Plan Review Details - Permit 18020090
Plan Review Stops For Permit 18020090
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-03-13 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2018-03-13 Time 07:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-07 Cont ID  
Sent By jwitmer Date 2018-02-07 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2018-02-07 Time 12:27 Sent To  
Notes
2018-02-07 15:07:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020090
 ADD: 1901 VILLAGE BLVD.
 CONT: MOUW ASSOCIATES INC.
 TEL: 561-276-9640
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. FEB. 09/ 2018
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE SCOPE OF WORK
 IS FOR SET UP OF A TEMPORARY OFFICE TRAILER. PLEASE
 CLARIFY WHO THIS OFFICE TRAILER IS BEING SET UP FOR.
 FOR THE USE BY THE ADMINISTRATION OF BEAR LAKES COUNTRY
 CLUB WHERE ACCESSIBILITY WILL BE A ISSUE OR IS THIS
 UNIT TO BE USED FOR CONSTRUCTION PERSONNEL? WILL THERE
 BE JOBSITE MEETINGS WITH DESIGN PROFESSIONALS WHERE A
 HANDICAPPED RAMP, WITH A HANDRAIL / GUARDRAIL SYSTEM
 REQUIRED? IF SO WILL THERE BE PARKING FOR A HANDICAPPED
 PERSON WITH ACCESS AISLE?
  
 2) DEC. 31/ 2017 THE STATE WENT TO THE 2017 FBC/ 6TH
 EDITION. PLANS WERE DESIGNED UNDER THE 2014 CODE BUR
 SUBMITTED AFTER THE ADOPTION DATE AFTER THE 2017 CODE
 WAS ADOPTED STATEWIDE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By jpearson Date 2018-03-12 Time 12:42 Rev Time 0.00
Received By jpearson Date 2018-03-12 Time 12:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-20 Cont ID  
Sent By jpearson Date 2018-02-20 Time 14:11 Rev Time 0.00
Received By jpearson Date 2018-02-20 Time 12:39 Sent To  
Notes
2018-02-20 14:11:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-06 Cont ID  
Sent By scaldero Date 2018-02-06 Time 13:27 Rev Time 0.00
Received By scaldero Date 2018-02-06 Time 13:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-15 Cont ID  
Sent By lmarchan Date 2018-03-15 Time 07:55 Rev Time 0.00
Received By lmarchan Date 2018-03-06 Time 14:26 Sent To  
Notes
2018-03-08 14:26:58B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-05 Cont ID  
Sent By thunt Date 2018-03-05 Time 15:40 Rev Time 0.00
Received By thunt Date 2018-02-02 Time 15:14 Sent To I
Notes
2018-02-02 15:14:21B14

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-09 Cont ID  
Sent By thunt Date 2018-03-09 Time 12:18 Rev Time 0.00
Received By thunt Date 2018-03-09 Time 12:18 Sent To  
Notes
2018-03-09 12:20:43WITH G.C APPROVAL FROM SITE MEETING ON 3/9/18 I INCLUDE
 THE CLEAR FLOOR SPACES ON THE PLAN AS FROM MY PRE-FIELD
 INSPECTION THIS RESTROOM MEETS ADA ONCE THE TOILET
 PAPER DISPENCER AND SIDE GRAB BAR ARE RELOCATED. TLH

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-05 Cont ID  
Sent By thunt Date 2018-03-05 Time 15:24 Rev Time 0.00
Received By thunt Date 2018-03-05 Time 15:24 Sent To  
Notes
2018-03-05 15:38:4703/05/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PLEASE REVISE PLAN SHOWING THAT WE ARE CURRENTLY
 USING THE 2017 (6TH EDITION) OF THE FBC AS OF
 DEC,31,2017
  
 2) SHOW CLEAR FLOOR SPACING FOR TOILET AND SINK AND
 COMPLY WITH FBC-A 604.8.1.6
  
 3) SHOW CLEAR APPROACH AND CLEAR FLOOR SPACE TO COMPLY
 WITH FBC-A 606.2, FBC-A 606.3
  
 4) VALUE OF JOB SEEMS LOW. 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-03-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-14 Time 10:39 Sent To  
Notes
2018-03-14 10:39:041.) ALL SITE WORK AND LANDSCAPING SHALL BE COMPLETED
 PRIOR TO C.O. FOR COUNTRY CLUB
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-02-13 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-13 Time 09:32 Sent To  
Notes
2018-02-13 10:05:501.) REQUIRES APPROVAL OF MINOR PD AMENDMENT
 (PB1778)(Z18010035)
 2.) PLEASE SATISFY BUILDING AND PUBLIC WORKS COMMENTS
 AND RESUBMIT
 3.) PRIOR TO FINAL C.O. FOR COUNTRY CLUB, ALL SITE WORK
 AND LANDSCAPE SHALL BE COMPLETE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved