Plan Review Details - Permit 18020210
Plan Review Stops For Permit 18020210
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-28 Cont ID  
Sent By aclange Date 2018-03-28 Time 10:04 Rev Time 0.00
Received By aclange Date 2018-03-28 Time 09:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 12:56 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 12:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By aclange Date 2018-02-14 Time 15:04 Rev Time 0.00
Received By aclange Date 2018-02-14 Time 14:30 Sent To  
Notes
2018-02-14 15:03:30****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. ONE SET OF PLANS NOT SIGNED AND SEALED BY WILLIAM
 TRACY ARCHITECT.
  
 61G1-16.001 ARCHITECTS AND INTERIOR DESIGNERS SEAL.
 EACH ARCHITECT AND INTERIOR DESIGNER SHALL ACQUIRE A
 SEAL WITH WHICH SHE OR HE SHALL IDENTIFY ALL PLANS,
 SPECIFICATIONS OR REPORTS PREPARED OR ISSUED BY HER OR
 HIM AND FILED FOR PUBLIC RECORD. THE SEAL SHALL BE
 CAPABLE OF LEAVING A PERMANENT INK REPRESENTATION OR
 OTHER FORM OF EMBOSSING OR OPAQUE AND PERMANENT
 IMPRESSION, WHICH ALSO MAY BE COMPUTER GENERATED
 IMPRESSIONS, ON THE SURFACE OF PRINTS OR OTHER
 DUPLICATIONS OF DRAWINGS, AND, AS APPROPRIATE, UPON
 SPECIFICATION PAGES, AND OTHER ARTICLES OF SERVICE.
 WHERE REQUIRED, ELECTRONIC FILES MAY BE SEALED IN
 ACCORDANCE WITH RULE 61G1-16.005, F.A.C.
  
 2. PROVIDE THE FLAME SPREAD INDEX FOR THE US FLOORS
 SOUND PROOFING THAT WILL BE USED.
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
  
 3. PROVIDE EXISTING AND NEW STUD SPACING AT SHOWER WALL
 LOCATIONS AND INCLUDE TYPE OF BOARD THAT WILL BE USED.
 NOTE: MANY CEMENT BOARD MANUFACTURERS REQUIRE A MINIMUM
 OF 16 INCHES ON CENTER FOR FRAMING.
 FBC 107.2.1
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-04-03 Cont ID  
Sent By ppetty Date 2018-04-03 Time 14:55 Rev Time 0.00
Received By ppetty Date 2018-04-03 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-03-22 Cont ID  
Sent By ppetty Date 2018-03-22 Time 13:07 Rev Time 0.00
Received By ppetty Date 2018-03-22 Time 13:07 Sent To P
Notes
2018-03-22 12:55:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. PLAN PROVIDED DOES NOT SHOW ALL WORK DESCRIBED IN
 ATTACHED CONTRACT. SHOW ALL ELECTRICAL WORK ON PLAN.
 FBC 107.2.1, 107.3.5 (NOT CORRECTED)
 5. PROVIDE PANEL SCHEDULE INDICATING SIZE OF PANEL, ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4(NOT ALL CIRCUITS SHOWN)
 6. PROVIDE LOAD CALCULATION FOR SERVICE AND FOR
 INDIVIDUAL UNIT, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30 (CALCULATION PROVIDED IS NOT PER CODE,
 INCLUDE LOAD FOR TANKLESS WATER HEATER. ALSO PROVIDE
 LOAD CALC FOR BUILDING SERVICE TO CONFIRM THAT THE
 EXISTING SERVICE IS ADEQUATE FOR ADDITION OF TANKLESS
 LOAD.)
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-26 Cont ID  
Sent By jpearson Date 2018-02-26 Time 12:38 Rev Time 0.00
Received By jpearson Date 2018-02-26 Time 09:46 Sent To  
Notes
2018-02-26 12:38:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IN NOTE 4 AND THE DESIGN BLOCK THE PLAN SHOWS THE
 2011 NEC FOR DESIGN. THE NEC SPECIFIED FOR DESIGN IS
 NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE
 (ALSO SEE CURRENT CODES ABOVE)
 2. CARBON MONOXIDE DETECTORS ARE SHOWN IN WRONG
 LOCATION. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 3. PER THE 2014 NEC: ?BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED.? PROVIDE CORRECTION FOR ANY NEW OR ALTERED
 CIRCUITS, A NOTE WILL SUFFICE. NEC 210.12
 4. PLAN PROVIDED DOES NOT SHOW ALL WORK DESCRIBED IN
 ATTACHED CONTRACT. SHOW ALL ELECTRICAL WORK ON PLAN.
 FBC 107.2.1, 107.3.5
 5. PROVIDE PANEL SCHEDULE INDICATING SIZE OF PANEL, ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4
 6. PROVIDE LOAD CALCULATION FOR SERVICE AND FOR
 INDIVIDUAL UNIT, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30
 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 9. BOTH COPIES OF PLAN ARE REQUIRED TO BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. FS 471, 481; FBC
 107.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-03-29 Cont ID  
Sent By pleduc Date 2018-03-29 Time   Rev Time 0.00
Received By pleduc Date 2018-03-28 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By pleduc Date 2018-03-12 Time   Rev Time 0.00
Received By pleduc Date 2018-03-09 Time 15:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-09 Cont ID  
Sent By pleduc Date 2018-02-09 Time   Rev Time 0.00
Received By pleduc Date 2018-02-09 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-05 Cont ID  
Sent By skennedy Date 2018-04-05 Time 17:03 Rev Time 0.00
Received By skennedy Date 2018-03-26 Time 14:02 Sent To  
Notes
2018-03-27 14:02:15B04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-23 Cont ID  
Sent By gjohnson Date 2018-03-23 Time 13:36 Rev Time 0.00
Received By gjohnson Date 2018-03-07 Time 10:15 Sent To  
Notes
2018-03-08 10:15:37B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-02 Cont ID  
Sent By gjohnson Date 2018-03-02 Time 10:23 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 10:23 Sent To  
Notes
2018-02-08 13:31:19B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-02-14 Cont ID  
Sent By aclange Date 2018-02-14 Time 14:31 Rev Time 0.00
Received By aclange Date 2018-02-14 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-02-14 Cont ID  
Sent By aclange Date 2018-02-14 Time 14:35 Rev Time 0.00
Received By aclange Date 2018-02-14 Time 14:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-04-05 Cont ID  
Sent By skennedy Date 2018-04-05 Time 17:03 Rev Time 0.00
Received By skennedy Date 2018-04-05 Time 17:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-03-23 Cont ID  
Sent By gjohnson Date 2018-03-23 Time 13:28 Rev Time 0.00
Received By gjohnson Date 2018-03-23 Time 13:28 Sent To  
Notes
2018-03-23 13:35:132ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. NEW PLAN SHEET SHOW WATER HEATER AS EXISTING THE
 SCOPE OF WORK STATES THE EXISTING WATER HEATER TO BE
 REPLACED WITH A TANKLESS WATER HEATER PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 2. THE SCOPE OF WORK IS STATING TWO TYPES OF WATER
 HEATER THE PLANS AND SCOPE OF WORK NEED TO BE CLEAR AS
 TO WHICH TYPE IS BEING INSTALLED YOU WILL NEED TO
 DETERMINE YOUR ELECTRIC LOAD WILL BE TO HIGH. BEFORE
 RESUBMITTING. PER WPB AMEND TO FBC 107.2.1.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-02 Cont ID  
Sent By gjohnson Date 2018-03-02 Time 10:22 Rev Time 0.00
Received By gjohnson Date 2018-03-02 Time 09:37 Sent To  
Notes
***NONE***