Plan Review Details - Permit 18020060
Plan Review Stops For Permit 18020060
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By shill Date 2018-08-02 Time 18:19 Rev Time 0.00
Received By shill Date 2018-08-02 Time 18:16 Sent To  
Notes
2018-08-02 18:15:08****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD ARE
 TO BE SUBMITTED TO THE BUILDING DIVISION, REVIEWED AND
 ISSUED PRIOR TO INSTALLATION.
  
 2. A SEPARATE ROOF PERMIT IS REQUIRED. SUBMIT
 APPLICATION WITH ROOF PRODUCT APPROVAL AND ENGINEERING
 IF APPLICABLE. PRODUCT APPROVAL IS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 3. CANOPY ENGINEERING IS TO BE REVIED BY STRUCTURAL
 ENGINEER OF RECORD AND SUBITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 19:00 Rev Time 0.00
Received By shill Date 2018-05-22 Time 18:44 Sent To  
Notes
2018-05-22 19:11:20****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD ARE
 TO BE SUBMITTED TO THE BUILDING DIVISION, REVIEWED AND
 ISSUED PRIOR TO INSTALLATION.
  
 2. A SEPARATE ROOF PERMIT IS REQUIRED. SUBMIT
 APPLICATION WITH ROOF PRODUCT APPROVAL AND ENGINEERING
 IF APPLICABLE. PRODUCT APPROVAL IS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 3. CANOPY ENGINEERING IS TO BE REVIED BY STRUCTURAL
 ENGINEER OF RECORD AND SUBITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-02 Cont ID  
Sent By jwitmer Date 2018-03-02 Time 17:28 Rev Time  
Received By jwitmer Date 2018-03-02 Time 13:01 Sent To  
Notes
2018-03-02 17:13:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020060
 ADD: 2020 PALM BEACH LAKES BLVD. SUITE:2070
 CONT: TBD/ TO BE DETERMINED
 TEL: 407-629-9124
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 02/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET T-I.I:
 1A) PLEASE NOTE THE PLANS WERE SIGNED AND SEALED ON
 DEC. 14/ 2017 AND DESIGNED UNDER THE 2014 FBC BUT THEY
 WERE SUBMITTED ON FEB. 02/2018. DEC.31/2017 THE 6TH
 EDITION OR 2017 FBC FAMILY OF CODES WAS ADOPTED
 STATEWIDE. PLEASE REVIEW THE DIFFERENCE IN CODES, PLANS
 NEED TO SHOW CODE COMPLIANCE TO THE 2017 FBC.
  
 1B) ON THE LEFT SIDE OF THE SHEET JUST ABOVE THE AREA
 MAP THERE IS A STATEMENT THAT THIS PROJECT IS A LEVEL 2
 ALTERATION AND ADDITION AS DEFINED BY THE INTERNATIONAL
 BUILDING CODE. PLEASE NOTE THE IBC MAYBE THE BASE CODE,
 BUT THE 2017 FLORIDA BUILDING CODE, EXISTING BUILDING
 IS THE CODE ADOPTED STATEWIDE, PLEASE CORRECT THE CODE
 REFERENCE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1C) THE COVERSHEET NOTE 11.3 INDICATES THE EXISTING RTU
 # 4 IS TO BE REPLACED WHEREAS SHEET A1.7 AND
 SHEET M-I.I BOTH INDICATE THE 2 UNITS WILL BE REMAINING
 NOT BEING REPLACED? 107.2.1.3 DISCREPANCY IN PLANS,
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A-I.I AT THE DRIVE THROUGH WINDOW THERE ARE
 NOTES FOR THE BOND BEAM. SEE A1.3 STRUCTURAL FOR NEW
 BOND BEAM WITH BOTTOM AT 6 FOOT 0 3/8 INCH A.F.F. SHEET
 A-1.3 DETAIL 13 SHOW THE BOTTOM OF THE DRIVE THROUGH
 WINDOW AT 3 FOOT. A-I.I CUT SECTION THROUGH THE DRIVE
 THROUGH WINDOW DETAIL 3/ A3.1 . ON SHEET
 A-3.1 DETAIL 3 SHOWS A CUT SECTION THROUGH THE
 DRIVE-THRU WITH THE BOTTOM OF THE WINDOW AGAIN AT 3
 FOOT A.F.F. IN THIS SAME WALL SECTION OF THE DRIVE THRU
 WINDOW THERE ARE 2 MORE DETAILS OF THE WINDOW SILL
 12/A1.3 AND THE HEADER 11/A1.3 BOTH OF THESE DETAILS
 ARE ALSO MISLABELED. PLEASE CORRECT ALL OF THE
 MISLABELED DETAILS AND OR SECTIONS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) THE COVERSHEET NOTE # 7 INDICATES SEE ASP-I.I AND
 LANE CANOPIES SHOP DRAWINGS FOR NEW CANOPY LAYOUT.
 PLEASE NOTE SHEET ASP-I.I IS JUST A LAYOUT SHEET
 SHOWING THE DIMENSION. THERE IS NO INFORMATION AS TO
 THE CANOPY, MATERIALS, SIZE OF FRAMING MEMBERS, GAUGE
 OF METAL, DECKING MATERIAL NOR IS THERE ANY SHOP
 DRAWINGS.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES.
  
