| 2018-02-16 06:35:32 | 02/16/2018 1ST GAS REVIEW**DENIED** |
| | |
| | YOU PLANS CONTINUE TO HAVE THE SAME DEFICIENCIES EVEN |
| | AFTER REVIEWING WITH YOUR STAFF OVER THE PHONE AND |
| | HAVING SITE MEETINGS. IN ORDER TO HELP ME HELP YOU |
| | PLEASE PROVIDE THE FOLLOWING ON EACH GAS PERMIT. |
| | |
| | 1) PROVIDE TOTAL BTU OF ANY EXISTING SYSTEM. THIS PLAN |
| | SHOWS NO EXISTING SYSTEM BUT CITY RECORDS OF A RECENT |
| | PERMIT SHOW A GAS POOL HEATER AND RANGE. REFER TO THE |
| | 2017 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. |
| | |
| | 2) THE CURRENT CODE IN EFFECT IS THE 2017 FBC FUEL AND |
| | GAS BUT YOU CONTINUE TO LIST AND PROVIDE SIZING TABLES |
| | AS 2014. |
| | |
| | 3) PROVIDE THE CORRECT SIZING TABLES. YOU CONTINUE TO |
| | NOT PROVIDE THE REQUIRE SIZING TABLES FOR SCH 40 |
| | METALLIC PIPE .5 LB. REFER TO THE 2017 FBC- FUEL GAS |
| | SEC 402.4 |
| | |
| | 4) EXPLAIN YOUR INTENT TO CHANGE PIPING PRESSURES OF |
| | THE SYSTEM. THIS PLAN SHOWS A 2LB SYSTEM BUT AGAIN |
| | RECENT CITY RECORDS SHOW THIS AS A 12" WC (.5LB) |
| | SYSTEM. IS IT YOUR INTENT TO UPGRADE THE ENTIRE SYSTEM |
| | TO A 2LB SYSTEM? WPB AMEND 107.2.1 |
| | |
| | 5) IF YOUR DESIGNED SYSTEM IS GOING TO BE 2LB YOU MUST |
| | PROVIDE THE COMPLETE GAS REGULATOR INSTALLATION MANUAL. |
| | THIS PLAN SHOW IT AS A 2LB SYSTEM BUT NO INFORMATION ON |
| | THE GAS REGULATORS PROVIDED. 2017 FBC- FUEL GAS SEC |
| | 410.1 |
| | |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |