Plan Review Details - Permit 18020164
Plan Review Stops For Permit 18020164
Review Stop AD ADDRESSING
Rev No 3 Status F Date 2018-08-23 Cont ID  
Sent By cthroop Date 2018-08-23 Time 12:28 Rev Time 0.00
Received By cthroop Date 2018-08-23 Time 12:28 Sent To  
Notes
2018-08-23 12:32:25BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PAECEL HAS NOT BEEN SUB-DIVIDED. CANNOT ISSUE
 ADDRESSES. SEE ZONING COMMENTS.

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-04-07 Cont ID  
Sent By cthroop Date 2018-04-07 Time 11:51 Rev Time 0.00
Received By cthroop Date 2018-04-07 Time 11:51 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By cthroop Date 2018-03-15 Time 15:24 Rev Time 0.00
Received By cthroop Date 2018-03-14 Time 17:45 Sent To  
Notes
2018-03-15 15:25:15CONTACT MICHAEL ORIO @ [email protected] TO SET UP ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-23 Cont ID  
Sent By cthroop Date 2018-08-23 Time 14:21 Rev Time 0.00
Received By cthroop Date 2018-08-23 Time 09:05 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-07 Cont ID  
Sent By cthroop Date 2018-04-07 Time 12:12 Rev Time 0.00
Received By cthroop Date 2018-04-06 Time 14:48 Sent To  
Notes
2018-04-07 12:15:07BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. 2ND REQUEST. PROVIDE SOILS REPORT.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By cthroop Date 2018-03-15 Time 15:26 Rev Time 0.00
Received By cthroop Date 2018-03-14 Time 14:36 Sent To  
Notes
2018-03-15 15:28:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017
 FLORIDA BUILDING CODE, 6TH EDITION.
  
 1. SEE DESIGN PARAMETERS ON PAGE 1-4. PLANS DESIGNED TO
 THE 2014 FBC 5TH ED. CURRENT CODE IS THE 2017 FBC 6TH
 ED.
 2. PROVIDE SOILS REPORT.
 3. PALM BEACH COUNTY IMPACT FEES WILL APPLY.
 4. ROOFING PERMIT REQUIRED.
 5. VALUE WILL BE ADJUSTED FROM APPLIED VALUE OF $90,000
 TO CALCULATED VALUE OF $187,563 BASED ON THE CURRENT
 ICC BUILDING VALUATION DATA.
 6. THE FOLLOWING PRODUCT APPROVALS HAVE EXPIRED.
 FL15187 EXT. DOOR AND FL239-R24 SH WINDOWS. PROVIDE
 CURRENT PRODUCT APPROVALS FOR EACH ITEM.
 7. ADDRESS - CONTACT MICHAEL ORIO @ [email protected].
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-10 Cont ID  
Sent By ppetty Date 2018-04-10 Time 14:09 Rev Time 0.00
Received By ppetty Date 2018-04-10 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-01 Cont ID  
Sent By jpearson Date 2018-03-01 Time 15:39 Rev Time 0.00
Received By jpearson Date 2018-03-01 Time 15:39 Sent To  
Notes
2018-03-01 15:39:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT
 CODES ABOVE)
 2. PLAN IS REQUIRED TO SHOW THE ADDRESS OF THE PROJECT.
 PROVIDE CORRECTION. FBC 107.2.1
 3. PANEL SCHEDULE SHOWS AFCI PROTECTION IN SOME AREAS,
 BUT DOES NOT SHOW ALL AREAS REQUIRED PER CODE. BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH WOULD REQUIRE A 25 AMP BREAKER.
 PROVIDE CORRECTION. NEC 422.13; FBC RE E3702.10
 6. SMOKE ALARM MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR AND 3 FEET FROM ANY MECHANICAL DUCT OR
 CEILING FAN. PROVIDE CORRECTION. FBC RE R314.3(4); NFPA
 72; 29.8.3.4.6,7
 7. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-23 Cont ID  
Sent By cthroop Date 2018-08-23 Time 14:21 Rev Time 0.00
Received By cthroop Date 2018-08-13 Time 11:15 Sent To  
Notes
2018-08-15 11:15:40RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-24 Cont ID  
Sent By lmarchan Date 2018-04-24 Time 14:46 Rev Time 0.00
Received By lmarchan Date 2018-03-28 Time 12:56 Sent To  
Notes
2018-03-29 12:56:43R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-15 Cont ID  
Sent By cthroop Date 2018-03-15 Time 15:29 Rev Time 0.00
Received By cthroop Date 2018-02-05 Time 10:47 Sent To I
Notes
2018-02-07 10:47:18R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By cthroop Date 2018-03-15 Time 15:25 Rev Time 0.00
Received By cthroop Date 2018-03-14 Time 14:36 Sent To  
Notes
2018-03-15 15:26:51BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-17 Cont ID  
Sent By cmontell Date 2018-04-17 Time 13:31 Rev Time 0.00
Received By cmontell Date 2018-04-17 Time 13:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-03-01 Cont ID  
Sent By cmontell Date 2018-03-01 Time 15:08 Rev Time 0.00
Received By cmontell Date 2018-03-01 Time 14:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-30 Cont ID  
Sent By lcrespo Date 2018-03-30 Time 14:37 Rev Time 0.00
Received By lcrespo Date 2018-03-30 Time 14:37 Sent To  
Notes
2018-03-30 14:38:3503/30/18 APPROVED AND PUT BACK IN R18, LAC

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-13 Cont ID  
Sent By gjohnson Date 2018-03-13 Time 16:59 Rev Time 0.00
Received By gjohnson Date 2018-03-13 Time 16:35 Sent To  
Notes
2018-03-13 17:01:241ST REVIEW: FBC 2017 6TH EDITION
 PLUMBING COMMENTS: APPROVED
  
 SANITARY ISOMETRIC DRAWING WAS REDLINED FOR CODE
 COMPLIANCE PLEASE CORRECT IF PLUMBING PLAN IS
 RESUBMITTED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-03-15 Cont ID  
Sent By cthroop Date 2018-03-15 Time 15:24 Rev Time 0.00
Received By cthroop Date 2018-03-14 Time 17:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-03-15 Cont ID  
Sent By cthroop Date 2018-03-15 Time 15:25 Rev Time 0.00
Received By cthroop Date 2018-03-14 Time 14:36 Sent To  
Notes
2018-03-15 15:25:52DUPLICATE ROOFING STOP. CT

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2018-08-22 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-22 Time 09:44 Sent To B
Notes
2018-08-22 09:44:221.) PLEASE PROVIDE EVIDENCE THAT THE PROPOSED LOTS HAVE
 BEEN LEGALLY SUBDIVIDED AND MEET MINIMUM LOT WIDTH
 2.) LANDSCAPE PERMIT REQUIRED
 3.) PROVIDE ADDRESS OF PROPERTY
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-04-06 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-05 Time 14:36 Sent To  
Notes
2018-04-06 10:45:251.) PROVIDE SITE PLAN INDICATING SETBACKS OF ALL
 PROPOSED STRUCTURES
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-02-13 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-13 Time 09:32 Sent To  
Notes
2018-02-13 09:50:43FAILED
  
 1.) PROVIDE ADDRESS OF PROPERTY
 2.) SUBMIT REQUIRED LANDSCAPE PERMIT
 3.) DOES PROPERTY BOUNDARY ON SURVEY PROVIDED REFLECT
 CURRENT PROPERTY BOUNDARIES?
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]