Plan Review Details - Permit 18020219
Plan Review Stops For Permit 18020219
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-02-26 Cont ID  
Sent By jwitmer Date 2018-02-26 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2018-02-26 Time 08:21 Sent To  
Notes
2018-02-26 13:30:132017 FBC
 CONSTRUCTION TYPE: I-A
 SUITE 200 2072 SQ. FT. 21 OCC. LOAD
 SUITE 202 1437 SQ. FT. 15 OCC. LOAD
 SUITE 203 1581 SQ. FT. 16 OCC. LOAD
 SUITE 204 1231 SQ. FT. 13 OCC. LOAD
 TOTAL SQ. FT. 6321 65 TOTAL OCC. LOAD
  
 BUSINESS OCCUPANCY
  
 SPRINKLERED/ YES
  
 RESTROOMS 2
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By jpearson Date 2018-03-23 Time 15:20 Rev Time 0.00
Received By jpearson Date 2018-03-23 Time 15:20 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 08:56 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 07:12 Sent To  
Notes
2018-03-16 08:56:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEED FROM DISCONNECT TO TRANSFORMER T1A IS SHOWN
 WITH FOUR 3/0 AND ONE #2 WIRE. THIS FEED SHOULD NOT
 INCLUDE A NEUTRAL CONDUCTOR (GROUNDED CONDUCTOR) AS
 THIS WOULD CREATE A POSSIBILITY OF OBJECTIONABLE
 CURRRENT. THIS FEED SHOULD HAVE ONLY THE THREE PHASE
 CONDUCTORS AND AN EQUIPMENT GROUNDING CONDUCTOR.
 PROVIDE CORRECTION. NEC 250.6, 250.30
 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-12 Cont ID  
Sent By pleduc Date 2018-02-12 Time   Rev Time 0.00
Received By pleduc Date 2018-02-12 Time 14:28 Sent To  
Notes
2018-02-12 15:28:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET T - THERE ARE INDICATIONS OF INCORRECT
 EDITIONS OF THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE ENSURE COMPLIANCE AND ADJUST YOUR RECORDS
 ACCORDINGLY.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-22 Time 14:49 Sent To  
Notes
2018-03-23 14:49:24RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 10:51 Rev Time 0.00
Received By gjohnson Date 2018-02-06 Time 14:27 Sent To  
Notes
2018-02-07 14:27:23C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-02-26 Cont ID  
Sent By jwitmer Date 2018-02-26 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2018-02-26 Time 13:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-08 Cont ID  
Sent By ccole Date 2018-02-08 Time 08:19 Rev Time 0.00
Received By ccole Date 2018-02-07 Time 17:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 10:50 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 08:58 Sent To  
Notes
***NONE***