 CANOPY DRAWINGS (SHOP DRAWINGS) CAN BE A DEFERRED
 SUBMITTAL. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4) SHEET A-1.3 DETAILS 14 & 15 BOTH INDICATE THE USE OF
 CMU FOAM INSULATION AND REFERENCE 6A3.1. THE INDEX
 SHEET DOES NOT REFERENCE A 6A3.1? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 5) UNDER THE 1ST REVIEW THERE WERE NO DOCUMENTS
 SUBMITTED FOR COMPLIANCE WITH THE ENERGY CODE. THERE
 ARE 2 CRITERIA THAT NEEDS TO BE DETERMINED:
  
 5A) IF THIS BUILDING MEETS THE DEFINITION OF RENOVATED
 BUILDING UNDER THE 2017 FBC-ENERGY CODE.
 RENOVATED BUILDING. A RESIDENTIAL OR NONRESIDENTIAL
 BUILDING UNDERGOING ALTERATION THAT VARIES OR CHANGES
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS OR
 EXTERIOR ENVELOPE CONDITIONS, PROVIDED THE ESTIMATED
 COST OF RENOVATION EXCEEDS 30 PERCENT OF THE ASSESSED
 VALUE OF THE STRUCTURE.
  
 5B) 2017 FBC-ENERGY CODE C401.2 APPLICATION. COMMERCIAL
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL
 COMPLY WITH SECTION C406 AND TENANT SPACES SHALL COMPLY
 WITH SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407.
 THE BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN
 85 PERCENT OF THE STANDARD REFERENCE
 DESIGN BUILDING.
  
 6) SHEET S0.1:
 6A) SHEET S0.1 INDICATES UNDER NOTE # 2 THE DESIGN AND
 CONSTRUCTION SHALL BE BASED ON THE 2014 FBC-B. THE
 PLANS WERE SIGNED AND DATED 12/15/2017. THE PLANS WERE
 SUBMITTED ON FEB. 02/2018. DEC.31/2017 THE 6TH EDITION
 OR 2017 FBC FAMILY OF CODES WAS ADOPTED STATEWIDE.
 PLEASE REVIEW THE DIFFERENCE IN CODES, PLANS NEED TO
 SHOW THE BUILDING DESIGN IS BASED ON THE 2017 FBC
 ?BUILDING, THE 6TH EDITION OF THE FLORIDA BUILDING
 CODE.
  
 6B) THE FOUNDATION NOTES 1 & 2 BOTH APPEAR THERE SHOULD
 BE A SOILS REPORT SUBMITTED BASED ON AN ALLOWABLE SOILS
 BEARING PRESSURE OF 2000 PSF AND TO BE CONFIRMED BY A
 FLORIDA LICENSED SOILS ENGINEER.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL.
  
 6C) NOTICE ONLY NOT NECESSARY FOR A RESPONSE. THE ROOF
 PRESSURES AND WALL PRESSURES SUBMITTED IN VASD ARE ALL
 GOOD!
  
 6D) NOTES UNDER THE HEADING MASONRY WALL CONSTRUCTION
 NOTE 10 FOR LINTELS INDICATES SUBMIT SHOP DRAWINGS WITH
 RATED LOAD CAPACITIES. TO BE REVIEWED BY THE STRUCTURAL
 ENGINEER OF RECORD AND SHOP DRAWING STAMP OF APPROVAL
 APPLIED BEFORE BEING SUBMITTED TO THE JURISDICTION
 HAVING AUTHORITY.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 7) PLEASE SUBMIT PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 FANS, VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS & LINTELS
  
 7A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 9) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 10 ) SHEET A-5.3 DETAIL #4 SHOWS THE FRONT SERVING
 COUNTER BUT THERE ARE NO MEASUREMENTS PROVIDING
 COMPLIANCE WITH ACCESSIBILITY.
 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE
 LINES SHALL COMPLY WITH 904.5.
  
 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL COMPLY WITH 308.
  
 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 11) SHEET A-1.1 SHOWS THE REQUIRED AMOUNT OF ACCESSIBLE
 TABLES, WHAT THE PLAN DOES NOT SHOW IS AT WHAT HEIGHT
 THE ACCESSIBLE TABLE ARE FROM THE FINISH FLOOR AND
 COMPLIANCE WITH;
 2017 FBC- ACCESSIBILITY CODE SECTION 902.3 HEIGHT. THE
 TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By jpearson Date 2018-07-24 Time 15:03 Rev Time 0.00
Received By jpearson Date 2018-07-24 Time 12:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-18 Cont ID  
Sent By jpearson Date 2018-05-18 Time 10:56 Rev Time 0.00
Received By jpearson Date 2018-05-18 Time 09:21 Sent To  
Notes
2018-05-18 10:55:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SEVERAL LOCATIONS ON PLAN SHOW THE NEC USED FOR
 DESIGN AS OLDER CODES. THE CURRENT NEC IN EFFECT IS THE
 2014 NEC. REMOVE ALL REFERENCES TO OLDER VERSIONS OF
 THE CODE. FBC PREFACE, 107.2.1 (SHEET T-1.1 STILL SHOWS
 THE 2011 NEC AS BASIS FOR DESIGN. PROVIDE CORRECTION.)
 2. CORRECTED.
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE,
 AND FOR PROPER MARKING OF EQUIPMENT PER CODE. NEC
 110.9, 110.10, 110.16, 110.24 (THIS WILL BE A DEFERRED
 SUBMITTAL AS DISCUSSED AND WILL SHOW AS A PROVISO ON
 PLAN. NO FURTHER ACTION NECESSARY AT THIS TIME.)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED, NOT APPLICABLE.
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94 (NOTE ADDED TO PLAN
 STATES: "INTERLOCK COMMUNICATION SYSTEM GROUND WITH
 MAIN GROUND SYSTEM." THIS DOES NOT FULFILL THE
 REQUIREMENT PER CODE. AN INTERSYSTEM BONDING
 TERMINATION POINT MUST BE LOCATED AT THE SERVICE. SEE
 250.94)
 8. IT APPEARS THE 1200 AMP SERVICE IS LOCATED OUTSIDE.
 PROVIDE DETAILS OF ENCLOSURE RATING FOR THIS
 ENVIRONMENT. NEC 110.3, 110.28 (NOTE WAS ADDED TO PLAN
 THAT STATES TVSS AND SURGE ARRESTOR UNITS SHALL BE NEMA
 3R. THIS DOES NOT ADDRESS PANEL MDP. PROVIDE CORRECTION
 AS PREVIOUSLY REQUESTED.)
 9. CORRECTED.
 10. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE FOR THE BACK AREAS
 INCLUDING THE KITCHEN, OFFICE, AND MULTI-PURPOSE ROOM.
 FBC EC C405.2 (COMMENT RESPONSE STATED THAT EXPLANATION
 FOR LIGHTING CONTROL PANEL WAS ON SHEET E2.2. I FOUND
 NO EXPLANATION OF THIS PANEL AND WHAT IT DOES OR DOES
 NOT CONTROL. PROVIDE AS PREVIOUSLY REQUESTED.)
 11. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-07 Cont ID  
Sent By jpearson Date 2018-03-07 Time 15:49 Rev Time 0.00
Received By jpearson Date 2018-03-07 Time 11:43 Sent To  
Notes
2018-03-07 15:49:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SEVERAL LOCATIONS ON PLAN SHOW THE NEC USED FOR
 DESIGN AS OLDER CODES. THE CURRENT NEC IN EFFECT IS THE
 2014 NEC. REMOVE ALL REFERENCES TO OLDER VERSIONS OF
 THE CODE. FBC PREFACE, 107.2.1
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE,
 AND FOR PROPER MARKING OF EQUIPMENT PER CODE. NEC
 110.9, 110.10, 110.16, 110.24
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. MAIN BONDING JUMPER IS SIZED AS 3/0 COPPER, WHICH IS
 TOO SMALL. THIS WIRE SHOULD BE SIZED A MINIMUM OF 12.5%
 OF THE SERVICE CONDUCTOR TOTAL AREA. PROVIDE
 CORRECTION. NEC 250.28(D), TABLE 250.102(C)(1)
 6. SHOW COMPLIANCE WITH NEC 240.87
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 8. IT APPEARS THE 1200 AMP SERVICE IS LOCATED OUTSIDE.
 PROVIDE DETAILS OF ENCLOSURE RATING FOR THIS
 ENVIRONMENT. NEC 110.3, 110.28
 9. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 10. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE FOR THE BACK AREAS
 INCLUDING THE KITCHEN, OFFICE, AND MULTI-PURPOSE ROOM.
 FBC EC C405.2
 11. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: ?WITHIN
 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO
 THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM
 OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2.
 FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL
 DISTRIBUTION.? FBC EC C405.6.4.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-07-24 Cont ID  
Sent By jpearson Date 2018-07-24 Time 13:10 Rev Time 0.00
Received By jpearson Date 2018-07-24 Time 13:10 Sent To  
Notes
2018-07-24 13:10:46LOW VOLTAGE SHOWN ON PLANS. VALUE SHOULD BE CONFIRMED
 ON PERMIT APPLICATION FOR LOW VOLTAGE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2018-02-06 Cont ID  
Sent By squinone Date 2018-02-06 Time   Rev Time 0.00
Received By squinone Date 2018-02-05 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 11:53 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 11:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-01 Cont ID  
Sent By scaldero Date 2018-05-01 Time 12:13 Rev Time 0.00
Received By scaldero Date 2018-05-01 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-09 Cont ID  
Sent By scaldero Date 2018-03-09 Time 11:36 Rev Time 0.00
Received By scaldero Date 2018-03-09 Time 11:23 Sent To  
Notes
2018-03-09 11:35:21PERMIT # 18020060
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) PLEASE SEE AND RESPOND TO BUILDING REVIEW COMMENTS
 REGARDING THE CANOPY.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-08-29 Cont ID  
Sent By gjohnson Date 2018-08-29 Time 17:17 Rev Time 0.00
Received By gjohnson Date 2018-08-29 Time 17:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-08-03 Cont ID  
Sent By gjohnson Date 2018-08-03 Time 12:00 Rev Time 0.00
Received By gjohnson Date 2018-08-03 Time 12:00 Sent To  
Notes
2018-08-03 12:08:522ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: 3RD REQUEST PREVIOUS COMMENTS NOT
 COMPLIED WITH. RESPONSE LETTER STATED THAT COMMENTS HAD
 BEEN CORRECTED, THE PLANS DID NOT REFLECT THE
 RESPONSES.
  
 1. THE GAS RISER SHALL HAVE THE FOLLOWING INFORMATION
 ON IT TO SHOW CODE COMPLIANCE.
 A) SHOW THE LENGTH OF CUT SECTION OF PIPE.
 B) SHOW TYPE OF PIPE.
 C) SHOW SYSTEM PRESSURE.
 D) SHOW SHUT OF VALVES, DRIP LEGS AND REGULATORS.
 PER FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2. AND WPB
 AND TO FBC 107.2.1
  
 2. PROVIDE SIZING TABLES USED IN SIZING NEW PIPING. PER
 FBC-2017 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(37).
  
 3. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RELOCATED WATER HEATER. PER FBC-2017 FUEL GAS CODE SEC.
 304.
  
 NEW COMMENT:
  
 1. SHT. P 4.1 DETAIL #3 SHOWS GAS PIPING RUNNING ON TOP
 OF THE ROOF BUT THE RISER AND FLOOR PLAN SHOWS THE
 PIPING RUNNING UNDER THE ROOF. PLEASE CLARIFY PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT. P 4.1 DETAIL #4 THE GAS SCHEDULE SHOWS TOTAL OF
 1245 UNDER REMARKS IT SHOWS 1230 PLEASE CLARIFY PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-24 Cont ID  
Sent By gjohnson Date 2018-05-24 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2018-05-24 Time 15:00 Sent To  
Notes
2018-05-24 17:31:051ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: 2ND REQUEST PREVIOUS COMMENTS NOT
 COMPLIED WITH.
  
 1. THE GAS RISER SHALL HAVE THE FOLLOWING INFORMATION
 ON IT TO SHOW CODE COMPLIANCE.
 A) SHOW THE LENGTH OF CUT SECTION OF PIPE.
 B) SHOW TYPE OF PIPE.
 C) SHOW SYSTEM PRESSURE.
 D) SHOW SHUT OF VALVES, DRIP LEGS AND REGULATORS.
 PER FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2. AND WPB
 AEND TO FBC 107.2.1
  
 2. PROVIDE SIZING TABLES USED IN SIZING NEW PIPING. PER
 FBC-2017 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(37).
  
 3. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RELOCATED WATER HEATER. PER FBC-2017 FUEL GAS CODE SEC.
 304.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By lcrespo Date 2018-03-19 Time 07:14 Rev Time 0.00
Received By lcrespo Date 2018-03-19 Time 07:14 Sent To  
Notes
2018-03-19 07:13:1103/19/18
 GAS PLAN REVIEW
  
 DENIED WITH COMMENTS NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. 14. THE PLANS INDICATE AN
 EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4,
 401.8, 402.1, 402.2, 402.3
 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1
 3. 21. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.5 (9) COMMERCIAL GAS
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS
 SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1)
 THROUGH 402.4 (37)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1
 6. THE WATER HEATER HAS BEEN MOVED, PLEASE SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER THE 2017 FBC FUEL
 GAS SEC. 304.1, 614.5
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS SECS.
 502 THRU 505.
 9. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1.
 11. GAS APPLIANCES SHALL BE LISTED AND LABELED.
 10. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37)
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 18:32 Rev Time 0.00
Received By shill Date 2018-08-22 Time 09:57 Sent To  
Notes
2018-08-24 09:58:11RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-03 Cont ID  
Sent By gjohnson Date 2018-08-03 Time 12:09 Rev Time 0.00
Received By gjohnson Date 2018-06-22 Time 15:47 Sent To  
Notes
2018-06-25 15:47:40C31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-24 Cont ID  
Sent By gjohnson Date 2018-05-24 Time 17:34 Rev Time 0.00
Received By gjohnson Date 2018-04-25 Time 11:28 Sent To  
Notes
2018-04-27 11:28:42C31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-19 Cont ID  
Sent By lcrespo Date 2018-03-19 Time 07:14 Rev Time 0.00
Received By lcrespo Date 2018-02-02 Time 13:42 Sent To  
Notes
2018-02-02 13:42:35C31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 18:31 Rev Time 0.00
Received By shill Date 2018-08-29 Time 17:20 Sent To  
Notes
2018-08-30 18:32:33MU 2018 019709 $12,992.20
 PLANS WERE NOT STAMPED BUT RECEIVED EMAIL FROM PALM
 BEACH COUNTY THAT IT IS OK TO PASS; SENT EMAIL TO
 FILENET, RECEIPT WITH APPLICATION
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-08-02 Cont ID  
Sent By shill Date 2018-08-02 Time 18:19 Rev Time 0.00
Received By shill Date 2018-08-02 Time 18:19 Sent To  
Notes
2018-08-02 18:19:40PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-02 Cont ID  
Sent By jwitmer Date 2018-03-02 Time 17:28 Rev Time  
Received By jwitmer Date 2018-03-02 Time 13:01 Sent To  
Notes
2018-03-02 17:08:19IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-15 Cont ID  
Sent By ccole Date 2018-05-15 Time 11:53 Rev Time 0.00
Received By ccole Date 2018-05-15 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-06 Cont ID  
Sent By ccole Date 2018-03-06 Time 17:08 Rev Time 0.00
Received By ccole Date 2018-03-06 Time 17:03 Sent To  
Notes
2018-03-06 17:39:531ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION,
 WEST PALM BEACH AMENDMENTS TO THE FBC.
 PERMIT #18020060
 3/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR: A)
 KITCHEN HOODS AND EXHAUST SYSTEMS. B) FIRE SUPPRESSION
 SYSTEMS. C) WALK-IN COOLERS AND FREEZERS. PLEASE PLACE
 A NOTE ON THE PLAN IN BOLD LETTERS.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS SECTION C403.2.1 FBC-17 ENERGY CONSERVATION.
  
