| 2018-02-09 13:13:15 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017 |
| | FLORIDA BUILDING CODE, 6TH EDITION. |
| | |
| | 1. TEMPORARY STRUCTURES SHALL COMPLY WITH 2017 FBC |
| | CHPT. 31. |
| | 2. PROVIDE LIFE SAFETY PLAN DELINEATING THE MEANS OF |
| | EGRESS AND OCCUPANT LOAD. |
| | 3. EXIT TRAVEL DISTANCE SHALL BE 100 FEET OR LEASS PER |
| | SECTION 3103.4. |
| | 4. OCCUPANT LOAD SHALL BE DETERMINED PER CHPT. 10, |
| | SECTION 1004, TABLE 1004.1.2. |
| | 5. NUMBER OF EGRESS EXITS SHALL BE DETERMINED PER |
| | SECTION 1006, TABLE 1006.2.1. |
| | 6. MEANS OF EGRESS ILLUMINATION SHALL BE DETERMINED PER |
| | SECTION 1008.3 |
| | |
| | |
| | 3103.1 GENERAL. |
| | |
| | THE PROVISIONS OF SECTIONS 3103.1 THROUGH 3103.4 SHALL |
| | APPLY TO STRUCTURES ERECTED FOR A PERIOD OF LESS THAN |
| | 180 DAYS. TENTS AND OTHER MEMBRANE STRUCTURES ERECTED |
| | FOR A PERIOD OF LESS THAN 180 DAYS SHALL COMPLY WITH |
| | THE FLORIDA FIRE PREVENTION CODE. THOSE ERECTED FOR A |
| | LONGER PERIOD OF TIME SHALL COMPLY WITH APPLICABLE |
| | SECTIONS OF THIS CODE. |
| | |
| | 3103.1.1 CONFORMANCE. |
| | TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| | STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| | ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| | REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| | HEALTH, SAFETY AND GENERAL WELFARE. |
| | |
| | 3103.1.2 PERMIT REQUIRED. |
| | TEMPORARY STRUCTURES THAT COVER AN AREA GREATER THAN |
| | 120 SQUARE FEET (11.16 M2), INCLUDING CONNECTING AREAS |
| | OR SPACES WITH A COMMON MEANS OF EGRESS OR ENTRANCE |
| | THAT ARE USED OR INTENDED TO BE USED FOR THE GATHERING |
| | TOGETHER OF 10 OR MORE PERSONS, SHALL NOT BE ERECTED, |
| | OPERATED OR MAINTAINED FOR ANY PURPOSE WITHOUT |
| | OBTAINING A PERMIT FROM THE BUILDING OFFICIAL. |
| | |
| | 3103.2 CONSTRUCTION DOCUMENTS. |
| | A PERMIT APPLICATION AND CONSTRUCTION DOCUMENTS SHALL |
| | BE SUBMITTED FOR EACH INSTALLATION OF A TEMPORARY |
| | STRUCTURE. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE A |
| | SITE PLAN INDICATING THE LOCATION OF THE TEMPORARY |
| | STRUCTURE AND INFORMATION DELINEATING THE MEANS OF |
| | EGRESS AND THE OCCUPANT LOAD. |
| | |
| | 3103.3 LOCATION. |
| | TEMPORARY STRUCTURES SHALL BE LOCATED IN ACCORDANCE |
| | WITH THE REQUIREMENTS OF TABLE 602 BASED ON THE |
| | FIRE-RESISTANCE RATING OF THE EXTERIOR WALLS FOR THE |
| | PROPOSED TYPE OF CONSTRUCTION. |
| | |
| | 3103.4 MEANS OF EGRESS. |
| | TEMPORARY STRUCTURES SHALL CONFORM TO THE MEANS OF |
| | EGRESS REQUIREMENTS OF CHAPTER 10 AND SHALL HAVE AN |
| | EXIT ACCESS TRAVEL DISTANCE OF 100 FEET (30 480 MM) OR |
| | LESS |
| | |
| | |