Plan Review Details - Permit 18020238
Plan Review Stops For Permit 18020238
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-02-13 Cont ID  
Sent By jwitmer Date 2018-02-13 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2018-02-13 Time 13:42 Sent To  
Notes
2018-02-13 14:50:09PERMIT DATA:
 OCCUPANCY: B
 BLDG TYPE:II-B
 SQ. FT. 1737 SQ. FT.
 OCC. LOAD 18
 RESTROOM CT. 0

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-04-23 Cont ID  
Sent By jpearson Date 2018-04-23 Time 13:28 Rev Time 0.00
Received By jpearson Date 2018-04-23 Time 13:28 Sent To I
Notes
2018-04-23 13:28:17CHANGED PERMIT VALUE TO $95,535 FROM $20,000 PER
 CONTRACT PROVIDED AND APPROVED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-03-20 Cont ID  
Sent By jpearson Date 2018-03-20 Time 16:42 Rev Time 0.00
Received By jpearson Date 2018-03-20 Time 16:42 Sent To I
Notes
2018-03-20 16:18:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES AND NEED TO BE
 CORRECTED.
  
 1. CORRECTED.
 2. CORRECTED.
 3. VALUE STATED ON APPLICATION APPEARS LOW. PROVIDE
 COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK,
 TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 (NOT
 PROVIDED)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-23 Cont ID  
Sent By jpearson Date 2018-02-23 Time 11:49 Rev Time 0.00
Received By jpearson Date 2018-02-23 Time 11:49 Sent To  
Notes
2018-02-23 11:49:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. VALUE STATED ON APPLICATION APPEARS LOW. PROVIDE
 COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK,
 TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-13 Cont ID  
Sent By pleduc Date 2018-02-13 Time   Rev Time 0.00
Received By pleduc Date 2018-02-12 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-04-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-13 Time 12:59 Sent To  
Notes
2018-04-16 12:59:22RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-16 Time 14:52 Sent To  
Notes
2018-03-19 14:52:20RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-02 Cont ID  
Sent By gjohnson Date 2018-03-02 Time 09:14 Rev Time 0.00
Received By gjohnson Date 2018-02-06 Time 14:32 Sent To  
Notes
2018-02-07 14:32:51B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-02-13 Cont ID  
Sent By jwitmer Date 2018-02-13 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2018-02-13 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-20 Cont ID  
Sent By ccole Date 2018-02-20 Time 13:02 Rev Time 0.00
Received By ccole Date 2018-02-20 Time 13:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-02 Cont ID  
Sent By gjohnson Date 2018-03-02 Time 09:14 Rev Time 0.00
Received By gjohnson Date 2018-03-02 Time 09:14 Sent To  
Notes
***NONE***