 3) SHEET M-1.1: PROVIDE DUCT SMOKE DETECTORS IN THE
 SUPPLY SYSTEMS OF AC #2 & #3- SECTION 606.2.1.
  
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL ROOFTOP EQUIPMENT, AND THE REQUIRED CLEARANCE
 DISTANCE MEASUREMENTS FROM AIR INTAKES TO EXHAUST
 OUTLETS- SECTION 107.1 WPB AMENDMENTS.
  
 5) M-3.1: REFER TO SECTION C403.2.8 AND SHOW COMPLIANCE
 IN THE PLANS AND CALCULATIONS- C403.2.8 KITCHEN EXHAUST
 SYSTEMS:
  
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
  
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
  
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
  
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
  
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
  
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
  
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
  
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED
  
 6) M-4.1: PROVIDE COMPLETE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE NEW AND RELOCATED RTU'S INCLUDING
 THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE WITH
 SECTION 1609 FBC-17 BUILDING. INDICATE HOW THE UNIT
 CURBS WILL BE ATTACHED TO THE ROOF STRUCTURE AND HOW
 THE RTU'S AND FANS WILL BE ATTACHED TO THE CURBS-
 SECTION 301.15.
  
 7) M-4.2: PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE AVCOA CONDENSER STAND WITH REVIEW STAMP BY
 THE ENGINEER OF RECORD. THE EOR SHALL CIRCLE,
 HIGHLIGHT, OR OTHERWISE MARK ALL APPLICABLE
 INSTALLATION DETAILS AND DESIGN PRESSURES SHOWN IN THE
 DOCUMENT- SECTION 301.15.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-03 Cont ID  
Sent By gjohnson Date 2018-08-03 Time 11:58 Rev Time 0.00
Received By gjohnson Date 2018-08-03 Time 11:58 Sent To  
Notes
2019-06-28 13:44:46GREASE INTERCEPTOR WAS REVIEWED UNDER MASTER PLAN
 REVIEW. T.LARGE.
2018-08-03 11:59:45PLUMBING PROVISO:
 PRIOR TO INSPECTIONS PROVIDE MANUFACTURE SPECIFICATIONS
 FOR ALL VALVES, BACKFLOW DEVISES, FILTERS AND FAUCETS
 MUST BE APPROVED BY BUILDING DEPT. PRIOR TO INSPECTION
 ALL SPECIFICATIONS SHALL SHOW COMPLIANCE WITH LEAD FREE
 REQUIREMENTS NSF 321/61 AND FAUCETS ASME A112.18.1/CSA
 B125.1. NSF 18. BACKFLOWS ASSE 1022
  
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-05-23 Cont ID  
Sent By gjohnson Date 2018-05-23 Time 15:29 Rev Time 0.00
Received By gjohnson Date 2018-05-23 Time 08:59 Sent To  
Notes
2018-05-23 15:29:522ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
 1. PROVIDE MANUFACTURE SPECIFICATIONS FOR PREFABRICATED
 BACKFLOW PANEL SHALL MEET NSF 372/61 LEAD FREE
 REQUIREMENTS. THEY SHALL BE ON JOBSITE PRIOR TO 1ST
 ROUGH INSPECTION.
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE ECO-POWER
 SENSOR LAVATORY FAUCETS SHALL MEET NSF 372 AND ASSE
 1070.
 3. THE MOP SINK SHALL COMPLY WITH FBC PL 405.9.
 4. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMER VALVE PER
 FBC PL 1002.4.1.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-17 Cont ID  
Sent By lcrespo Date 2018-03-17 Time 11:14 Rev Time 0.00
Received By lcrespo Date 2018-03-15 Time 15:40 Sent To  
Notes
2018-03-17 11:14:1603/17/2018 1ST REVIEW DENIED
 2017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT: 18020060
  
