEM SHALL BE LOCATED IN A
 SEPARATE ROOM ENCLOSED WITH 2-HOUR FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. SYSTEM SUPERVISION WITH MANUAL
 START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE
 FIRE COMMAND CENTER.
  
 4A-D) COMPLIED. MATRIX PROVIDING THE TOTAL AMOUNT OF
 SLEEPING ROOMS ACCESSIBILITY.
  
 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 &
 051-A-122:
 5A-F) COMPLIED.
  
 6-7) COMPLIED.
  
 8) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR
 STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM,
 HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE
 DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS
 THE HARDWARE MEET COMPLIANCE WITH :
 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN
 POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND
 USABLE FROM BOTH SIDES.
  
 9) COMPLIED.
  
 10) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A
 SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND
 CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 11) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 12) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By jwitmer Date 2018-02-15 Time 16:22 Rev Time 0.00
Received By jwitmer Date 2018-02-13 Time 16:07 Sent To  
Notes
2018-02-15 16:22:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020254
 ADD: 1675 PALM BEACH LAKES BLVD.
 CONT: STRATICON LLC
 TEL: 772-210-0200 STRATICON
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. FEB. 14/ 2018
 ACTION: DENIED
  
 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 PLEASE UPDATE FILES SINCE THEIR MAYBE ADDITIONAL
 PERSONNEL TO ACT AS THE JOBSITE INSPECTOR.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE
 E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED,
 THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED
 AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS,
 TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1)
 FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK
 & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
  
  
  
 2) SHEET 042-LS-111 & 045-A-111:
  
 2A) THE LIFE SAFETY PLAN SHOWS THE EGRESS DOOR
 CAPACITIES AT 36 INCHES/ .2 = 180 OCCUPANT LOAD. PLEASE
 REDUCE ALL OPENINGS BY 2 INCHES FOR THE CLEAR WIDTH OF
 THE DOOR WHEN OPEN 90 DEGREES TO THE DOOR JAMB.
 2017 FBC-B 1010.1.1 SIZE OF DOORS. THE REQUIRED
 CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR
 THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM
 CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES. PLEASE CORRECT ALL DOORWAYS ON ALL FLOORS.
  
 2B) IN THE LIFE SAFETY PLAN ONLY DISTANCES ARE GIVEN
 FOR THE MEANS OF EGRESS. SOME OF THE AREAS SHOW THE
 OCCUPANT LOAD #1 ASSEMBLY DINING 116 TOTAL OCC. LOAD.
 IS THE KITCHEN LOAD FIGURED IN THIS CALCULATION?
 THE SAME WITH THE EMPLOYEES BREAK ROOM, LAUNDRY AND OR
 EMPLOYEES WORK AREA. WHERE THE PLAN SETS A POINT AS THE
 START OF A MEANS OF EGRESS THE PLANS SHOULD SHOW AN
 OCCUPANT LOAD AND ALONG THE PATH OF TRAVEL THE AMOUNT
 OF OCCUPANTS BEING ADDED AND THE NEW SUBTOTAL. IN THIS
 WAY THE OCCUPANT LOAD IS KNOWN FOR EACH DOOR, RAMP OR
 STAIR.
 2017 FBC-B 1003.6 MEANS OF EGRESS CONTINUITY.
  
 THE PATH OF EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL
 NOT BE INTERRUPTED BY A BUILDING ELEMENT OTHER THAN A
 MEANS OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF A MEANS OF
 EGRESS SYSTEM SHALL NOT BE DIMINISHED ALONG THE PATH OF
 EGRESS TRAVEL.
  
 2C) THE LIFE SAFETY PLAN SHOWS THE 2 VERTICAL EXITS AS
 2 HOUR RATED BUT THE EXIT CORRIDOR 119 & 120 ARE SHOWN
 AS A 1 HOUR FIRE RATED CORRIDOR. PLEASE NOTE THESE
 CORRIDORS ARE IDENTIFIED WRONG, THEY ARE EXIT
 PASSAGEWAYS.
 2017 FBC-B PLEASE REFER TO 1024 .3. 1024.3
 CONSTRUCTION. EXIT PASSAGEWAY ENCLOSURES SHALL HAVE
 WALLS, FLOORS AND CEILINGS OF NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING, AND NOT LESS THAN THAT REQUIRED
 FOR ANY CONNECTING INTERIOR EXIT STAIRWAY OR RAMP ( 2
 HOUR STAIR ENCLOSURE/ 2 HOUR EXIT PASSAGEWAY). EXIT
 PASSAGEWAYS SHALL BE CONSTRUCTED AS FIRE BARRIERS IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
 PLEASE UPDATE ALL WALL IDENTIFICATION TAGS, F1 RATED
 WALLS TO F2, D RATED WALLS SHOWING NO RATING, INCLUDING
 THE 2 HOUR RATED STAIR ENCLOSURES AND IN THE DRY
 STORAGE ROOM 114 A NON-RATED WALL C WHICH GOES THROUGH
 A RATED WALL.
  
 2D) SHEET A-111 IN THE EXIT PASSAGEWAY 119 & 120.
 PLEASE NOTE UNDER THE 2017 FLORIDA BUILDING CODE
 EXISTING BUILDING CODE TABLE 1012.4 MEANS OF EGRESS
 HAZARD CATEGORIES THIS BUILDING WAS A BUSINESS
 OCCUPANCY. UNDER THE CHANGE OF OCCUPANCY TO A R1 THIS
 IS A HIGH RELATIVE HAZARD UNDER TABLE 1012.4.
 EXIST. BUILD. CODE 1012.4.1 MEANS OF EGRESS FOR CHANGE
 TO HIGHER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 CLASSIFICATION IS MADE TO A HIGHER HAZARD CATEGORY
 (LOWER NUMBER) AS SHOWN IN TABLE 1012.4, THE MEANS OF
 EGRESS SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10
 OF THE FLORIDA BUILDING CODE, BUILDING. THE 2017 FBC-B
 STATES IN 1024.1 EXIT PASSAGEWAYS. AN EXIT PASSAGEWAY
 SHALL NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS
 OF EGRESS AND A CIRCULATION PATH. THE 2012 IBC CODE
 COMMENTARY STATES THE ONLY OPENINGS THAT ARE PERMITTED
 IN THE FIRE RESISTANCE RATED EXIT PASSAGEWAY ARE DOORS
 THAT LEAD EITHER FROM NORMALLY OCCUPIED SPACES, FROM
 THE ENCLOSURE FOR THE EXIT STAIRWAY AND DOORS LEADING
 TO THE OUTSIDE.
  
 PLEASE ALSO REVIEW SECTION 1023 2017 FBC-B INTERIOR
 EXIT & STAIRWAYS& RAMPS, 1023.11 TERMINATION AND
 EXTENSIONS. EXCEPTION 1 ALLOWS FOR OPENINGS IN THE EXIT
 PASSAGEWAY SERVING A SMOKEPROOF ENCLOSURE ARE PERMITTED
 WHERE THE EXIT PASSAGEWAY IS PROTECTED AND PRESSURIZED
 IN THE SAME MANNER AS THE SMOKEPROOF ENCLOSURE, AND
 OPENINGS ARE PROTECTED AS REQUIRED FOR ACCESS FROM
 OTHER FLOORS.
  
 PLEASE ALSO REVIEW SECTION 1024.7 VENTILATION FOR EXIT
 PASSAGEWAYS PROVIDE WHICH OF THE 3 METHODS WILL
 INSTALLED.
  
 2E) PLEASE ALSO REVIEW IN THE 2 HOUR FIRE RATED EXIT
 PASSAGEWAY 119 DOOR 116 AND SIDELIGHT, IN THE 2017
 FBC-B TABLE 716.5 FOR A 2 HOUR WALL ONLY ALLOWS A 100
 SQ. IN. VISION PANEL IN THE DOOR AND SIDELIGHT OR
 TRANSOM NOT PERMITTED.
  
 2F) PLEASE NOTE WITH BOTH EXIT PASSAGE WAYS 119 & 120
 THE ONLY ALLOWABLE PENETRATIONS ARE THOUGH ALLOWED
 UNDER SECTION FBC-B 1024.6 PENETRATIONS INTO OR THROUGH
 AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY
 SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL
 BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL NOT BE PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2G) PLEASE REVIEW SHEET M-101 AND THE DUCTWORK THAT IS
 RUNNING THROUGH THE EXIT PASSAGEWAY. SHOW HOW
 COMPLIANCE WITH SECTION FBC-B 1024.7 IS TO BE ACHIEVED.
 1024.7 VENTILATION.
 EQUIPMENT AND DUCTWORK FOR EXIT PASSAGEWAY VENTILATION
 AS PERMITTED BY SECTION 1024.6 SHALL COMPLY WITH ONE OF
 THE FOLLOWING:
 1. THE EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR
 TO THE BUILDING AND SHALL BE DIRECTLY CONNECTED TO THE
 EXIT PASSAGEWAY BY DUCTWORK ENCLOSED IN CONSTRUCTION AS
 REQUIRED FOR SHAFTS.
 2. WHERE THE EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE EXIT PASSAGEWAY, THE INTAKE AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE
 DISCHARGED DIRECTLY TO THE OUTDOORS, OR THE AIR SHALL
 BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS
 REQUIRED FOR SHAFTS. 2017 FLORIDA BUILDING CODE W 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 105.1.1. PERMIT
 REQUIRED.
 3. WHERE LOCATED WITHIN THE BUILDING, THE EQUIPMENT AND
 DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH
 CONSTRUCTION AS REQUIRED FOR SHAFTS.
 IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED
 CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR
 MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY
 OPENING PROTECTIVES IN ACCORDANCE WITH SECTION 716 FOR
 SHAFT ENCLOSURES.
 EXIT PASSAGEWAY VENTILATION SYSTEMS SHALL BE
 INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS.
  
 2H) PLEASE NOTE AS MEASURED FOR THE EXITS AND
 REMOTENESS, SPRINKLERED BUILDING 1/3 RD. THE OVERALL
 DISTANCE CENTER OF DOOR LINE TO CENTER OF DOOR LINE.
 2017 FBC-B 1007.1.1 EXCEPTION 1 & 2.
  
 1ST FLOOR SHEET 047-A-112 THE OVERALL DIAGONAL DISTANCE
 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT DOOR 133
 THROUGH CENTERLINE OF RATED CORRIDOR TO CENTERLINE EXIT
 DOOR 135 IS 42 FT. DOES NOT MEET REMOTENESS.
  
 2ND FLOOR SHEET 051-A-122 THE OVERALL DIAGONAL DISTANCE
 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT DOOR 233
 THROUGH CENTERLINE OF RATED CORRIDOR TO CENTERLINE EXIT
 DOOR 235 IS 42 FT. DOES NOT MEET
 REMOTENESS.
  
 3RD-9TH FLOORS SHEET 054-A-1.32 THE OVERALL DIAGONAL
 DISTANCE 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT
 DOOR 333 THROUGH CENTERLINE OF RATED CORRIDOR TO
 CENTERLINE EXIT DOOR 335 IS 48.16 FT. DOES MEET
 REMOTENESS TEST.
  
 2I) SHEET P-106 THE EXIT PASSAGE WAY LISTED ON THE
 ARCHITECTURAL AND MECHANICAL SHEETS AS 119 AND 120 IS
 LISTED HERE AS EXIT CORRIDOR 121. PLEASE REMOVE ALL ?
 INCH, 3 INCH AND 4 INCH COLD WATER AS WELL AS 1 ? INCH
 HOT WATER PIPING FROM THE 2 HOUR FIRE RATED EXIT
 PASSAGEWAY. SEE FBC-B SECTION 1024.6 PENETRATIONS.
  
 PENETRATIONS INTO OR THROUGH AN EXIT PASSAGEWAY ARE
 PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT
 PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL
 NOT BE PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2J) SHEET E-106 THE EXIT PASSAGE WAY LISTED ON THE
 ARCHITECTURAL AND MECHANICAL SHEETS AS 119 AND 120 IS
 LISTED HERE AS EXIT CORRIDOR 121. THE SHEET INDEX LIST
 SHEET E-105 AS THE 1ST FLOOR OVERALL LIGHTING PLAN,
 THERE SEEMS TO BE A DISCREPANCY IN PLANS. IN EITHER
 CASE SHOW COMPLIANCE WITH FBC-B SECTION 1024.6
 PENETRATIONS. PENETRATIONS INTO OR THROUGH AN EXIT
 PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY
 SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL
 BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL NOT BE PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2K) LS-111 AND A-111A BOTH SHOW WITHIN THE 2 HOUR EXIT
 PASSAGE WAY 120 TAKING PART OF THE OCCUPANTS FROM THE 2
 HOUR ENCLOSURE OUT THROUGH DOOR 124 IN FRONT OF THE
 ELEVATOR LOBBY ON THE 1ST FLOOR, OUT THROUGH THE
 GENERAL LOBBY AND OUT THE FRONT DOORS. THE DOOR 124 IS
 A OUTSWING DOOR AND DIRECTLY IN FRONT
 IS DOOR 125 ALSO A OUTSWING DOOR THAT WOULD IMPEDE THE
 EXITING FROM THE VERTICAL EXIT STAIRWAY. NOTE THE DOOR
 SWING DOES NOT CUT THE REQUIRED EGRESS WIDTH IN HALF.
  
 2L) LS-111 AND A-111A PLEASE REVIEW LAUNDRY CHUTE
 SHAFT. THE LIFE SAFETY PLAN DOES NOT INDICATE THE
 LAUNDRY SHAFT AS RATED. THE A-111A SHEET SHOWS THE
 RATING ON THE LAUNDRY SHAFT WALLS AS F1 ONE HOUR FIRE
 RATED WALL UL 448, NOT EVEN SHAFT WALL CONSTRUCTION.
 SHAFT WALL CONSTRUCTION SHALL BE 2 HOURS WHEN
 CONNECTING 4 STORIES OR MORE. FBC-B 713.4. FIRE
 RESISTANCE RATING. THE PLANS WILL NEED TO BE UPDATES
 SHOWING A 2 HOUR SHAFT AND MEETING ALL OF THE
 REQUIREMENTS OF FBC-B 713.13.1-4 AND 713.13.6.
  
 2M) THE PLANS SHOW A SPACE THAT IS VOID, ENCLOSED ON
 THE KITCHEN, LAUNDRY SHAFT AND EXIT PASSAGE WAY 120,
 WHAT IS SPACE TO BE USED FOR? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2N) SHEET A-407 NOTICE ONLY!!! THE ENLARGED MENS &
 WOMENS RESTROOM ON SHEET A407 & A-408 MEASURE 7-0
 OVERALL. THE LAYOUT JUST BARELY MEETS THE REQUIREMENT
 FOR THE CLEAR FLOOR SPACE UNDER THE ACCESSIBILITY CODE
 SECTION 604.3.1. DEPENDING ON THE SIZE LAV TO BE
 INSTALLED THE CLEAR FLOOR SPACE MAY NOT BE ACHIEVED!!!
  
 2O) SHEET A-407 & A-408 THE MIRRORS IN THE VANITY
 ELEVATION ARE DIMENSIONED WITH THE DIMENSION OF 3 FOOT
 4 ? INCHES TO THE BOTTOM OF THE MIRROR FRAME. THE 2017
 FBC-ACCESSIBILITY CODE REQUIRES A MAXIMUM OF 40 INCHES
 TO THE REFLECTIVE SURFACE TO FINISH FLOOR AS A MAXIMUM
 HEIGHT. SEE 603.3.
  
 2P) SHEET A-111 EMPLOYEE RESTROOM SHOWS A ACCESSIBLE
 SHOWER. THIS PLAN DOES NOT REFERENCE ANY DETAILS FOR
 THE ACCESSIBLE SHOWER, WHEN MEASURED THE SHOWER IS 3X3
 FEET. THERE IS A SEAT WITHIN THE SHOWER BUT THE SEAT
 FALL SHORT OF COMPLYING WITH 2017 ACC. CODE 610.3.
 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES
 MAXIMUM AND THE FRONT EDGE 15 INCHES MINIMUM AND 16
 INCHES MAXIMUM FROM THE SEAT WALL. PLEASE PROVIDE GRAB
 BARS FOR A TRANSFER SHOWER IN COMPLIANCE WITH 608.3.1.
  
 2Q) SHEET A-112 THE EMPLOYEE RESTROOM SHOWS A OVERALL
 DIMENSION OF THE RESTROOM BUT NOT THE CLEAR FLOOR SPACE
 REQUIRED FOR THE WATER CLOSET. SEE ACC. CODE 604.3.1.
 SIZE.
  
 2R) SHEET 042-LS-111 THE FLOOR PLAN SHOWS A DINING AND
 BAR AREA, PLEASE PROVIDE COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2S) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2T) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS.
 2T)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2T)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2U) POOL, GENERATOR, KITCHEN HOODS, SUPPRESSION, GAS,
 FENCES, SIGNS, FIRE SPRINKLERS, FIRE ALARMS,
 LANDSCAPING, IRRIGATION PERMITS ARE NOT REVIEWED UNDER
 THE MAIN BUILDING PERMIT AND ALL REQUIRE A SEPARATE
 REVIEW AND FEE.
  
 2V) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE
 PLANS WERE DEVELOPED UNDER THE 2014 FBC-B BROUGHT IN
 AFTER DEC. 31/ 2017 WHICH WAS THE ADOPTION DATE OF THE
 2017 FBC-B.
  
 2W) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE
 PLANS WERE DEVELOPED A CONSTRUCTION TYPE II-A, THIS
 ONLY ALLOWS UNDER THE 2014 CODE TABLE 503 A 4 STORY
 BUILDING WITH ONE STORY INCREASE, IT WOULD BE REQUIED
 TO BE A CONSTRUCTION TYPE I-B . UNDER THE 2017 FBC-B
 TABLE 504.4 THE BUILDING TYPE WOULD ALSO BE REQUIRED TO
 BE I-B.
  
 2X) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE
 HOTEL AS A R-2 HOTEL TRANSIENT, PLEASE NOTE R-1 IS
 CONSIDERED TRANSIENT A STAY30 DAYS OR LESS, R-2 IS
 CONSIDERED NON-TRANSIENT OR STAYS OVER 30 DAYS. SEE
 FBC-B 310.3 & 310.4.
  
 2Y) SHEETS 042-ALS-111 NOR SHEET 045-A-111-A SHOW THE
 LOCATION OF THE FIRE PUMP LOCATION. SHEET E-101 SHOWS
 THE FIRE PUMP IN THE MECHANICAL/ ELECTRICAL ROOM 127.
 PLEASE SHOW COMPLIANCE WITH:
 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL
 BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH
 SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS.
 FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 711, OR BOTH.
 EXCEPTIONS:
 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY
 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE
 PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2.
  
 3) SHEET 046-A-111-B:
 3A) THE COVERED ENTRY PORT COCHERE SHOWS THE USE OF A
 LULA LIFT, PLEASE PROVIDE CONFIRMATION THE
 LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION
 ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1
 ?REFERENCED STANDARDS?.
  
 3B) SHEET 046-A-111-B SHOWS A NEW FIRE COMMAND ROOM.
 [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND
 EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY
 WITH SECTIONS 403.4.1 THROUGH 403.4.8.
  
 3C) [F]403.4.1 SMOKE DETECTION. SMOKE DETECTION SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.1.
  
 3D) [F]403.4.2 FIRE ALARM SYSTEM. A FIRE ALARM SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.
  
 3E) [F]403.4.3 STANDPIPE SYSTEM. A HIGH-RISE BUILDING
 SHALL BE EQUIPPED WITH A STANDPIPE SYSTEM AS REQUIRED
 BY SECTION 905.3.
  
 3F) [F]403.4.4 EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 3G) [F]403.4.5 EMERGENCY RESPONDER RADIO COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 3H)SEMI-COMPLIED. [F]403.4.6 FIRE COMMAND. A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 3I) 403.4.7 SMOKE REMOVAL. TO FACILITATE SMOKE REMOVAL
 IN POST-FIRE SALVAGE AND OVERHAUL OPERATIONS, BUILDINGS
 AND STRUCTURES SHALL BE EQUIPPED WITH NATURAL OR
 MECHANICAL VENTILATION FOR REMOVAL OF PRODUCTS OF
 COMBUSTION IN ACCORDANCE WITH ONE OF THE FOLLOWING:
 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR
 PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF
 EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM)
 INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL
 BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR
 FEET (15 240 MM) OF PERIMETER.
  
 EXCEPTIONS:
 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE
 HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE
 PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA
 IN LIEU OF THE AREA SPECIFIED IN ITEM 1.
 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT
 GLAZING CAN BE CLEARED BY FIRE FIGHTERS.
 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE
 EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA
 INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED
 DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER
 PORTIONS OF THE BUILDING.
 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE
 EQUIVALENT RESULTS.
  
 3J) [F]403.4.8 STANDBY AND EMERGENCY POWER. A STANDBY
 POWER SYSTEM COMPLYING WITH SECTION 2702 AND SECTION
 3003 SHALL BE PROVIDED FOR THE STANDBY POWER LOADS
 SPECIFIED IN SECTION 403.4.8.3. AN EMERGENCY POWER
 SYSTEM COMPLYING WITH SECTION 2702 SHALL BE PROVIDED
 FOR THE EMERGENCY POWER LOADS SPECIFIED IN SECTION
 403.4.8.4.
  
 3K) [F]403.4.8.1 EQUIPMENT ROOM. IF THE STANDBY OR
 EMERGENCY POWER SYSTEM INCLUDES A GENERATOR SET INSIDE
 A BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE
 ROOM ENCLOSED WITH 2-HOUR FIRE BARRIERS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
 SYSTEM SUPERVISION WITH MANUAL START AND TRANSFER
 FEATURES SHALL BE PROVIDED AT THE FIRE COMMAND CENTER.
  
 4) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 &
 051-A-122:
 4A) THIS STATEMENT IS GOING TO BE A COMMON STATEMENT
 FOR ALL FLOORS CONTAINING SLEEPING ROOMS. THE PLANS
 WILL NEED TO PROVIDE A MATRIX PROVIDING THE TOTAL
 AMOUNT OF SLEEPING ROOMS. IT APPEARS THERE ARE 168
 SLEEPING ROOMS. A-4.05A INDICATES THE STYLE OF ROOM FOR
 A ADA DOUBLE QUEEN AND SHEET A-406-A SHOWS THE ADA KING
 PLEASE PROVIDE A MATRIX WHICH UNITS ARE ACCESSIBLE.
 PLEASE USE TABLE 224.2 OF THE 2017 ACCESS. CODE TO
 PROVIDE THE NUMBER OF UNITS WITH ROLL-IN SHOWER, NUMBER
 OF ROOMS WITHOUT THE ROLL IN SHOWER AND TOTAL NUMBER OF
 REQUIRED ROOMS.
  
 4B) ACCESS. CODE SHOW 224.5 DISPERSION. GUEST ROOMS
 REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH
 806.2 AND GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION
 FEATURES COMPLYING WITH 806.3 SHALL BE DISPERSED AMONG
 THE VARIOUS CLASSES OF GUEST ROOMS, AND SHALL PROVIDE
 CHOICES OF TYPES OF GUEST ROOMS, NUMBER OF BEDS, AND
 OTHER AMENITIES COMPARABLE TO THE CHOICES PROVIDED TO
 OTHER GUESTS. WHERE THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW
 FOR COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED
 IN THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF
 BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3.
  
 4C) ACCESS. CODE SHOW COMPLIANCE WITH: 224.1.2 GUEST
 ROOM DOORS AND DOORWAYS. ENTRANCES, DOORS, AND DOORWAYS
 PROVIDING USER PASSAGE INTO AND WITHIN GUEST ROOMS THAT
 ARE NOT REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING
 WITH 806.2 SHALL COMPLY WITH 404.2.3.
  
 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL PROVIDE A
 CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM. CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
  
 806.2.3 SLEEPING AREAS. AT LEAST ONE SLEEPING AREA
 SHALL PROVIDE A CLEAR FLOOR SPACE COMPLYING WITH 305 ON
 BOTH SIDES OF A BED. THE CLEAR FLOOR SPACE SHALL BE
 POSITIONED FOR PARALLEL APPROACH TO THE SIDE OF THE
 BED. EXCEPTION: WHERE A SINGLE CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR PARALLEL APPROACH IS
 PROVIDED BETWEEN TWO BEDS, A CLEAR FLOOR OR GROUND
 SPACE SHALL NOT BE REQUIRED ON BOTH SIDES OF A BED.
  
  
 806.2.4 TOILET AND BATHING FACILITIES. AT LEAST ONE
 BATHROOM THAT IS PROVIDED AS PART OF A GUEST ROOM SHALL
 COMPLY WITH 603. NO LESS THAN ONE WATER CLOSET, ONE
 LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610. IN
 ADDITION, REQUIRED ROLL-IN SHOWER COMPARTMENTS SHALL
 COMPLY WITH 608.2.2 OR 608.2.3. TOILET AND BATHING
 FIXTURES REQUIRED TO COMPLY WITH 603 THROUGH 610 SHALL
 BE PERMITTED TO BE LOCATED IN MORE THAN ONE TOILET OR
 BATHING AREA, PROVIDED THAT TRAVEL BETWEEN FIXTURES
 DOES NOT REQUIRE TRAVEL BETWEEN OTHER PARTS OF THE
 GUEST ROOM.
  
  
 806.2.4.1 VANITY COUNTER TOP SPACE. IF VANITY COUNTER
 TOP SPACE IS PROVIDED IN NON-ACCESSIBLE GUEST TOILET OR
 BATHING ROOMS, COMPARABLE VANITY COUNTER TOP SPACE, IN
 TERMS OF SIZE AND PROXIMITY TO THE LAVATORY, SHALL ALSO
 BE PROVIDED IN ACCESSIBLE GUEST TOILET OR BATHING
 ROOMS.
 ADVISORY 806.2.4.1 VANITY COUNTER TOP SPACE. THIS
 PROVISION IS INTENDED TO ENSURE THAT ACCESSIBLE GUEST
 ROOMS ARE PROVIDED WITH COMPARABLE VANITY COUNTER TOP
 SPACE.
  
 4D) PLEASE PROVIDE COMPLIANCE WITH ACCESS. CODE TABLE
 224.4 GUEST ROOMS WITH COMMUNICATION FEATURES, PROVIDE
 ALSO IN MATRIX SHOWING WHAT ROOMS ARE TO COMPLY.
  
 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 &
 051-A-122:
 5A) SHEET 043-LS-121 IS MISSING THE ROOM LABEL 224 AND
 IDENTIFIED AS A WARMING KITCHEN. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. NOTE, CANNOT EXIT THROUGH A
 KITCHEN OR STORAGE ROOM. ALSO SEE 2017 FBC-B 1016.2(2)
 (5) EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS, OR SPACES USED FOR SIMILAR PURPOSES.
  
 5B) MEETING ROOM 226, YOUR OVERALL DIAGONAL FOR THIS
 ROOM IS 50.50 FT. 1/3RD THE OVERALL DISTANCE IS 16 FOOT
 10 INCHES. THE 2 EXIT DOORS MEET THIS REQUIREMENT BUT
 THE 2 MEANS OF ACCESS CONVERGE BETWEEN THE DOOR LEADING
 TO STAIR 233 AND DOOR 205. BETWEEN THE WALL OF THE
 STAIR AND DOOR 205 THERE IS ONLY 12 FEET OR THE 2 EXITS
 CONVERGE, DOES NOT MEET THE REQUIREMENT OF REMOTENESS
 UNDER 2017 FBC-B 1007.1.1EXCEP. 2. 1/3 DISTANCE APART.
  
 5C) SHEET 050-A-121 THE COMMON WALL BETWEEN THE MEETING
 ROOM STORAGE CLOSET AND GUEST ROOM 222 IS IDENTIFIED
 WITH WALL TAG F3. PLEASE NOTE THE WALL SCH. ON A-501
 DOES NOT ASSIGN A STC RATING TO THIS WALL.
 FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5D) PAGE 051-A-122 & LS-1.21. GUEST ROOM 220 THIS
 COMMENT IS TO STAND FOR ALL FLOORS 2-10. THE COMMON
 PATH OF TRAVEL IS TAKEN FROM THE DOORWAY OR THE
 BEGINNING OF THE EXIT ACCESS CORRIDOR. PLEASE NOTE
 COMMON PATH OF EGRESS TRAVEL,
 DEFINITION: THAT PORTION OF THE EXIT ACCESS TRAVEL
 DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A
 STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE
 AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS
 DOORWAYS.
 PLEASE PROVIDE THE COMMON PATH OF EGRESS TRAVEL SHOW
 THE COMMON PATH OF EGRESS TRAVEL FROM THE MOST REMOTE
 POINT IN THE ROOM AND AROUND FURNITURE AND ONE FOOT
 FROM WALL LINES TO THE CLOSET VERTICAL EXIT. IT APPEARS
 THE TRAVEL DISTANCE EXCEEDS 75 FEET.
  
 5E) SHEET 050-A-121. COMMON COMMENT FOR ALL FLOORS
 2-10. THE LINEN CHUTE SHOWS THE SHAFT WALLS AROUND
 IDENTIFIED WITH A WALL TAG F2. THIS WALL IS A 1 HOUR
 RATING REQUIRES A 2 HOUR FIRE RATING PER 713.4
 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE
 CONNECTING FOUR STORIES OR MORE.
  
 5F) SHEET 050-A-121 COMMON COMMENT FOR ALL FLOORS 2-10.
 THE LINEN CHUTE SHOWS THE SHAFT WALLS AROUND IDENTIFIED
 WITH A WALL TAG F2. PLEASE ALSO PROVIDE THE CORRECT UL
 LISTING FOR SHAFT WALL CONSTRUCTION. 713.4
 FIRE-RESISTANCE RATING.
  
 6) SHEET 054-A-132 GUEST ROOMS 302, THIS COMMENT WILL
 STAND FOR THIS ROOM ALL FLOORS 3-9. THE COMMON PATH OF
 TRAVEL IS TAKEN FROM THE DOORWAY OR THE BEGINNING OF
 THE EXIT ACCESS CORRIDOR. PLEASE NOTE COMMON PATH OF
 EGRESS TRAVEL,
 DEFINITION: THAT PORTION OF THE EXIT ACCESS TRAVEL
 DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A
 STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE
 AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS
 DOORWAYS.
 PLEASE PROVIDE THE COMMON PATH OF EGRESS TRAVEL SHOW
 THE COMMON PATH OF EGRESS TRAVEL FROM THE MOST REMOTE
 POINT IN THE ROOM AND AROUND FURNITURE AND ONE FOOT
 FROM WALL LINES TO THE CLOSET VERTICAL EXIT. IT APPEARS
 THE TRAVEL DISTANCE EXCEEDS 75 FEET.
  
 7) SHEET 067-A-305:
 7A) DETAIL 2 EXTERIOR STAIR. THE PLAN INDICATES THE
 RISE OF 7 INCHES AND RUN OF 11 INCHES BUT DOES NOT
 PROVIDE THE CIRCULAR AREA MADE OF THE RISE, RUN AND
 SLOPE OF THE BOTTOM GUARDRAIL. SHOW COMPLIANCE WITH
 2017 FBC-B 1015.4 EXCEPTION 2. 2. THE TRIANGULAR
 OPENINGS AT THE OPEN SIDES OF A STAIR, FORMED BY THE
 RISER, TREAD AND BOTTOM RAIL SHALL NOT ALLOW PASSAGE OF
 A SPHERE 6 INCHES (152 MM) IN DIAMETER.
  
 7B) DETAIL 2 EXTERIOR STAIR. THE UPPER LANDING SHOWS
 THE GUARDRAIL AT 3 FOOT 6 INCHES OF 43 INCHES.
 THE GUARDRAIL DROPS VERTICALLY 4 INCHES AT THE FIRST
 RISER. THE HEIGHT MEASUREMENT FOR THE GUARDRAIL IS TO
 BE TAKEN AT THE NOSING OF THE RISER, VERTICALLY. SEE
 2017 FBC-B 1015.3 HEIGHT. REQUIRED GUARDS SHALL BE NOT
 LESS THAN 42 INCHES (1067 MM) HIGH, MEASURED
 VERTICALLY.
  
 7C) THE BOTTOM OF THE GUARDRAIL DOES NOT CONTINUE DOWN
 THE SLOPE 11 INCHES PAST THE LAST RISER, THIS IS WHERE
 THE HORIZONTAL EXTENSION WOULD BEGIN, THAT IS ALSO THE
 REASON ON THE STAIRS THE HANDRAIL IS 34 INCHES IN
 HEIGHT, THE HANDRAIL ALSO DOES NOT CONTINUE 11 INCHES
 PAST THE LAST RISER BEFORE CONTINUING THE HORIZONTAL
 EXTENSION. 2017 FBC-B 1014.6 HANDRAIL EXTENSIONS. THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 8) SHEET A104-A-601 DOOR STYLE 20 IS A SLIDING BARN
 DOOR AND TRACK SYSTEM, HARDWARE GROUP 11 INDICATES ADA
 COMPLIANT PULLS. THE DOOR HAS TO MAINTAIN A 32 INCH
 CLEAR OPENING AS WELL AS THE HARDWARE MEET COMPLIANCE
 WITH :
 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN
 POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND
 USABLE FROM BOTH SIDES.
  
 9) WITH NOT KNOWING THE LOCATION OF THE ACCESSIBLE
 ROOMS, THIS IS ONE OF THE CONCERNS WITH THE EGRESS DOOR
 TO THE INDUVIAL SUITES. THIS EXAMPLE IS FOR ALL ROOMS,
 THE ADA ROOM NEED TO COMPLY. SEE ROOM COLUMN 214 -1013.
 THE ENTRY DOOR IS RECESSED BACK 10 INCHES FROM THE
 REMAINDER OF THE CORRIDOR WALL.
 SHOW COMPLIANCE WITH THE 2017 FLORIDA ACCESSIBILITY
 CODE FOR THE ACCESSIBLE ROOMS. 404.2.4.3 RECESSED DOORS
 AND GATES. MANEUVERING CLEARANCES FOR FORWARD APPROACH
 SHALL BE PROVIDED WHEN ANY OBSTRUCTION WITHIN 18 INCHES
 (455 MM) OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE
 THAN 8 INCHES (205 MM) BEYOND THE FACE OF THE DOOR,
 MEASURED PERPENDICULAR TO THE FACE OF THE DOOR OR GATE.
  
 10) WINDOWS ARE UNDER A SEPARATE PERMITS BUT THERE WILL
 BE OTHER COMPONENTS AND CLADDING REQUIREMENTS. 2017
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 11) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-05-17 Cont ID  
Sent By jpearson Date 2018-05-17 Time 16:14 Rev Time 0.00
Received By jpearson Date 2018-05-17 Time 16:14 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-05-08 Cont ID  
Sent By jpearson Date 2018-05-08 Time 16:44 Rev Time 0.00
Received By jpearson Date 2018-05-04 Time 06:56 Sent To  
Notes
2018-05-08 16:31:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 THESE ITEMS HAVE BEEN DISCUSSED WITH ENGINEER AT
 MEETING ON 5-7-18.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. RISER DIAGRAM SHOWS 3 MAINS. IT APPEARS MAIN # 1 AND
 2 ARE LOCATED IN MDB AND MAIN # 3 IS IN A SEPARATE
 LOCATION. SHOULD MDB BE LABELED MDP? THERE IS A NOTE
 THAT THIS EQUIPMENT IS RATED FOR 12000 AMPS, PROVIDE
 CLARIFICATION AND/OR CORRECTION. PROVIDE PANEL SCHEDULE
 FOR THIS PANEL. ALSO, I DO NOT SEE MAIN # 3 IN THE
 ELECTRICAL ROOM (ROOM 127). PROVIDE CLARIFICATION AND
 NAMES FOR EACH MAIN. WHAT IS THE RATING OF MAIN #1?
 ALSO, FOR PANEL ?MDB?, THERE APPEARS TO ONLY BE 17?
 CLEARANCE FOR THIS? PROVIDE CORRECTIONS AND/OR
 CLARIFICATIONS AS NEEDED. FBC 107.2.1; NEC 110.26,
 695.3 (SOME ITEMS CORRECTED. BASED ON NEW RISER
 DIAGRAM, THERE WOULD BE 4 SERVICES TO THIS BUILDING.
 THERE IS A 2000 AMP SERVICE AT MDP, A 600 AMP SERVICE
 SHOWN ON RISER BUT NOT ON POWER PLAN, A SERVICE TO FIRE
 PUMP, AND A PROPOSED 200 AMP SERVICE FOR KITCHEN. EACH
 SERVICE NEEDS TO BE CLEARLY IDENTIFIED WITH LABELS THAT
 STATE WHICH SERVICE IT IS AND THE LOCATION OF OTHER
 SERVICES ON PROPERTY. EACH MAIN WITHIN EACH SERVICE
 SHOULD ALSO BE LABELED ACCORDINGLY. PANEL A ON ROOF IS
 SHOWS AS BEING FED FROM THE 600 AMP SERVICE, WHICH ONLY
 HAS 198 AMPS DEMAND, SO WHY DOES THE 200 AMP SERVICE
 NEED TO BE ADDED? PANEL A IS ALSO BEING SHOWN AS FED
 FROM MDP AS AN 800 AMP PANEL INSTEAD OF 600 AMP AND IT
 IS INCLUDED IN THE LOAD CALCULATION FOR PANEL MDP,
 WHICH IS AN OBVIOUS DISCREPANCY. WHILE ADDITIONAL
 SERVICES CAN BE ALLOWED, THERE NEEDS TO BE
 JUSTIFICATION. PROVIDE CLARIFICATIONS.)(3RD REVIEW,
 PLAN CURRENTLY SHOWS MORE THAN 6 MAINS WHICH VIOLATES
 NEC 230.71. ENGINEER IS CONFIRMING THE LAYOUT OF MDP
 AND WILL RE-LABEL PLAN WITH ACCURATE COUNT OF MAINS.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. SOME PANEL SCHEDULE SHOW DEMAND FACTORS
 FOR DWELLING UNITS. THE NEC DEFINES A DWELLING UNIT AS:
 ?A SINGLE UNIT, PROVIDING COMPLETE AND INDEPENDENT
 LIVING FACILITIES FOR ONE OR MORE PERSONS, INCLUDING
 PERMANENT PROVISIONS FOR LIVING, SLEEPING, COOKING, AND
 SANITATION.? THIS DEFINITION DOES NOT MATCH THIS
 FACILITY, SO THESE DEMAND FACTORS SHOULD NOT BE USED.
 ALSO, PROVIDE LOAD CALCULATION FOR BUS DUCT. NEC 100,
 215.2, 220, 408.30 (NEED FURTHER EXPLANATION OF LOAD ON
 SERVICE. THE FEEDERS AND OVERCURRENT PROTECTION SHOULD
 BE SIZED TO HANDLE 100% OF THE NON-CONTINUOUS LOAD PLUS
 125% OF THE CONTINUOUS LOAD. THE ONLY CONTINUOUS LOAD
 SHOWN IS FOR LIGHTING, THE LARGEST MOTOR LOAD IS NOT
 SHOWN ON ANY SCHEDULES. ADDITIONALLY, THE RISER DIAGRAM
 SHOWS A FUTURE POOL, BUT NO LOAD IS INCLUDED FOR THIS.
 PROVIDE CORRECTIONS. NEC 215.2, 215.3, 220.14(C),
 430.24)(3RD REVIEW - SOME DATA IS NOT TRANSFERRING
 CORRECTLY IN PANEL SCHEDULES. ENGINEER ADVISED THAT THE
 PROBLEM WILL BE FIXED AND AN ACCURATE LOAD CALCULATION
 PROVIDED.)
 7. CORRECTED.
 8. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE
 CONFIRMED BY INSPECTOR.
 9. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE
 CONFIRMED BY INSPECTOR.
 10. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE
 CONFIRMED BY INSPECTOR.
 11. CORRECTED.
 12. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING
 ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE
 FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. IT APPEARS THAT SOME
 SCHEDULES ARE MISSING AND SOME HAVE INFORMATION THAT IS
 TBD. PROVIDE COMPLETED SCHEDULES. PANEL SCHEDULES
 SHOULD INCLUDE UNIQUE IDENTIFIERS FOR CIRCUITS, SUCH AS
 ROOM NUMBERS OR LOCATIONS. GENERAL TERMS ARE NOT
 ACCEPTABLE. NEC 210.8, 210.12, 215.5, 408.4 (SOME
 PANELS STILL DO NOT HAVE CLEAR LOCATIONS FOR EQUIPMENT
 THAT IS USED IN MORE THAN ONE LOCATION. PROVIDE
 CORRECTION.)
 13. THE FOLLOWING PANELS ARE SHOWN WITH A 125 MAIN
 CIRCUIT BREAKER, BUT HAVE A LOAD THAT EXCEEDS 125 AMP:
 PANEL EML, 4LA, 5LA, 6LA, 7LA, 8LA 9LA, 10LA. PROVIDE
 CORRECTION. NEC 215.3 (THERE ARE STILL MANY PANELS THAT
 ARE NOT SHOWING THE CORRECT TYPE AND SIZE. PROVIDE
 CORRECTIONS.)
 14. CORRECTED.
 15. CORRECTED.
 16. IT APPEARS THE GENERATOR WILL BE OVERLOADED AS
 PANEL EMH SHOWS A LOAD OF 330.7 KVA BEFORE CORRECTIONS
 NOTED IN COMMENT # 14. PROVIDE CORRECTION. NEC 701.4,
 695.3(D)(1) (3RD REVIEW - THE GENERATOR IS STILL SHOWN
 AS OVERLOADED. PROVIDE CORRECTIONS.)
 17. CORRECTED.
 18. CORRECTED.
 19. CORRECTED.
  
 NEW COMMENTS:
  
 20. FIRE PUMP IS BEING SHOWN AS FED FROM MDP IN PANEL
 SCHEDULE. PROVIDE CORRECTION. ALSO, DID NOT SEE A LOAD
 FOR A JOCKEY PUMP ANYWHERE. WILL THERE BE A PRESSURE
 MAINTENANCE PUMP WITH THIS SYSTEM, AND WHERE IS IT FED
 FROM? FBC 107.2.1
 21. DURING MEETING WITH ENGINEER, THE FAULT CURRENT FOR
 THE MAINS WAS DISCUSSED. FAULT CALCULATIONS WILL NEED
 TO BE PROVIDED FOR ANY MODIFICATIONS OF THE SERVICE
 EQUIPMENT SO THAT PROPER SIZING OF EQUIPMENT CAN BE
 CONFIRMED, AS WELL AS PROPER LABELING. PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. IF FPL IS
 NOT ABLE TO RESPOND IN A TIMELY FASHION, WE WILL ACCEPT
 THIS AS A DEFERRED SUBMITTAL WITH THE UNDERSTANDING
 THAT ALL PANELS WILL NEED TO MEET OR EXCEED THE
 CALCULATED FAULT CURRENT. NEC 110.9, 110.10
 22. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-05 Cont ID  
Sent By jpearson Date 2018-04-05 Time 16:53 Rev Time 0.00
Received By jpearson Date 2018-04-05 Time 16:53 Sent To  
Notes
2018-04-05 16:53:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1 (DID NOT SEE THIS NOTE
 ADDED.)
 2. CORRECTED.
 3. RISER DIAGRAM SHOWS 3 MAINS. IT APPEARS MAIN # 1 AND
 2 ARE LOCATED IN MDB AND MAIN # 3 IS IN A SEPARATE
 LOCATION. SHOULD MDB BE LABELED MDP? THERE IS A NOTE
 THAT THIS EQUIPMENT IS RATED FOR 12000 AMPS, PROVIDE
 CLARIFICATION AND/OR CORRECTION. PROVIDE PANEL SCHEDULE
 FOR THIS PANEL. ALSO, I DO NOT SEE MAIN # 3 IN THE
 ELECTRICAL ROOM (ROOM 127). PROVIDE CLARIFICATION AND
 NAMES FOR EACH MAIN. WHAT IS THE RATING OF MAIN #1?
 ALSO, FOR PANEL ?MDB?, THERE APPEARS TO ONLY BE 17?
 CLEARANCE FOR THIS? PROVIDE CORRECTIONS AND/OR
 CLARIFICATIONS AS NEEDED. FBC 107.2.1; NEC 110.26,
 695.3 (SOME ITEMS CORRECTED. BASED ON NEW RISER
 DIAGRAM, THERE WOULD BE 4 SERVICES TO THIS BUILDING.
 THERE IS A 2000 AMP SERVICE AT MDP, A 600 AMP SERVICE
 SHOWN ON RISER BUT NOT ON POWER PLAN, A SERVICE TO FIRE
 PUMP, AND A PROPOSED 200 AMP SERVICE FOR KITCHEN. EACH
 SERVICE NEEDS TO BE CLEARLY IDENTIFIED WITH LABELS THAT
 STATE WHICH SERVICE IT IS AND THE LOCATION OF OTHER
 SERVICES ON PROPERTY. EACH MAIN WITHIN EACH SERVICE
 SHOULD ALSO BE LABELED ACCORDINGLY. PANEL A ON ROOF IS
 SHOWS AS BEING FED FROM THE 600 AMP SERVICE, WHICH ONLY
 HAS 198 AMPS DEMAND, SO WHY DOES THE 200 AMP SERVICE
 NEED TO BE ADDED? PANEL A IS ALSO BEING SHOWN AS FED
 FROM MDP AS AN 800 AMP PANEL INSTEAD OF 600 AMP AND IT
 IS INCLUDED IN THE LOAD CALCULATION FOR PANEL MDP,
 WHICH IS AN OBVIOUS DISCREPANCY. WHILE ADDITIONAL
 SERVICES CAN BE ALLOWED, THERE NEEDS TO BE
 JUSTIFICATION. PROVIDE CLARIFICATIONS.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. SOME PANEL SCHEDULE SHOW DEMAND FACTORS
 FOR DWELLING UNITS. THE NEC DEFINES A DWELLING UNIT AS:
 ?A SINGLE UNIT, PROVIDING COMPLETE AND INDEPENDENT
 LIVING FACILITIES FOR ONE OR MORE PERSONS, INCLUDING
 PERMANENT PROVISIONS FOR LIVING, SLEEPING, COOKING, AND
 SANITATION.? THIS DEFINITION DOES NOT MATCH THIS
 FACILITY, SO THESE DEMAND FACTORS SHOULD NOT BE USED.
 ALSO, PROVIDE LOAD CALCULATION FOR BUS DUCT. NEC 100,
 215.2, 220, 408.30 (NEED FURTHER EXPLANATION OF LOAD ON
 SERVICE. THE FEEDERS AND OVERCURRENT PROTECTION SHOULD
 BE SIZED TO HANDLE 100% OF THE NON-CONTINUOUS LOAD PLUS
 125% OF THE CONTINUOUS LOAD. THE ONLY CONTINUOUS LOAD
 SHOWN IS FOR LIGHTING, THE LARGEST MOTOR LOAD IS NOT
 SHOWN ON ANY SCHEDULES. ADDITIONALLY, THE RISER DIAGRAM
 SHOWS A FUTURE POOL, BUT NO LOAD IS INCLUDED FOR THIS.
 PROVIDE CORRECTIONS. NEC 215.2, 215.3, 220.14(C),
 430.24)
 7. CORRECTED.
 8. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE
 CONFIRMED BY INSPECTOR.
 9. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE
 CONFIRMED BY INSPECTOR.
 10. EXPLANATION PROVIDED FOR CLEARANCE, WILL NEED TO BE
 CONFIRMED BY INSPECTOR.
 11. CORRECTED.
 12. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING
 ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE
 FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. IT APPEARS THAT SOME
 SCHEDULES ARE MISSING AND SOME HAVE INFORMATION THAT IS
 TBD. PROVIDE COMPLETED SCHEDULES. PANEL SCHEDULES
 SHOULD INCLUDE UNIQUE IDENTIFIERS FOR CIRCUITS, SUCH AS
 ROOM NUMBERS OR LOCATIONS. GENERAL TERMS ARE NOT
 ACCEPTABLE. NEC 210.8, 210.12, 215.5, 408.4
  
 NEW COMMENTS:
  
 13. THE FOLLOWING PANELS ARE SHOWN WITH A 125 MAIN
 CIRCUIT BREAKER, BUT HAVE A LOAD THAT EXCEEDS 125 AMP:
 PANEL EML, 4LA, 5LA, 6LA, 7LA, 8LA 9LA, 10LA. PROVIDE
 CORRECTION. NEC 215.3
 14. PANEL EMH SHOWS A LOAD OF 400.36 AMPS ON A?, WHICH
 EXCEEDS THE RATING OF THE PANEL AND THE CONDUCTORS
 FEEDING THE PANEL. IN ADDITION TO THIS, THE LARGEST
 MOTOR DEMAND AT 125% HAS NOT BEEN INCLUDED, WHICH WOULD
 FURTHER OVERLOAD THIS PANEL AND CONDUCTORS. PROVIDE
 CORRECTION. NEC 215.2, 215.3, 310.15(B)(16)
 15. PROVIDE VOLTAGE DROP CALCULATION FOR FEEDER NUMBER
 7 FROM GENERATOR TO TRANSFER SWITCH TO CONFIRM THE
 CONDUCTOR SIZE IS ADEQUATE FOR CODE COMPLIANCE. PROVIDE
 A NOTE TO INCLUDE INDICATION OF SUBMITTAL OF COMPLETION
 DOCUMENTS PER FBC EC C405.6.4, FBC EC C405.6.3, NEC
 695.7
 16. IT APPEARS THE GENERATOR WILL BE OVERLOADED AS
 PANEL EMH SHOWS A LOAD OF 330.7 KVA BEFORE CORRECTIONS
 NOTED IN COMMENT # 14. PROVIDE CORRECTION. NEC 701.4,
 695.3(D)(1)
 17. PLAN SHOWS THE FIRE PUMP CONTROLLER BEING FED FROM
 PANEL EMH THROUGH ATS-1. THIS ATS IS REQUIRED TO BE
 LISTED FOR USE WITH FIRE PUMP EQUIPMENT. PROVIDE SPEC
 SHEET TO CONFIRM LISTING. NEC 110.3, 695.10
 18. IF THE FIRE PUMP CONTROLLER IS FED FROM PANEL EMH
 AS SHOWN, THIS BREAKER WILL NEED TO COMPLY WITH NEC
 695.4(B)(3)(B) THROUGH (E). SHOW METHOD OF COMPLIANCE.
 19. THE PREFERRED METHOD OF CONNECTION FROM THE
 GENERATOR TO THE FIRE PUMP CONTROLLER PER THE NEC WOULD
 BE A DIRECT CONNECTION WITH THE GENERATOR HAVING TWO
 BREAKERS, ONE DEDICATED TO ATS-1 AND ONE DEDICATED TO
 THE FIRE PUMP CONTROLLER, WHICH WOULD BE A LISTED FIRE
 PUMP CONTROLLER WITH BUILT IN ATS. THIS IS HOW WE
 NORMALLY SEE THIS TYPE OF INSTALLATION DESIGNED. THE
 DESIGN SHOWN IS PERMITTED, BUT MUST COMPLY WITH
 COMMENTS 17 AND 18 ABOVE. IF THE PREFERRED METHOD
 MENTIONED IN THE NEC IS USED, COMMENTS 17 AND 18 DO NOT
 APPLY. NEC 695.4(A)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-19 Cont ID  
Sent By jpearson Date 2018-02-19 Time 10:04 Rev Time 0.00
Received By jpearson Date 2018-02-18 Time 10:26 Sent To  
Notes
2018-02-19 10:04:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
 2. THERE IS A SYMBOL ON THE RISER DIAGRAM SEVERAL TIMES
 THAT LOOKS LIKE A SYMBOL FOR AN EXIT LIGHT. WHAT DOES
 THIS SYMBOL MEAN? FBC 107.2.1
 3. RISER DIAGRAM SHOWS 3 MAINS. IT APPEARS MAIN # 1 AND
 2 ARE LOCATED IN MDB AND MAIN # 3 IS IN A SEPARATE
 LOCATION. SHOULD MDB BE LABELED MDP? THERE IS A NOTE
 THAT THIS EQUIPMENT IS RATED FOR 12000 AMPS, PROVIDE
 CLARIFICATION AND/OR CORRECTION. PROVIDE PANEL SCHEDULE
 FOR THIS PANEL. ALSO, I DO NOT SEE MAIN # 3 IN THE
 ELECTRICAL ROOM (ROOM 127). PROVIDE CLARIFICATION AND
 NAMES FOR EACH MAIN. WHAT IS THE RATING OF MAIN #1?
 ALSO, FOR PANEL ?MDB?, THERE APPEARS TO ONLY BE 17?
 CLEARANCE FOR THIS? PROVIDE CORRECTIONS AND/OR
 CLARIFICATIONS AS NEEDED. FBC 107.2.1; NEC 110.26,
 695.3
 4. ELECTRICAL SCHEDULE PROVIDED ON SHEET E-401 IS
 UNREADABLE. PROVIDE CLEAR SCHEDULE. FBC 107.2.1
 5. THERE DOESN?T APPEAR TO BE THE PROPER CLEARANCE
 BETWEEN THE FIRE PUMP CONTROLLER/ATS AND THE FIRE PUMP.
 PROVIDE CORRECTION. NEC 110.26
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. SOME PANEL SCHEDULE SHOW DEMAND FACTORS
 FOR DWELLING UNITS. THE NEC DEFINES A DWELLING UNIT AS:
 ?A SINGLE UNIT, PROVIDING COMPLETE AND INDEPENDENT
 LIVING FACILITIES FOR ONE OR MORE PERSONS, INCLUDING
 PERMANENT PROVISIONS FOR LIVING, SLEEPING, COOKING, AND
 SANITATION.? THIS DEFINITION DOES NOT MATCH THIS
 FACILITY, SO THESE DEMAND FACTORS SHOULD NOT BE USED.
 ALSO, PROVIDE LOAD CALCULATION FOR BUS DUCT. NEC 100,
 215.2, 220, 408.30
 7. PROVIDE WIRE SIZES FOR ANY NEW FEEDERS TO BE
 INSTALLED NEC 215.2, 215.5
 8. SHEET E-102, THE 2ND FLOOR ELECTRICAL ROOM, LOCATION
 OF THE 75 KVA TRANSFORMER DOES NOT HAVE THE PROPER
 CLEARANCE. PROVIDE CORRECTION. NEC 110.26
 9. SHEET E-103, THE 3RD FLOOR TO 9TH FLOOR ELECTRICAL
 ROOMS, LOCATION OF THE 75 KVA TRANSFORMER DOES NOT HAVE
 THE PROPER CLEARANCE. PROVIDE CORRECTION. NEC 110.26
 10. SHEET E-104, THE 10TH FLOOR ELECTRICAL ROOM,
 LOCATION OF THE 75 KVA TRANSFORMER DOES NOT HAVE THE
 PROPER CLEARANCE. PROVIDE CORRECTION. NEC 110.26
 11. SHEET E-105, PROVIDE GFCI PROTECTED OUTLET FOR
 SERVICING OF A/C EQUIPMENT PER CODE. NEC 210.63
 12. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING
 ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE
 FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. IT APPEARS THAT SOME
 SCHEDULES ARE MISSING AND SOME HAVE INFORMATION THAT IS
 TBD. PROVIDE COMPLETED SCHEDULES. PANEL SCHEDULES
 SHOULD INCLUDE UNIQUE IDENTIFIERS FOR CIRCUITS, SUCH AS
 ROOM NUMBERS OR LOCATIONS. GENERAL TERMS ARE NOT
 ACCEPTABLE. NEC 210.8, 210.12, 215.5, 408.4
  
 BECAUSE OF MISSING INFORMATION ON THE PLANS SUBMITTED,
 FURTHER COMMENTS ARE POSSIBLE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-05-17 Cont ID  
Sent By pleduc Date 2018-05-17 Time   Rev Time 0.00
Received By pleduc Date 2018-05-17 Time 12:42 Sent To  
Notes
2018-05-17 12:57:45THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXIT PATH FROM THE SERVICE COURTYARD GOES THRU A
 DOUBLE GATE. THE GATE SHALL BE ACCESSIBLE AND FUNCTION
 AS AN EXIT DOOR AT ALL TIMES.
 CLOSE COORDINATION WITH THE OFFICE OF FIRE MARSHAL FOR
 EXIT FUNCTIONALITY IS REQUIRED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-28 Cont ID  
Sent By scaldero Date 2018-03-28 Time 10:44 Rev Time 0.00
Received By scaldero Date 2018-03-28 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-13 Cont ID  
Sent By scaldero Date 2018-02-13 Time 14:21 Rev Time 0.00
Received By scaldero Date 2018-02-13 Time 10:50 Sent To  
Notes
2018-02-13 14:21:05PERMIT # 18020254
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) AT A PRE-PERMIT MEETING ON JANUARY 25, 2018, IT WAS
 STATED THAT THE PLANS WERE BEING DRAWN IN ACCORDANCE
 WITH THE PREVIOUS EDITIONS (NOT CURRENT EDITIONS) OF
 THE FBC AND FFC.
 PLEASE UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
 IF THIS REQUEST IS NO LONGER BEING MADE, PLEASE UPDATE
 THE CODE LIST TO REFERENCE THE 6TH EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE 2015
 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PER NFPA 1: 16.3.5 STANDPIPES. IN ALL NEW BUILDINGS
 IN WHICH STANDPIPES ARE REQUIRED OR WHERE STANDPIPES
 EXIST IN BUILDINGS BEING ALTERED OR DEMOLISHED, SUCH
 STANDPIPES SHALL BE MAINTAINED IN CONFORMITY WITH THE
 PROGRESS OF BUILDING CONSTRUCTION IN SUCH A MANNER THAT
 THEY ARE ALWAYS READY FOR USE. [241:7.6]
  
 3) PER NFPA 1: 13.3.2.6 * EXTERIOR ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS. THE PORTE-COCHERE SHALL BE PROTECTED BY
 THE PROVIDED FIRE SPRINKLER SYSTEM.
 13.3.2.6.1 : UNLESS THE REQUIREMENTS OF 13.3.2.6.2,
 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE
 INSTALLED UNDER EXTERIOR ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH.
 [13:8.15.7.1]
  
 4) PER NFPA 101: 11.8.6.2 -- THE EMERGENCY COMMAND
 CENTER SHALL CONTAIN THE FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER
 SECTION OF THIS CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-05-16 Cont ID  
Sent By gjohnson Date 2018-05-16 Time 14:55 Rev Time 0.00
Received By gjohnson Date 2018-05-16 Time 14:55 Sent To  
Notes
2018-05-16 15:03:24GAS PROVISO:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL
 GAS CODE SEC. 502 THRU 505. SUBMIT CALCULATIONS FOR
 COMBUSTION AIR PER THE FBC-2014 FUEL GAS CODE SEC. 304.
 FOR BOILERS
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304. FOR BOILER AND DRYERS
  
 PROVIDE BEFORE ROUGH INSPECTION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-03-12 Cont ID  
Sent By gjohnson Date 2018-03-12 Time 12:04 Rev Time 0.00
Received By gjohnson Date 2018-03-12 Time 12:04 Sent To  
Notes
2018-03-12 12:06:35GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-05-17 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-15 Time 12:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-10 Cont ID  
Sent By rmcdouga Date 2018-05-10 Time 18:41 Rev Time 0.00
Received By rmcdouga Date 2018-05-02 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-18 Cont ID  
Sent By ajones Date 2018-04-18 Time 15:58 Rev Time 0.00
Received By ajones Date 2018-03-27 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-13 Cont ID  
Sent By cpuell Date 2018-03-13 Time 15:24 Rev Time 0.00
Received By cpuell Date 2018-02-09 Time 12:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By rmcdouga Date 2018-05-21 Time 09:07 Rev Time 0.00
Received By rmcdouga Date 2018-05-21 Time 09:06 Sent To  
Notes
2018-05-21 09:07:26MU-2018-17263, PAID $121,778.88

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-02-15 Time   Rev Time 0.00
Received By jwitmer Date 2018-02-14 Time 15:15 Sent To  
Notes
2018-02-15 16:22:471) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-05-16 Cont ID  
Sent By gjohnson Date 2018-05-16 Time 16:49 Rev Time 0.00
Received By ccole Date 2018-05-07 Time 09:38 Sent To  
Notes
2018-05-07 17:09:04MECHANICAL PLANS APPROVED WITH EXECEPTION AND PROVISOS.
 5/16/18
  
 AS OF 5/16/18 THE FOLLOWING LIST OF COMMENTS FROM THE
 3RD REVIEW WERE NOT ADDRESSED, HOWEVER DUE TO THE
 URGENT NEED TO HAVE THE PERMIT ISSUED, THE CURRENT
 MECHANICAL PLANS AND DOCUMENTS ARE APPROVED WITH
 EXCEPTION, AND THE REMAINING COMMENTS LISTED BELOW ARE
 DEEMED TO BE PROVISOS TO BE ADDRESSED BY THE DESIGN
 PROFESSIONAL AS SOON AS POSSIBLE.
  
 3RD REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODE
 PERMIT #18020254
 5/7/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS FOLLOW-UP (3RD) REVIEW IS BASED ON THE RESUBMITTED
 PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE
 ENGINEER OF RECORD.
 ALL PREVIOUS REVIEW COMMENTS NOT COMPLETELY RESOLVED
 ARE LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER.
  
 2) THE BTUH CAPACITY OF THE BOILER AS SHOWN IN THE
 ENERGY CALCULATIONS DOES NOT MATCH THE CAPACITY IN THE
 SCHEDULE ON SHEET M-601.
  
 5) PLEASE INCLUDE IN THE SMOKE CONTROL OUTLINE A
 NARRATIVE THAT CLARIFIES THE SEQUENCE OF OPERATION OF
 THE SMOKE CONTROL SYSTEM DURING AN ALARM AND THAT
 ANSWERS THESE QUESTIONS:
  
 A) WILL ALL PRESSURIZATION FANS ACTIVATE DURING AN
 ALARM?
 B) HOW WILL THE PRESSURIZATIONS IN THE STAIRWELL AND
 ELEVATOR SHAFTS MODULATE AND BE MONITORED? WILL THE
 SYSTEMS BE DIGITALLY CONTROLLED USING SENSORS AND A
 DIGITAL CONTROL PANEL? I AM NOT SEEING ANY CONTROLS IN
 THE FA DRAWINGS, OR ANY CONTROL DIAGRAMS FOR SMOKE
 CONTROL SEQUENCING.
 D) WHAT IS THE SEQUENCE OF OPERATION FOR THE DOA UNITS
 DURING AN ALARM PERTAINING TO THE FLOOR OF INCIDENT AND
 THE UNINVOLVED FLOORS ABOVE AND BELOW?
 E) WHAT IS THE SEQUENCE OF OPERATION FOR THE FIRE/SMOKE
 DAMPERS AT THE SHAFTS ON EACH FLOOR?
 F) WHAT SYSTEMS WILL BE CONNECTED TO STANDBY POWER?
 G) WHAT IS THE RESPONSE TIME OF THE FANS, DAMPERS,
 ETC.?
 H) WHAT WILL BE THE DURATION OF THE OPERATION?
 I) CLARIFY HOW SMOKE REMOVAL WILL BE ACCOMPLISHED. THE
 NARRATIVE RESPONSE TO THIS COMMENT INDICATES REMOVAL BY
 NATURAL MEANS- OPERABLE WINDOWS IN ACCORDING WITH
 SECTION 403.4.7 ITEM #1. PLEASE NOTE THAT THE PLANS DO
 NOT PROVIDE A SCHEDULE FOR THE WINDOWS ON THE BUILDING
 PERIMETER WHICH IS NEEDED TO VERIFY COMPLIANCE.
 J) PROVIDE CONTROL DIAGRAMS ON THE PLANS SHOWING THE
 SEQUENCE OF OPERATION FOR THE SMOKE CONTROL SYSTEM.
  
 5 CONTINUED) CONCERNING THE "EXIT VESTIBULE"
 VENTILATION, THE ENGINEER IS STATING IN THE NARRATIVE
 THAT THE "VESTIBULES" ARE NOT REQUIRED, HOWEVER THE
 "EXIT VESTIBULES" ARE SHOWING ON ALL THE RESIDENTIAL
 FLOORS AT STAIRS #235-935. PLEASE REFER TO SECTION
 909.20.3.3 FOR VENTILATION REQUIREMENTS FOR VESTIBULES.
 BASED ON THAT REQUIREMENT, IT SEEMS POSSIBLE THAT
 DEFINING THESE AREAS
  
 AS "VESTIBULES" MAY BE INCORRECT. FURTHER, I AM NOT
 SEEING ANY REFERENCES OR DEFINITIONS IN THE BUILDING
 CODE FOR "EXIT VESTIBULES".
  
 5 CONTINUED) SHEET M-106: CLARIFY WHY SMOKE DETECTORS
 ARE TO BE INSTALLED ADJACENT TO THE STAIRWELL FANS.
 WHICH CODE, STANDARD, OR ENGINEERING ANALYSIS DOES THIS
 REQUIREMENT COME FROM? PLEASE NOTE THAT THE REQUIREMENT
 IN SECTION 606.2.1 IS FOR AIR HANDLING SYSTEMS.
  
 5 CONTINUED) SHEET M-601: NOTE #9 SPECIFYING A SECOND
 DRIVE BELT HAS NOT BEEN ADDED TO THE NOTES UNDER EACH
 SMOKE CONTROL FAN. CLARIFY IS THE FANS WILL BE UL 705
 LISTED AND LABELED AS POWER VENTILATORS.
  
 5 CONTINUED) CLASS 1 MOTORIZED DAMPERS REQUIRED ON
 STAIRWAY AND ELEVATOR RELIEF VENTS, AND ON O/A AND
 EXHAUST DUCTS AT THE SHAFT PENETRATIONS- SECTION
 C403.2.4.3
  
 7) SHEET M-401: PLEASE INCLUDE THE EXHAUST CLEARANCE
 DISTANCES TO ADJOINING GRADE AND PROPERTY LINES PER
 SECTION 501.3.1(2).
  
 9) CONCERNING THE KEF INLINE FAN, PLEASE CLARIFY IF THE
 GREASE EXHAUST DUCT IS TO BE FIRE-WRAPPED. IF SO, THE
 FAN MUST BE IN A FIRE RATED ROOM EQUAL TO RATING OF THE
 WRAPPING- SECTION 506.5.1.2
  
 ADDITIONAL COMMENTS:
  
 1) MECHANICAL ROOM DOORS #241 & 349, 449, 549, 649,
 749, 849, & 949 MUST BE NON-COMBUSTIBLE- SECTION
 C403.2.9.2 & SECTION 602.2.1.
  
 2) M-601: MAKEUP AIR FOR THE HOOD CANNOT BE USED AS
 COMBUSTION AIR FOR THE COOKING APPLIANCES. THAT AIR IS
 SOLEY FOR REPLACEMENT OF EXHAUSTED AIR- SECTION 304.9.1
 PLEASE SEE SECTION 304.9.3: WHERE COMBUSTION AIR IS
 PROVIDED BY MECHANICAL VENTILATION, THE SYSTEM SHALL
 PROVIDE THE COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. THE RATE SHALL BE 0.35 CFMS
 PER
  
 1000 BTUH.
  
 3) DEFERRED SUBMITTALS: 9) THE FOLLOWING IS A LIST OF
 DEFERRED SUBMITTALS FOR THE MECHANICAL PERMIT THAT WILL
 REQUIRE SHOP DRAWING APPROVAL BY THE ENGINEER OF
 RECORD:
  
 A) SMOKE CONTROL FANS.
 B) FIRE AND FIRE/SMOKE DAMPERS.
 C) BAROMETRIC DAMPERS
 D) DUCT SMOKE DETECTORS
 E) AC ROOF AND DUCT STANDS, WALL BRACKETS
 F) EXHAUST AND OUTSIDE AIR LOUVERS
 G) PIPING INSULATIONS
 H) ACCESS PANELS
 I) GENERATOR
 J) COMMERCIAL CLOTHES DRYERS
 K) COOKING APPLIANCES
 L) DUCT FIRE WRAPPING
 M) FIRESTOPPING AND FIRE CAULKING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-12 Cont ID  
Sent By ccole Date 2018-04-12 Time 08:58 Rev Time 0.00
Received By ccole Date 2018-04-06 Time 12:32 Sent To  
Notes
2018-04-12 09:03:162ND REVIEW FBC-2017 MECHANICAL, BUILDING, EXISTING
 BUILDING, ENERGY CONSERVATION CODES
 PERMIT #18020254
 4/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS FOLLOW-UP REVIEW IS BASED ON THE RESUBMITTED
 PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE
 ENGINEER OF RECORD.
 ALL 1ST REVIEW COMMENTS NOT COMPLETELY RESOLVED ARE
 LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER.
  
 COMMENT #2) A) THE REVISED ENERGYGAUGE COMPLIANCE FORM
 DOES NOT LIST THE G2 SYSTEM WHICH IS LISTED IN AC
 SCHEDULE AT 18,800 BTUH (15.74 SEER). B) THE C-1,2
 SYSTEMS SHOWN IN THE REPORT ARE NOT IN THE SCHEDULE. C)
 THE COMPLIANCE DATA LISTED FOR WSHP 2-1 & 2-2 IN THE
 REPORT DOES NOT MATCH THE SCHEDULE.
 D) THE SEER FOR WSHP-1-5 LISTED IN THE FORM DOES NOT
 MATCH THE SCHEDULE.
  
 4) COMMISSIONING: A) THE SUBMITTED PLAN IS INDICATING
 THAT THE CONSTRUCTION CONTRACTOR SHALL BE THE
 RESPONSIBLE PARTY TO OVERSEE THE COMMISSIONING PROCESS,
 HOWEVER IT IS THE RESPONSIBILITY OF THE LICENSED MEP
 ENGINEERS OR APPROVED AGENCY TO PROVIDE EVIDENCE OF
 SYSTEM COMMISSIONING PER SECTION C408.2. FURTHER,
 SECTION C408.2.1 ITEM #1 SPECIFIES THAT THE LICENSED
 ENGINEERS OR APPROVED AGENCY NAME OR SELECT THE
 PERSONNEL INTENDED TO ACCOMPLISH EACH OF THE
 ACTIVITIES. B) PLEASE REVIEW THE FOLLOWING CODE
 SECTIONS PERTAINING TO COMMISSIONING AND PROVIDE MORE
 SPECIFIC INFORMATION ON THE PROPOSED COMMISSIONING
 PLAN: C408.2.2, C408.2.2.1, C408.2.3, C408.2.3.1,
 C408.2.3.1, AND (C408.3- PLEASE NOTE THE SUBMITTED PLAN
 DOES NOT PROVIDE ANY DETAILS FOR THE LIGHTING SYSTEMS
 FUNCTIONAL TESTING.) B) ADVISORY: PLEASE REVIEW SECTION
 C408.2.4 PERTAINING TO THE PRELIMINARY COMMISSIONING
 REPORT TO BE COMPLETED AND CERTIFIED BY THE LICENSED
 ENGINEER, AND THEN SUBMITTED TO THE BUILDING OWNERSHIP
 AND THE BUILDING DEPARTMENT FOR REVIEW.
  
 5) THE SMOKE CONTROL RATIONAL ANALYSIS DOES NOT ADDRESS
 MANY OF THE COMPLIANCES LISTED UNDER SECTION 513-
 PLEASE REVIEW SECTION 513.6.3 FBC-17 MECHANICAL:
 PRESSURIZED STAIRWAYS AND ELEVATOR HOISTWAYS: WHERE
 STAIRWAYS OR ELEVATOR HOISTWAYS ARE PRESSURIZED, SUCH
 PRESSURIZATION SYSTEMS SHALL COMPLY WITH SECTION 513 AS
 SMOKE CONTROL SYSTEMS, IN ADDITION TO THE REQUIREMENTS
 OF SECTIONS 909.20 OF THE FLORIDA BUILDING CODE,
 BUILDING AND THE FLORIDA FIRE PREVENTION CODE.
 PLEASE REVIEW AND INCLUDE IN THE REPORT REQUIRED
 INFORMATION AS OUTLINED IN SECTION 513 INCLUDING, BUT
 NOT LIMITED TO: 513.2 GENERAL DESIGN REQUIREMENTS
 INCLUDING APPLICABLE CODES AND STANDARDS. 513.3 SPECIAL
 INSPECTION AND TEST REQUIREMENTS. 513.4.4 HVAC SYSTEMS.
 513.4.6 DURATION OF OPERATION. 513.4.7 SMOKE CONTROL
 SYSTEM INTERACTION. 513.5 SMOKE BARRIER CONSTRUCTION.
 513.5.1 TOTAL LEAKAGE AREA. 513.5.2 TESTING OF LEAKAGE
 AREA. 513.5.3 OPENING PROTECTION. 513.10 EQUIPMENT.
 513.10.5 FANS. 513.11 STANDBY POWER. 513.11.1 EQUIPMENT
 ROOM. 513.12 DETECTION AND CONTROL SYSTEMS. 513.16
 FIREFIGHTER'S SMOKE CONTROL PANEL.
  
 5) CONTINUED- CONCERNING THE REDESIGN USING VESTIBULES
 AT STAIR #2 LOCATION ON THE RESIDENTIAL FLOORS, THE
 CODE GIVES TWO OPTIONS FOR VENTILATION- NATURAL OR
 MECHANICAL- SECTIONS 909.20.3 AND 909.20.4 FBC-17
 BUILDING. BECAUSE NATURAL VENTILATION IS NOT POSSIBLE,
 MECHANICAL VENTILATION MUST BE PROVIDED PER SECTION
 909.20.4.2. PLEASE REVIEW THIS SECTION AND SECTIONS
 909.20.4.4 AND 909.20.5 STAIRWAY AND RAMP
 PRESSURIZATION ALTERNATIVE. 909.20.4.4 REQUIRES A
 DAMPERED RELIEF OPENING IN THE STAIRWAY. 909.20.5
 PROVIDES THE DESIGN PARAMETERS FOR PRESSURIZATION OF
 THE STAIRWAYS.
  
 5) CONTINUED- THE SELECTED SMOKE CONTROL FANS SHOWN IN
 THE SCHEDULE ARE NOT COMPLETELY IN COMPLIANCE WITH
 SECTION 513.10.5 WHICH REQUIRES BELTED FANS TO HAVE 1.5
 TIMES THE NUMBER OF BELTS FOR THE DESIGN DUTY WITH THE
 MINIMUM NUMBER OF BELTS BEING TWO. THE FANS MUST ALSO
 BE UL LISTED AS POWER VENTILATORS FOR SMOKE CONTROL
 SYSTEMS.
  
 5) CONTINUED- PLEASE REVIEW THE FOLLOWING CODE SECTIONS
 THAT APPLY TO THE PRESSURIZED ELEVATOR HOISTWAYS, AND
 REVISE THE ANALYSIS AND PLANS TO SHOW COMPLIANCE.
 909.21 ELEVATOR HOISTWAY PRESSURIZATION ALTERNATIVE.
 WHERE ELEVATOR HOISTWAY PRESSURIZATION IS PROVIDED IN
 LIEU OF REQUIRED ENCLOSED ELEVATOR LOBBIES, THE
 PRESSURIZATION SYSTEM SHALL COMPLY WITH SECTIONS
 909.21.1 THROUGH 909.21.11.
 909.21.1 PRESSURIZATION REQUIREMENTS.
 ELEVATOR HOISTWAYS SHALL BE PRESSURIZED TO MAINTAIN A
 MINIMUM POSITIVE PRESSURE OF 0.10 INCH OF WATER (25 PA)
 AND A MAXIMUM POSITIVE PRESSURE OF 0.25 INCH OF WATER
 (67 PA) WITH RESPECT TO ADJACENT OCCUPIED SPACE ON ALL
 FLOORS. THIS PRESSURE SHALL BE MEASURED AT THE MIDPOINT
 OF EACH HOISTWAY DOOR, WITH ALL ELEVATOR CARS AT THE
 FLOOR OF RECALL AND ALL HOISTWAY DOORS ON THE FLOOR OF
 RECALL OPEN AND ALL OTHER HOISTWAY DOORS CLOSED. THE
 PRESSURE DIFFERENTIALS SHALL BE MEASURED BETWEEN THE
 HOISTWAY AND THE ADJACENT ELEVATOR LANDING. THE OPENING
 AND CLOSING OF HOISTWAY DOORS AT EACH LEVEL MUST BE
 DEMONSTRATED DURING THIS TEST. THE SUPPLY AIR INTAKE
 SHALL BE FROM AN OUTSIDE, UNCONTAMINATED SOURCE LOCATED
 A MINIMUM DISTANCE OF 20 FEET (6096 MM) FROM ANY AIR
 EXHAUST SYSTEM OR OUTLET.
 EXCEPTIONS:
 1. ON FLOORS CONTAINING ONLY GROUP R OCCUPANCIES, THE
 PRESSURE DIFFERENTIAL IS PERMITTED TO BE MEASURED
 BETWEEN THE HOISTWAY AND A DWELLING UNIT OR SLEEPING
 UNIT.
 2. WHERE AN ELEVATOR OPENS INTO A LOBBY ENCLOSED IN
 ACCORDANCE WITH SECTION 3007.6 OR 3008.6, THE PRESSURE
 DIFFERENTIAL IS PERMITTED TO BE MEASURED BETWEEN THE
 HOISTWAY AND THE SPACE IMMEDIATELY OUTSIDE THE DOOR(S)
 FROM THE FLOOR TO THE ENCLOSED LOBBY.
 3. THE PRESSURE DIFFERENTIAL IS PERMITTED TO BE
 MEASURED RELATIVE TO THE OUTDOOR ATMOSPHERE ON FLOORS
 OTHER THAN THE FOLLOWING:
 1.THE FIRE FLOOR.
 2. THE TWO FLOORS IMMEDIATELY BELOW THE FIRE FLOOR.
 3. THE FLOOR IMMEDIATELY ABOVE THE FIRE FLOOR.
 4. THE MINIMUM POSITIVE PRESSURE OF 0.10 INCH OF WATER
 (25 PA) AND A MAXIMUM POSITIVE PRESSURE OF 0.25 INCH OF
 WATER (67 PA) WITH RESPECT TO OCCUPIED FLOORS ARE NOT
 REQUIRED AT THE FLOOR OF RECALL WITH THE DOORS OPEN.
 909.21.1.1 USE OF VENTILATION SYSTEMS.
 VENTILATION SYSTEMS, OTHER THAN HOISTWAY SUPPLY AIR
 SYSTEMS, ARE PERMITTED TO BE USED TO EXHAUST AIR FROM
 ADJACENT SPACES ON THE FIRE FLOOR, TWO FLOORS
 IMMEDIATELY BELOW AND ONE FLOOR IMMEDIATELY ABOVE THE
 FIRE FLOOR TO THE BUILDING'S EXTERIOR WHERE NECESSARY
 TO MAINTAIN POSITIVE PRESSURE RELATIONSHIPS AS REQUIRED
 IN SECTION 909.21.1 DURING OPERATION OF THE ELEVATOR
 SHAFT PRESSURIZATION SYSTEM.
 909.21.2 RATIONAL ANALYSIS.
 A RATIONAL ANALYSIS COMPLYING WITH SECTION 909.4 SHALL
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
 909.21.3 DUCTS FOR SYSTEM.
 ANY DUCT SYSTEM THAT IS PART OF THE PRESSURIZATION
 SYSTEM SHALL BE PROTECTED WITH THE SAME FIRE-RESISTANCE
 RATING AS REQUIRED FOR THE ELEVATOR SHAFT ENCLOSURE.
 909.21.4 FAN SYSTEM.
 THE FAN SYSTEM PROVIDED FOR THE PRESSURIZATION SYSTEM
 SHALL BE AS REQUIRED BY SECTIONS 909.21.4.1 THROUGH
 909.21.4.4.
 909.21.4.1 FIRE RESISTANCE.
 WHERE LOCATED WITHIN THE BUILDING, THE FAN SYSTEM THAT
 PROVIDES THE PRESSURIZATION SHALL BE PROTECTED WITH THE
 SAME FIRE-RESISTANCE RATING REQUIRED FOR THE ELEVATOR
 SHAFT ENCLOSURE.
 909.21.4.2 SMOKE DETECTION.
 THE FAN SYSTEM SHALL BE EQUIPPED WITH A SMOKE DETECTOR
 THAT WILL AUTOMATICALLY SHUT DOWN THE FAN SYSTEM WHEN
 SMOKE IS DETECTED WITHIN THE SYSTEM.
 909.21.4.3 SEPARATE SYSTEMS.
 A SEPARATE FAN SYSTEM SHALL BE USED FOR EACH ELEVATOR
 HOISTWAY.
 909.21.4.4 FAN CAPACITY.
 THE SUPPLY FAN SHALL BE EITHER ADJUSTABLE WITH A
 CAPACITY OF NOT LESS THAN 1,000 CFM (0.4719 M3/S) PER
 DOOR, OR THAT SPECIFIED BY A REGISTERED DESIGN
 PROFESSIONAL TO MEET THE REQUIREMENTS OF A DESIGNED
 PRESSURIZATION SYSTEM.
 909.21.5 STANDBY POWER.
 THE PRESSURIZATION SYSTEM SHALL BE PROVIDED WITH
 STANDBY POWER IN ACCORDANCE WITH SECTION 2702.
 909.21.6 ACTIVATION OF PRESSURIZATION SYSTEM.
 THE ELEVATOR PRESSURIZATION SYSTEM SHALL BE ACTIVATED
 UPON ACTIVATION OF EITHER THE BUILDING FIRE ALARM
 SYSTEM OR THE ELEVATOR LOBBY SMOKE DETECTORS. WHERE
 BOTH A BUILDING FIRE ALARM SYSTEM AND ELEVATOR LOBBY
 SMOKE DETECTORS ARE PRESENT, EACH SHALL BE
 INDEPENDENTLY CAPABLE OF ACTIVATING THE PRESSURIZATION
 SYSTEM.
 909.21.7 TESTING.
 TESTING FOR PERFORMANCE SHALL BE REQUIRED IN ACCORDANCE
 WITH SECTION 909.18.8. SYSTEM ACCEPTANCE SHALL BE IN
 ACCORDANCE WITH SECTION 909.19.
 909.21.8 MARKING AND IDENTIFICATION.
 DETECTION AND CONTROL SYSTEMS SHALL BE MARKED IN
 ACCORDANCE WITH SECTION 909.14.
 909.21.9 CONTROL DIAGRAMS.
 CONTROL DIAGRAMS SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 909.15.909.21.10 CONTROL PANEL.
 A CONTROL PANEL COMPLYING WITH SECTION 909.16 SHALL BE
 PROVIDED.
 909.21.11 SYSTEM RESPONSE TIME.
 HOISTWAY PRESSURIZATION SYSTEMS SHALL COMPLY WITH THE
 REQUIREMENTS FOR SMOKE CONTROL SYSTEM RESPONSE TIME IN
 SECTION 909.17.
  
 5) CONTINUED: REFER TO SECTION 403.4.7 FBC-17 BUILDING
 SMOKE REMOVAL AND INDICATE COMPLIANCE IN THE ANALYSIS
 AND THE PLANS.
  
 6) CONCERNING THE RISERS, SHOW LOCATIONS OF THE
 BAROMETRIC DAMPERS IN THE STAIR SHAFTS AND THE VENTS IN
 THE HOISTWAYS, IF APPLICABLE TO THE PROPOSED SMOKE
 CONTROL DESIGN.
  
 7) AS PREVIOUSLY NOTED, THE STANDBY POWER SOURCE AND
 ITS TRANSFER SWITCHES SHALL BE IN A ROOM SEPARATE FROM
 THE NORMAL POWER TRANSFORMERS AND SWITCH GEAR. SHEET
 E-401 SHOWS ATS-1 IN THE MAIN ELECTRICAL ROOM.
  
 9) ADVISORY NOTES FOR THE KITCHEN EXHAUST SYSTEM: A)
 SEPARATE PERMIT REQUIRED. B) THE GREASE DUCT SHALL HAVE
 A MINIMUM 18" CLEARANCE TO COMBUSTIBLE CONSTRUCTION. C)
 EXHAUST FAN MOTORS SHALL BE LOCATED OUTSIDE OF THE
 EXHAUST AIRSTREAM. D) WHERE ENCLOSED DUCT SYSTEMS ARE
 CONNECTED TO IN-LINE FANS NOT LOCATED OUTDOORS, THE FAN
 SHALL BE LOCATED IN A ROOM OR SPACE HAVING THE SAME
 FIRE-RESISTANCE RATING AS THE DUCT ENCLOSURE. E) THE
 EXHAUST OUTLET TERMINATION AT THE SIDEWALL SHALL BE
 LOCATED SO AS NOT TO CAUSE A PUBLIC NUISANCE OR A FIRE
 HAZARD. F) THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES F.
  
 12) FIRE DAMPERS REQUIRED FOR THE 60X10 RA GRILL AT
 HVAC 134.
  
 13) ACKNOWLEDGED THAT MANUFACTURER'S SPECIFICATIONS FOR
 THE COMMERCIAL DRYERS WILL BE A DEFERRED SUBMITTAL, AND
 WILL THE SUBMITTAL WILL BEAR AND APPROVAL STAMP BY THE
 EOR.
  
 18) ACKNOWLEDGED THAT ACCESS PANELS WILL BE PROVIDED
 FOR HEAT PUMPS ABOVE HARD CEILINGS AS SHOWN ON
 ARCHITECTURAL RCP PLANS. PLEASE NOTE THAT THE PANELS
 SHALL BE CONSTRUCTED WITH NON-COMBUSTIBLE MATERIALS
 WHERE INSTALLED IN ABOVE-CEILING PLENUM SPACES, AND
 MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED.
  
 26) ACKNOWLEDGED THAN MANUFACTURER'S SPECIFICATIONS FOR
 THE GENERATOR SHALL BE A DEFERRED SUBMITTAL WITH
 APPROVAL STAMP BY THE EOR. PLEASE NOTE THE GENERATOR
 SHALL MEET THE REQUIREMENTS OF UL 2200- SECTION 915.1
 FBC-17 MECHANICAL.
  
 26) SHEET 401: PLEASE PROVIDE NOTES AND/OR DIMENSIONS
 TO VERIFY ALL REQUIRED CLEARANCES FOR THE RADIATOR AND
 ENGINE EXHAUST TERMINATIONS ARE IN COMPLIANCE WITH
 SECTION 501.3.1 (2).
  
 31 & 32) THE ENGINEER HAS INDICATED IN HIS RESPONSE
 THAT THE FOLLOWING LIST OF MECHANCIAL EQUIPMENT AND
 COMPONENTS ETC. SHALL BE DEFERRED SUBMITTALS:
 A) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR THE LOUVERS, AC STANDS, WALL BRACKETS, DUCT AND
 PIPE STANDS AND BRACKETS.
 B) MANUFACTURER'S SPECIFICATIONS FOR THE SMOKE CONTROL
 FANS, MOTORIZED DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE
 DETECTORS, BOILERS AND WATER HEATERS, GENERATOR,
 DRYERS, COOKING APPLIANCES, PLENUM-RATED ACCESS PANELS,
 FIRE WRAPPING, FIRESTOPPING AND FIRE CAULKING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-26 Cont ID  
Sent By ccole Date 2018-02-26 Time 15:42 Rev Time 0.00
Received By ccole Date 2018-02-23 Time 09:00 Sent To  
Notes
2018-02-26 15:42:421ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18020254
 2/23/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ELECTRONIC SIGNATURES ARE REQUIRED ON THE MECHANICAL
 PLANS, AND THE FOLLOWING LIST OF DOCUMENTS: ENERGYGAUGE
 COMPLIANCE FORM, THE AC LOAD CALCULATIONS, AND THE
 VENTILATION CALCULATIONS- SECTIONS 61G15-23.002 AND
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 2) THE ENERGYGAUGE REPORT IS MISSING COMPLIANCE DATA
 FOR OAU- 1 & 2, AND WSHP 1-3. TO HELP EXPEDITE THE
 REVIEW, PLEASE IDENTIFY THE OTHER SYSTEMS IN THE REPORT
 SO THEY MATCH THE IDENTIFICATIONS IN THE SCHEDULES ON
 SHEET M-601.
  
 3) AC CALCULATIONS: PLEASE CLARIFY WHY NO OUTDOOR
 VENTILATION DATA IS PROVIDED, AND WHY THE O/A DB/WB LOW
 TEMPS FOR THE COMMON AREAS AND KITCHEN ARE NOT
 CONSISTENT WITH ASHRAE 183 OR ACCA MANUAL N.
  
 4) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH C407
 FBC-17 ENERGY CONSERVATION. PLEASE NOTE THE HOTEL ROOM
 AC SYSTEMS ARE EXEMPT FROM THE REPORT.
  
 5) PLEASE REFER TO BUILDING REVIEW COMMENT # 2C: THE
 TWO PRESSURIZED INTERIOR EXIT STAIRWAYS #111 AND 114
 ARE EXITING INTO COMMON CORRIDORS AND NOT INTO EXIT
 DISCHARGES OR EXIT PASSAGEWAYS AS REQUIRED BY SECTIONS
 1023.2 AND 1023.11.1 FBC-17 BUILDING. IN ORDER FOR THE
 EXISTING MEANS OF EGRESS SYSTEM TO BE IN COMPLIANCE
 WITH THE CURRENT CODES, THE GROUND FLOOR CORRIDORS THAT
 ARE FORMING THE PATHS OF TRAVEL TO THE EXTERIOR OF THE
 BUILDING, MAY HAVE TO BE RE- CONSTRUCTED AS EXIT
 PASSAGEWAYS AND BECOME EXTENSIONS OF THE SMOKEPROOF
 ENCLOSURES- STAIRWAYS #111 AND 114. IN ADDITION THE
 PASSAGEWAYS SHALL BE PRESSURIZED EQUALLY TO THE
 PRESSURIZATION RATES PROVIDED FOR THE STAIRWAYS.
 CURRENTLY THERE IS NO SMOKE CONTROL RATIONAL ANALYSIS
 PROVIDED FOR THE PROPOSED PROJECT TO VERIFY THE CURRENT
 SYSTEM DESIGN WILL PROVIDE A TENABLE ENVIRONMENT FOR
 THE EVACUATION AND RELOCATION OF THE OCCUPANTS. PLEASE
 REVIEW SECTION 513 IN ENTIRETY AND PROVIDE A RATIONAL
 ANALYSIS REPORT THAT ENCOMPASSES ALL COMPLIANCES AS
 OUTLINED IN THE SUB-SECTIONS. ALL MECHANICAL COMPONENTS
 AND EQUIPMENT SUCH AS FANS, DUCTS, DAMPERS ETC. SHALL
 CORRESPOND WITH THE SPECIFICATIONS LISTED IN THE
 REPORT. THE REPORT SHALL INCLUDE, BUT NOT BE LIMITED TO
 THE FOLLOWING REQUIREMENTS LISTED IN SECTION 513.
  
 513.6 PRESSURIZATION METHOD.
 THE PRIMARY MECHANICAL MEANS OF CONTROLLING SMOKE SHALL
 BE BY PRESSURE DIFFERENCES ACROSS SMOKE BARRIERS.
 MAINTENANCE OF A TENABLE ENVIRONMENT IS NOT REQUIRED IN
 THE SMOKE CONTROL ZONE OF FIRE ORIGIN.
 513.6.1 MINIMUM PRESSURE DIFFERENCE.
 THE MINIMUM PRESSURE DIFFERENCE ACROSS A SMOKE BARRIER
 SHALL BE 0.05-INCH WATER GAGE (12.4 PA) IN FULLY
 SPRINKLERED BUILDINGS.
 IN BUILDINGS PERMITTED TO BE OTHER THAN FULLY
 SPRINKLERED, THE SMOKE CONTROL SYSTEM SHALL BE DESIGNED
 TO ACHIEVE PRESSURE DIFFERENCES NOT LESS THAN TWO TIMES
 THE MAXIMUM CALCULATED PRESSURE DIFFERENCE PRODUCED BY
 THE DESIGN FIRE.
 513.6.2 MAXIMUM PRESSURE DIFFERENCE.
 THE MAXIMUM AIR PRESSURE DIFFERENCE ACROSS A SMOKE
 BARRIER SHALL BE DETERMINED BY REQUIRED DOOR-OPENING OR
 CLOSING FORCES. THE ACTUAL FORCE REQUIRED TO OPEN EXIT
 DOORS WHEN THE SYSTEM IS IN THE SMOKE CONTROL MODE
 SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING. OPENING AND CLOSING FORCES FOR OTHER DOORS
 SHALL BE DETERMINED BY STANDARD ENGINEERING METHODS FOR
 THE RESOLUTION OF FORCES AND REACTIONS. THE CALCULATED
 FORCE TO SET A SIDE-HINGED, SWINGING DOOR IN MOTION
 SHALL BE DETERMINED BY:
 (EQUATION 5-1)
 WHERE:
 A = DOOR AREA, SQUARE FEET (M2).
 D = DISTANCE FROM DOOR HANDLE TO LATCH EDGE OF DOOR,
 FEET (M).
 F = TOTAL DOOR OPENING FORCE, POUNDS (N).
 FDC = FORCE REQUIRED TO OVERCOME CLOSING DEVICE, POUNDS
 (N).
 K = COEFFICIENT 5.2 (1.0).
 W = DOOR WIDTH, FEET (M).
 P = DESIGN PRESSURE DIFFERENCE, INCHES (PA) WATER GAGE.
  
 513.6.3 PRESSURIZED STAIRWAYS AND ELEVATOR HOISTWAYS.
 WHERE STAIRWAYS OR ELEVATOR HOISTWAYS ARE PRESSURIZED,
 SUCH PRESSURIZATION SYSTEMS SHALL COMPLY WITH SECTION
 513 AS SMOKE CONTROL SYSTEMS, IN ADDITION TO THE
 REQUIREMENTS OF SECTIONS 909.20 OF THE FLORIDA BUILDING
 CODE, BUILDING AND THE FLORIDA FIRE PREVENTION CODE.
  
 513.10 EQUIPMENT.
 EQUIPMENT SUCH AS, BUT NOT LIMITED TO, FANS, DUCTS,
 AUTOMATIC DAMPERS AND BALANCE DAMPERS SHALL BE SUITABLE
 FOR THEIR INTENDED USE, SUITABLE FOR THE PROBABLE
 EXPOSURE TEMPERATURES THAT THE RATIONAL ANALYSIS
 INDICATES, AND AS APPROVED BY THE CODE OFFICIAL.
  
 513.10.1 EXHAUST FANS.
 COMPONENTS OF EXHAUST FANS SHALL BE RATED AND CERTIFIED
 BY THE MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE
 TO WHICH THE COMPONENTS WILL BE EXPOSED. THIS
 TEMPERATURE RISE SHALL BE COMPUTED BY:
  
 (EQUATION 5-2)
 WHERE:
 C = SPECIFIC HEAT OF SMOKE AT SMOKE-LAYER TEMPERATURE,
 BTU/LB F (KJ/KG K).
 M = EXHAUST RATE, POUNDS PER SECOND (KG/S).
 QC = CONVECTIVE HEAT OUTPUT OF FIRE, BTU/S (KW).
 TA = AMBIENT TEMPERATURE, F (K).
 TS = SMOKE TEMPERATURE, F (K).
 EXCEPTION: REDUCED TS AS CALCULATED BASED ON THE
 ASSURANCE OF ADEQUATE DILUTION AIR.
  
 513.10.2 DUCTS.
 DUCT MATERIALS AND JOINTS SHALL BE CAPABLE OF
 WITHSTANDING THE PROBABLE TEMPERATURES AND PRESSURES TO
 WHICH THEY ARE EXPOSED AS DETERMINED IN ACCORDANCE WITH
 SECTION 513.10.1. DUCTS SHALL BE CONSTRUCTED AND
 SUPPORTED IN ACCORDANCE WITH CHAPTER 6. DUCTS SHALL BE
 LEAK TESTED TO 1.5 TIMES THE MAXIMUM DESIGN PRESSURE IN
 ACCORDANCE WITH NATIONALLY ACCEPTED PRACTICES. MEASURED
 LEAKAGE SHALL NOT EXCEED 5 PERCENT OF DESIGN FLOW.
 RESULTS OF SUCH TESTING SHALL BE A PART OF THE
 DOCUMENTATION PROCEDURE. DUCTS SHALL BE SUPPORTED
 DIRECTLY FROM FIRE-RESISTANCE-RATED STRUCTURAL ELEMENTS
 OF THE BUILDING BY SUBSTANTIAL, NONCOMBUSTIBLE
 SUPPORTS.
 EXCEPTION: FLEXIBLE CONNECTIONS, FOR THE PURPOSE OF
 VIBRATION ISOLATION, THAT ARE CONSTRUCTED OF APPROVED
 FIRE-RESISTANCE-RATED MATERIALS.
  
 513.10.3 EQUIPMENT, INLETS AND OUTLETS.
 EQUIPMENT SHALL BE LOCATED SO AS TO NOT EXPOSE
 UNINVOLVED PORTIONS OF THE BUILDING TO AN ADDITIONAL
 FIRE HAZARD. OUTDOOR AIR INLETS SHALL BE LOCATED SO AS
 TO MINIMIZE THE POTENTIAL FOR INTRODUCING SMOKE OR
 FLAME INTO THE BUILDING. EXHAUST OUTLETS SHALL BE SO
 LOCATED AS TO MINIMIZE REINTRODUCTION OF SMOKE INTO THE
 BUILDING AND TO LIMIT EXPOSURE OF THE BUILDING OR
 ADJACENT BUILDINGS TO AN ADDITIONAL FIRE HAZARD.
  
 513.10.4 AUTOMATIC DAMPERS.
 AUTOMATIC DAMPERS, REGARDLESS OF THE PURPOSE FOR WHICH
 THEY ARE INSTALLED WITHIN THE SMOKE CONTROL SYSTEM,
 SHALL BE LISTED AND CONFORM TO THE REQUIREMENTS OF
 APPROVED RECOGNIZED STANDARDS.
  
 513.10.5 FANS.
 IN ADDITION TO OTHER REQUIREMENTS, BELT-DRIVEN FANS
 SHALL HAVE 1.5 TIMES THE NUMBER OF BELTS REQUIRED FOR
 THE DESIGN DUTY WITH THE MINIMUM NUMBER OF BELTS BEING
 TWO. FANS SHALL BE SELECTED FOR STABLE PERFORMANCE
 BASED ON NORMAL TEMPERATURE AND, WHERE APPLICABLE,
 ELEVATED TEMPERATURE. CALCULATIONS AND MANUFACTURER?S
 FAN CURVES SHALL BE PART OF THE DOCUMENTATION
 PROCEDURES. FANS SHALL BE SUPPORTED AND RESTRAINED BY
 NONCOMBUSTIBLE DEVICES IN ACCORDANCE WITH THE
 STRUCTURAL DESIGN REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING. MOTORS DRIVING FANS SHALL NOT BE
 OPERATING BEYOND THEIR NAMEPLATE HORSEPOWER (KILOWATTS)
 AS DETERMINED FROM MEASUREMENT OF ACTUAL CURRENT DRAW.
 MOTORS DRIVING FANS SHALL HAVE A MINIMUM SERVICE FACTOR
 OF 1.15.
  
 513.11 STANDBY POWER.
 THE SMOKE CONTROL SYSTEM SHALL BE SUPPLIED WITH STANDBY
 POWER IN ACCORDANCE WITH SECTION 2702 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 513.11.1 EQUIPMENT ROOM.
 THE STANDBY POWER SOURCE AND ITS TRANSFER SWITCHES
 SHALL BE IN A ROOM SEPARATE FROM THE NORMAL POWER
 TRANSFORMERS AND SWITCH GEAR AND VENTILATED DIRECTLY TO
 AND FROM THE EXTERIOR. THE ROOM SHALL BE ENCLOSED WITH
 NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OF
 THE FLORIDA BUILDING CODE, BUILDING OR HORIZONTAL
 ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711
 OF THE FLORIDA BUILDING CODE, BUILDING, OR BOTH.
  
 513.11.2 POWER SOURCES AND POWER SURGES.
 ELEMENTS OF THE SMOKE MANAGEMENT SYSTEM RELYING ON
 VOLATILE MEMORIES OR THE LIKE SHALL BE SUPPLIED WITH
 UNINTERRUPTIBLE POWER SOURCES OF SUFFICIENT DURATION TO
 SPAN 15-MINUTE PRIMARY POWER INTERRUPTION. ELEMENTS OF
 THE SMOKE MANAGEMENT SYSTEM SUSCEPTIBLE TO POWER SURGES
 SHALL BE SUITABLY PROTECTED BY CONDITIONERS,
 SUPPRESSORS OR OTHER APPROVED MEANS.
  
 513.12 DETECTION AND CONTROL SYSTEMS.
 FIRE DETECTION SYSTEMS PROVIDING CONTROL INPUT OR
 OUTPUT SIGNALS TO MECHANICAL SMOKE CONTROL SYSTEMS OR
 ELEMENTS THEREOF SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 907 OF THE FLORIDA BUILDING CODE, BUILDING.
 SUCH SYSTEMS SHALL BE EQUIPPED WITH A CONTROL UNIT
 COMPLYING WITH UL 864 AND LISTED AS SMOKE CONTROL
 EQUIPMENT.
  
 6) PLEASE PROVIDE STAIR AND ELEVATOR PRESSURIZATION
 RISER DRAWINGS SHOWING THE LOCATIONS OF BAROMETRIC
 RELIEF DAMPS AND HOISTWAY VENTS.
  
 7) CONCERNING SECTION 513.11.1 LISTED ABOVE, PLEASE
 SHOW THE LOCATION OF THE GENERATOR TRANSFER SWITCHES.
  
 8) SHEET M-106: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD, FIRE SUPPRESSION SYSTEM, AND WALK IN
 COOLER AND FREEZER, HOWEVER AN AIR BALANCE CALCULATION
 IS REQUIRED PER SECTION 508.1.2:
 508.1.2AIR BALANCE.
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION.
  
 9) M-106: AS STATED IN THE PREVIOUS COMMENT, A SEPARATE
 PERMIT IS REQUIRED FOR THE KITCHEN HOOD AND EXHAUST
 SYSTEM, HOWEVER IT IS IMPORTANT TO NOTE AT THIS TIME OF
 THE MAIN PERMIT AND PLANS THAT COMPLIANCE WITH SECTION
 C403.2.8 FBC-17 ENERGY CONSERVATION IS REQUIRED.
 C403.2.8 KITCHEN EXHAUST SYSTEMS
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
 1. THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
 2. THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1. NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR
 SHALL BE TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED.
 2. DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
 3. LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED.
  
 10) M-101: VERIFY THAT EXHAUST HOOD GREASE DUCT IS NOT
 TERMINATING ABOVE A WALKWAY OR ANYPLACE THAT COULD
 CREATE A PUBLIC NUISANCE OR FIRE HAZARD- SECTION
 506.3.13.2. PROVIDE THE HEIGHT OF THE OUTLET ABOVE THE
 ADJOINING GRADE.
  
 11) M-101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY TRUNKS OF WSHP-1-1 AND WSHP-1-4 PER SECTION
 606.2.1. PLEASE NOTE AN EXEMPTION CAN BE APPLIED TO 1-4
 IF MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 12) M-101 & M-102: THE OUTSIDE AIR DUCT DOES NOT APPEAR
 TO BE MAKING DIRECT CONNECTIONS TO WSHP-1-5, 1-6, AND
 1-7- PLEASE CLARIFY.
  
 13) M-101: PLEASE CLARIFY HOW SUPPLY AIR TO THE LOBBY,
 MARKET PLACE, RECEPTION AREAS ETC. IS BEING RETURNED TO
 WSHP-1-3- SECTION 601.6.
  
 14) M-101: PROVIDE DRYER EXHAUST PLANS AND DETAILS PER
 SECTION 504, AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE DRYERS REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD.
  
 15) M-101: THE LAUNDRY SERVICE ROOM IS MISLABELED AS
 THE CHEF'S OFFICE.
  
 16) M-101: PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL
 GAS-FIRED KITCHEN COOKING APPLIANCES AND SUBMIT
 EQUIPMENT CUT SHEETS REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD- SECTIONS 304 AND 623.1 FBC-17 FUEL
 GAS. PLEASE NOTE THERE DOES NOT APPEAR TO BE FOOD
 SERVICE PLANS INCLUDED IN THE SETS- PLEASE PROVIDE
 THEM.
  
 17) M-102: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY TRUNK OF WSHP-2-2 PER SECTION 606.2.1.
  
 18) M-102: FIRE DAMPERS NOT SHOWN AT A) THE O/A AND E/A
 DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM
 WALLS. B) THE S/A DUCT PENETRATION THROUGH THE
 FIRE-RATED WALL AT ROOM 226/227. C) THE 8" E/A DUCT
 PENETRATION THROUGH THE FIRE-RATED 227/231 WALL-
 SECTION 607.5.2 & 607.5.3
  
 19) M-102: INDICATE HOW ACCESS FOR SERVICE AND
 REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL
 CEILINGS WILL BE PROVIDED- SECTION 306.
  
 20) M-102: SHOW HOW SUPPLY AIR FROM WSHP-2-2 AND
 WSHP-C-2 IS BEING RETURNED INTO THE MECHANICAL ROOM-
 SECTION 601.6.
  
 21) M-103: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A
 DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM
 WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-3
 PENETRATING THE FIRE-RATED 323/324/325 WALLS.- SECTION
 607.5.2 & 607.5.3
  
 22) M-103: INDICATE HOW ACCESS FOR SERVICE AND
 REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL
 CEILINGS WILL BE PROVIDED- SECTION 306.
  
 23) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-3 IS BEING
 RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6.
  
 24) M-104: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A
 DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM
 WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-10
 PENETRATING THE FIRE-RATED 1023/1025 WALLS- SECTION
 607.5.2 & 607.5.3
  
 25) M-103: INDICATE HOW ACCESS FOR SERVICE AND
 REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL
 CEILINGS WILL BE PROVIDED- SECTION 306.
  
 26) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-10 IS BEING
 RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6.
  
 27) M-401: PROVIDE AN ENLARGED PLAN OF THE GENERATOR
 THAT PROVIDES DETAILS FOR THE ENGINE AND RADIATOR
 EXHAUST SYSTEMS, AND THE ROOM VENTILATION. CLARIFY IF
 THE GENERATOR HAS A BELLY TANK FOR DIESEL FUEL OR IF
 THERE IS TO BE A SEPARATE TANK AND TANK ROOM PROVIDED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD.
  
 28) M-501: PROVIDE WSHP INSTALLATION DETAILS.
  
 29) M-502: THE RTU ATTACHMENT DETAIL TO THE CURB IS FOR
 A CARRIER UNIT, HOWEVER THE SYSTEMS SELECTED ARE TRANE-
 PLEASE CORRECT.
  
 30) M-601: PLEASE PROVIDE COMPLETE WINDLOAD ENGINEERING
 FOR INSTALLATION OF THE OAU'S, THE ROOF AND WALL FANS,
 THE ROOFTOP DUCTWORK, AND THE WATER PIPING. PLEASE
 INCLUDE THE WIND LOAD DESIGN CRITERIA AND DETAILS FOR
 ATTACHING THE CURBS AND BRACKETS TO THE ROOF STRUCTURE,
 AND THE UNITS TO THE CURBS AND BRACKETS- SECTION
 301.15.
  
 31) PROVIDE A CONDENSATE DISPOSAL PLAN AND RISER
 DRAWING- SECTION 307.
  
 32) PROVIDE FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR ALL EXTERIOR EXHAUST AND O/A INLET LOUVERS,
 AC STANDS AND WALL BRACKETS, DUCT AND PIPE STANDS AND
 BRACKETS- RULE 9N-03 FAC.
  
 32) REQUIRED SUBMITTALS TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD: PRODUCT APPROVALS AND NOA?S,
 SMOKE CONTROL FANS, FIRE AND FIRE/SMOKE DAMPERS,
 MOTORIZED DAMPERS, DUCT SMOKE DETECTORS, BOILER AND
 WATER HEATERS, COOKING APPLIANCES, PLENUM RATED ACCESS
 PANELS FOR ABOVE CEILING HEAT PUMPS AND FANS,
 GENERATOR, FIRE CAULKING AND FIRE WRAPPING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-04 Cont ID  
Sent By gjohnson Date 2018-05-04 Time 12:19 Rev Time 0.00
Received By gjohnson Date 2018-05-04 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-16 Cont ID  
Sent By gjohnson Date 2018-04-16 Time 15:30 Rev Time 0.00
Received By gjohnson Date 2018-04-13 Time 09:16 Sent To  
Notes
2018-04-16 16:04:152ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED WITH.
  
 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL.
 PER WPB AMEND TO FBC 107.2.1
 DESIGN MANUAL WAS NOT IN SUBMITTAL PLEASE DOWN LOAD
 MANUAL UNDER SUPPORTING DOCUMENTS
  
 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE
 (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER
 FBC PL 316.1.3 AND 919.1
 PLEASE PROVIDE DOCUMENTATION FROM THE MANUFACTURE
 STATING THEY REVIEWED AND APPROVED YOUR DESIGN.
  
 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE
 SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US
 FOOD CODE CH 5 AND FBC EX 1010.2
 COULD NOT LOCATE NOTE ON PLAN PLEASE PROVIDE SHEET
 NUMBER SHOULD BE LOCATED ON BOTH ISOMETRIC AND FLOOR
 PLAN AND AND PROVIDE DETAIL OF WHAT TYPE OF SHIELDING
 OR PAN WILL BE USED.
  
 NEW COMMENT:
 1. SHT. 702 SHOWS THE CONDENSATE RECOVERY PUMP
 DISCHARGING INTO THE SANITARY ALL CONDENSATE SHALL
 DISCHARGE TO STORM OR TO PERMEABLE GROUND IT IS
 PROHIBITED TO DISCHARGE TO THE SANITARY. PER CITY OF
 WPB CODE OF ORDINANCE SEC. 90-126. (5)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-12 Cont ID  
Sent By gjohnson Date 2018-03-12 Time 11:57 Rev Time 0.00
Received By gjohnson Date 2018-03-08 Time 14:56 Sent To  
Notes
2018-03-12 12:03:061ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN
 WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON
 THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS
 CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED
 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT
 SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB
 AMEND TO FBC 107.2.1
  
 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD
 CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT
 CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED.
 PER FBC PL 1108.1
  
 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB
 BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE
 GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN.
 OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE
 CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER
 FBC ACC 604.5.1
  
 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH
 DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL
 405.3.1
  
 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB
 BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN
 MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS
 WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL
 DETAILS. PER FBC ACC 609.4
  
 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM
 OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34
 MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3
  
 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1
  
 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE
 WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3
  
 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER
 CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1
  
 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR
 ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54?
 OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL
 DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC
 604.5.1
  
 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE
 SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF
 THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE
 CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT
 BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC
 609.4
  
 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING
 KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3
  
 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON
 BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE
 ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM
 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1?
 WALL THICKNESS. PER FBC ENERGY C404.4
  
 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS
 BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE
 COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK
 IT SHALL CONNECT TO INTAKE OF THE BOILER. PER
 MANUFACTURE INSTALL GUIDE
  
 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL.
 PER WPB AMEND TO FBC 107.2.1
  
 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE
 (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER
 FBC PL 316.1.3
  
 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER
 ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON
 THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. PER FBC PL 1003.2
  
 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON
 BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS
 DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM
 CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE
 ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK.
  
 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC
 IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE
 SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS
 TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN
 AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY
 ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO
 DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW
 PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO
 MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON
 THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701,
 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO
 DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW
 PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO
 MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER
 DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT
 AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC
 VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1
  
 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6
  
 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE
 SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US
 FOOD CODE
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected] REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN
 WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON
 THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS
 CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED
 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT
 SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB
 AMEND TO FBC 107.2.1
  
 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD
 CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT
 CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED.
 PER FBC PL 1108.1
  
 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB
 BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE
 GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN.
 OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE
 CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER
 FBC ACC 604.5.1
  
 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH
 DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL
 405.3.1
  
 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB
 BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN
 MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS
 WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL
 DETAILS. PER FBC ACC 609.4
  
 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM
 OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34
 MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3
  
 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1
  
 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE
 WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3
  
 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER
 CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1
  
 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR
 ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54?
 OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL
 DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC
 604.5.1
  
 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE
 SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF
 THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE
 CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT
 BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC
 609.4
  
 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING
 KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3
  
 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON
 BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE
 ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM
 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1?
 WALL THICKNESS. PER FBC ENERGY C404.4
  
 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS
 BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE
 COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK
 IT SHALL CONNECT TO INTAKE OF THE BOILER. PER
 MANUFACTURE INSTALL GUIDE
  
 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL.
 PER WPB AMEND TO FBC 107.2.1
  
 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE
 (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER
 FBC PL 316.1.3
  
 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER
 ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON
 THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. PER FBC PL 1003.2
  
 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON
 BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS
 DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM
 CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE
 ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK.
  
 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC
 IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE
 SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS
 TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN
 AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY
 ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO
 DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW
 PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO
 MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON
 THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701,
 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO
 DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW
 PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO
 MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER
 DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT
 AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC
 VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1
  
 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6
  
 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE
 SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US
 FOOD CODE
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-05-17 Cont ID  
Sent By shill Date 2018-05-17 Time 11:48 Rev Time 0.00
Received By shill Date 2018-05-17 Time 11:48 Sent To  
Notes
2018-05-17 11:48:59****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CIVIL SHEETS ARE NOT DIGITALLY SIGNED AND SEALED.
 PAPER ORIGINALS MAY BE PROVIDED TO RESOLVE THIS ISSUE.
  
 2. FMEP SHEETS HAVE A SIGNATURE FROM DOCUSIGN. AS
 DISCUSSED WITH BEN ELLIS, PE, WE ARE WAITING FOR A
 REPLY FROM FBPE. THEY WILL ADVISE AS TO WHETHER OR NOT
 THIS MEETS THE REQUIREMENT FOR DIGITAL SIGNATURE AND
 SEAL. AS DISCUSSED, IF THEY DETERMINE THAT IT DOES NOT,
 A PAPER ORIGINAL CAN SERVE AS A SIGNATURE DOCUMENT.
  
 IF WE DO NOT RECEIVE A RESPONSE FROM FBPE, A PAPER
 ORIGINAL IS REQUIRED FOR ALL FMEP SHEETS AND SUPPORTING
 DOCUMENTS.
  
 3. ALL OTHER SHEETS ARE DIGITALLY SIGNED AND SEALED IN
 ACCORDANCE WITH FLORIDA STATUTE 471, 481.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-05-08 Cont ID  
Sent By shill Date 2018-05-08 Time 17:45 Rev Time 0.00
Received By shill Date 2018-05-08 Time 17:37 Sent To  
Notes
2018-05-08 17:45:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CIVIL SHEETS ARE NOT DIGITALLY SIGNED AND SEALED.
 PAPER ORIGINALS MAY BE PROVIDED TO RESOLVE THIS ISSUE.
  
 2. FMEP SHEETS HAVE A SIGNATURE FROM DOCUSIGN. AS
 DISCUSSED WITH BEN ELLIS, PE, WE ARE WAITING FOR A
 REPLY FROM FBPE. THEY WILL ADVISE AS TO WHETHER OR NOT
 THIS MEETS THE REQUIREMENT FOR DIGITAL SIGNATURE AND
 SEAL. AS DISCUSSED, IF THEY DETERMINE THAT IT DOES NOT,
 A PAPER ORIGINAL CAN SERVE AS A SIGNATURE DOCUMENT.
  
 IF WE DO NOT RECEIVE A RESPONSE FROM FBPE, A PAPER
 ORIGINAL IS REQUIRED FOR ALL FMEP SHEETS AND SUPPORTING
 DOCUMENTS.
  
 3. ALL OTHER SHEETS ARE DIGITALLY SIGNED AND SEALED IN
 ACCORDANCE WITH FLORIDA STATUTE 471, 481.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-04-13 Cont ID  
Sent By shill Date 2018-04-13 Time 11:58 Rev Time 0.00
Received By shill Date 2018-04-13 Time 11:53 Sent To  
Notes
2018-04-13 11:56:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CIVIL SHEETS ARE NOT DIGITALLY SIGNED AND SEALED.
 PAPER ORIGINALS MAY BE PROVIDED TO RESOLVE THIS ISSUE.
  
 2. FMEP SHEETS HAVE A SIGNATURE FROM DOCUSIGN. AS
 DISCUSSED WITH BEN ELLIS, PE, WE ARE WAITING FOR A
 REPLY FROM FBPE. THEY WILL ADVISE AS TO WHETHER OR NOT
 THIS MEETS THE REQUIREMENT FOR DIGITAL SIGNATURE AND
 SEAL. AS DISCUSSED, IF THEY DETERMINE THAT IT DOES NOT,
 A PAPER ORIGINAL CAN SERVE AS A SIGNATURE DOCUMENT.
  
 3. ALL OTHER SHEETS ARE DIGITALLY SIGNED AND SEALED IN
 ACCORDANCE WITH FLORIDA STATUTE 471, 481.
  
  
  
  
2018-02-26 15:52:37MECHANICAL PLANS AND SUBMITTAL DOCUMENTS NOT
 ELECTROCNICALLY SIGNED AND SEALED.
 CCOLE- 2/26/18

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By shill Date 2018-05-11 Time 07:43 Rev Time 0.00
Received By shill Date 2018-05-11 Time 07:43 Sent To  
Notes
2018-05-11 07:49:36SPECIAL INSPECTOR AGREEMENT ORIGINAL RECEIVED
 GFA INTERNATIONAL
 HECTOR VERGARA, PE25764, SI0283
 NOEL WOODALL, BN2505
 CARLTON CROOK, BN3909
 MARK SHARMAN, BN4742
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-04-04 Cont ID  
Sent By jwitmer Date 2018-04-04 Time 08:23 Rev Time 0.00
Received By jwitmer Date 2018-04-04 Time 08:23 Sent To  
Notes
2018-04-04 08:23:312017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020254
 ADD: 1675 PALM BEACH LAKES BLVD.
 CONT: STRATICON LLC
 TEL: 772-210-0200 STRATICON
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: WED. APRIL 04/ 2018
 ACTION: DENIED
  
 1) 2ND REQUEST. THRESHOLD BUILDING / FL S. S. 553.71(7)
 ?THRESHOLD BUILDING".
 THE RESPONSE IS THAT THE THRESHOLD DOCUMENTS WERE
 SUBMITTED UNDER THE BUCK HOIST PERMIT. PLEASE NOTE THE
 SUBMITTED FORMS DATED MARCH 29, 2017 WERE NOT COMPLETE
 IN REQUIRED SIGNATURES.
 THE CERTIFIED INSPECTION CO. LINE IS LEFT BLANK, NO
 NOTARY WORK, CONTRACTOR SIGNATURE WITH NO NOTARY WORK,
 MISSING THE ARCHITECT AND ENGINEERS SIGNATURE AND SEAL
 AND NOTARY WORK, YOU SHOULD UPDATE YOUR SITE INSPECTOR
 INFORMATION WHO IS STILL WITH THE COMPANY, MIKE ADAIR
 IS NOW A CITY INSPECTOR.
  
  
 THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. PLEASE
 UPDATE FILES SINCE THEIR MAYBE ADDITIONAL PERSONNEL TO
 ACT AS THE JOBSITE INSPECTOR.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A)2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
  
 1C)COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2018-02-22 Cont ID  
Sent By jwitmer Date 2018-02-22 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2018-02-22 Time 10:11 Sent To  
Notes
2018-02-22 10:37:32DATE: 02/22/2018
 ORIGINAL DOCUMENTATION THRESHOLD INSPECTION FORMS GIVEN
 TO CAROLINE PUELL FOR DIGITAL PLANS.
 SPECIAL INSPECTION PLANS IN STRUCTURAL DRAWINGS, SHEET
 S.1.02.
 COPY OF DOCUMENTS GIVEN TO KEN CONRAD.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-04-18 Cont ID  
Sent By ajones Date 2018-04-18 Time 15:58 Rev Time 0.00
Received By ajones Date 2018-04-18 Time 15:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-03-12 Cont ID  
Sent By AV Date 2018-03-12 Time 17:02 Rev Time 0.00
Received By ajones Date 2018-03-12 Time 17:02 Sent To  
Notes
2018-03-12 17:10:403/12/18- APPROVED WITH THE PROVISO THAT A SEPERATE
 PERMIT IS REQUIRED FOR THE FOLLOWING:
  
 1. A SEPARATE PERMIT IS REQUIRED FOR LANDSCAPING,
 SIGNAGE, SWIMMING POOL, FENCES/WALLS, DUMPSTER
 ENCLOSURE.
 2. A SEPARATE PERMIT IS REQUIRED FOR THE SHORT TERM
 PARKING IN THE EXISTING GARAGE.
  
 ANGELLA VA
  
  