 1. 2018 PERMIT MUST REFLECT THE FLORIDA BUILDING CODE
 PLUMBING 2017 6TH EDITION, PLEASE MAKE CHANGES ALONG
 WITH ALL OTHER DISCIPLINES WHO HAVE NOTED IT.
 2. A SEPARATE BACKFLOW APPLICATION SHALL BE REQUIRED
 AND LOCATION OF THE DEVICE IS SET BY THE WEST PALM
 BEACH UTILITIES CROSS CONNECTION MANUAL AND OR
 ORDINANCES.
 3. VERTICAL HANDRAIL NOT REQUIRED FOR ADA COMPLIANCE ON
 A5.1
 4. MEN?S ROOM ADA BACK BAR DIMENSION MISSING ON THE
 VERTICAL PLANE. WPB AMENDMENTS. TO FBC SEC. 107.2.1.
 5. WHERE IS THE BOOSTER PUMP BEING RELOCATED TO? WPB
 AMENDMENTS. TO FBC SEC. 107.2.1.
 6. PIPING ON P-6.1 #2 SHOW A REDUCED PRESSURE VALVE
 WATER SERVICE AND YOU ALSO HAVE A BOOSTER PUMP
 INCORPORATED IN THE SYSTEM, IS THE RPV REQUIRED? FBC P
 SEC. 604.8 WATER PRESSURE-REDUCING VALVE OR REGULATOR.
 7. P-2.1 NOTE 2 AND 4 CALLS FOR PVC WATER DISTRIBUTION
 AND IT IS NOT ALLOWED BY PLUMBING CODE ON TABLE FBC P
 TABLE 605.4
 8. NEED SPECIFICATION ON PREFABRICATED BACKFLOW PANEL.
 WPB AMENDMENTS TO FBC SEC. 107.2.1.
 9. TEMPERED WATER VALVE MUST BE RATED FOR MULTI-LAVS
 CAPACITY PER MANUFACTURES SPECIFICATION.
 10. PAGE P2.1 PIPING FOR FILTER NEED SHUT OFF VALVE FOR
 TRAP PRIMER AND TO BE CONNECTED BEHIND FULL PORT VALVE
 TO ISOLATE, IF THIS A GENERIC AND IT SHOWS THIS WAY
 PLEASE CLARIFY IT OR REMOVE IT FOR IT NOT TO CREATE
 CONFUSION IN THE FIELD.
 11. ALL WATER FEED MUST BE PROTECTED WITH AN IN-LINE
 VACUUM BREAKER. 405.1 WATER SUPPLY PROTECTION. THE
 SUPPLY LINES AND FITTINGS FOR EVERY PLUMBING FIXTURE
 SHALL BE INSTALLED SO AS TO PREVENT BACKFLOW. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 12. CONDENSATE MATERIAL ON THE ROOF IS PVC AND THIS
 MATERIAL IS NOT UV PROTECTED AND PER MANUFACTURES
 SPECIFICATION IT CANNOT BE IN THE SUNLIGHT OF UV,
 PLEASE TELL US HOW YOU ARE GOING TO PROTECT IT? WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 13. A SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED
 FOR A CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE AT THIS TIME. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 14. EXPANSION DEVICE NOT SHOWN IN THE ISOMETRIC
 DRAWING, WPB AMENDMENTS TO FBC SEC. 107.2.1.
 15. MOP SINK NOT LABELED ON ISOMETRIC AND P1.1. MOP
 SINK AS MANUFACTURED PLUMBING FIXTURES OR PLUMBING
 FIXTURES CONSTRUCTED ON SITE SHALL MEET THE DESIGN
 REQUIREMENTS OF ASME A112.19.2/CSA B45.1 OR ASME
 A112.19.3/CSA B45.4. 2017 FBC P 405.9 DESIGN AND
 INSTALLATION OF PLUMBING FIXTURES.
 16. PLEASE PROVIDE A SIZING CALCULATION FOR EXISTING
 GREASE TRAP TO REFLECT NEW OCCUPANCY LOAD WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 17. TRAP SEAL SUBJECT TO EVAPORATION SHALL BE
 PROTECTED, A BARRIER DEVICE MAY BE USED THAT COMPLIES
 WITH ASSE 1072 BUT WHERE FOOD PREPARATION IS PRESENT
 THIS DEVICE MAY NOT COMPLY AND A TRAP PRIMER MAY BE
 REQUIRED FBC P SEC. 1002.4. PLEASE SUBMIT THE
 SPECIFICATION FOR APPROVAL AND REFER TO P-7.1, COMMENT
 P26A TO REFLECT THIS ASSE 1072 STANDARD.
 18. REQUIRED PAN DRAIN ON WATER HEATER, SHOW RELIEF
 LINE DUMPING INTO PAN DRAIN 2017 FBC P SEC. 504.6 AND
 2017 FBC P SEC. 504.7.1
 19. ICE MAKER, SOAP OR CHEMICAL DISPENSER SHALL HAVE AN
 INLINE BACKFLOW DEVICE AND THE SODA DISPENSER SHALL
 HAVE A CARBONATED BACKFLOW DEVICE AS WELL. EACH DEVICE
 SHALL HAVE ITS OWN SHUT-OFF VALVE FBC P SEC. 608.13.9
 CHEMICAL DISPENSER BACKFLOW DEVICES, 608.16.7 CHEMICAL
 DISPENSERS, 608.16.1 BEVERAGE DISPENSERS.
 20. ISOMETRIC OF THE SANITARY RISER ON P-5.1, (N)P-6
 THE DIRECTION OF FLOW IS INCORRECT. WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
  
  
 PLEASE NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE
 AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-06-28 Cont ID  
Sent By tklarge Date 2019-06-28 Time 13:47 Rev Time 0.00
Received By tklarge Date 2019-06-28 Time 13:46 Sent To  
Notes
2019-06-28 13:48:36GREASE INTERCEPTOR REVIEWED UNDER MASTER PERMIT
 #18020060. T.LARGE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 19:11 Rev Time 0.00
Received By shill Date 2018-05-22 Time 19:11 Sent To  
Notes
2018-05-22 19:11:55PROVISO: A SEPARATE ROOF PERMIT IS REQUIRED. SUBMIT
 APPLICATION WITH ROOF PRODUCT APPROVAL AND ENGINEERING
 IF APPLICABLE. PRODUCT APPROVAL IS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 SIGNED & SEALED RAS117 CALCULATIONS WERE SUBMITTED AND
 THE COVER SHEET FOR DUROLAST WAS SUBMITTED. NEITHER WAS
 REVIEWED BY DESIGNER OF RECORD, EVALUATION REPORT NOT
 SUBMITTED, AND ASSEMBLY NOT SELECTED, SO THESE ITEMS
 ARE BEING RETURNED TO THE APPLICANT.
  
  

Review Stop X PERMIT EXTENSION
Rev No 1 Status P Date 2019-01-30 Cont ID  
Sent By rbrown Date 2019-01-30 Time 18:04 Rev Time 0.00
Received By rbrown Date 2019-01-30 Time 18:04 Sent To  
Notes
2019-01-30 18:07:26RECEIVED LETTER DATED 1/25/19 REQUESTING THAT PERMIT
 APPLICATION BE EXTENDED FOR 90 DAYS AFTER THE 2/28/19
 EXPIRATION DATE WHILE THE TENANT IS IN NEGOTAITIONS
 WITH THE LANDLORD. EXTEND PERMIT APPLICATION UNTIL
 5/28/19.

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-27 Cont ID  
Sent By hmtribou Date 2018-06-27 Time 11:07 Rev Time 0.00
Received By hmtribou Date 2018-06-27 Time 11:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By hmtribou Date 2018-05-17 Time 07:45 Rev Time 0.00
Received By hmtribou Date 2018-05-17 Time 07:45 Sent To I
Notes
2018-05-17 07:46:261. PRIOR TO ISSUANCE OF CERTIFICATE OF COMPLETION ALL
 LANDSCAPING AS SHOWN ON APPROVED PLANS FOR AFFECTED
 AREA, SHALL BE INSTALLED, INSPECTED, AND ACCEPTED.
 ADDITIONALLY, ALL EXISTING LANDSCAPING SHALL BE
 INSPECTED FOR COMPLIANCE WITH THE PREVIOUSLY APPROVED
 PLANS.
  
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-03-02 Cont ID  
Sent By HT Date 2018-03-02 Time 11:16 Rev Time 0.00
Received By hmtribou Date 2018-03-02 Time 11:16 Sent To I
Notes
2018-03-02 11:17:59INFORMAL SITE PLAN REVIEW REQUIRED. SUBMITTED
 APPLICATION SCHEDULED FOR PPRC APRIL 11, 2018.