Plan Review Details - Permit 18020058
Plan Review Stops For Permit 18020058
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-02 Cont ID  
Sent By pleduc Date 2018-02-02 Time   Rev Time 0.00
Received By pleduc Date 2018-02-02 Time 11:57 Sent To M
Notes
2018-02-02 13:19:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE IS NO CLEAR INDICATION OF A MANUAL PULL
 STATION FOR THE SYSTEM. PLEASE ENSURE ONE IS INSTALLED
 PER NFPA 96:
  
 10.5 MANUAL ACTIVATION.
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN.
 AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT
 OF A FIRE, BE LOCATED IN A PATH OF EGRESS, AND CLEARLY
 IDENTIFY THE HAZARD PROTECTED.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M
 (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S)
 WITHIN A PATH OF EGRESS OR AT AN ALTERNATIVE LOCATION
 ACCEPTABLE TO THE AHJ.
 10.5.1.2 MANUAL ACTIVATION USING A CABLE-OPERATED PULL
 STATION SHALL NOT REQUIRE MORE THAN 178 N (40 LB) OF
 FORCE, WITH A PULL MOVEMENT NOT TO EXCEED 356 MM (14
 IN.) TO ACTIVATE THE AUTOMATIC FIRE-EXTINGUISHING
 EQUIPMENT.
  
  
  
 2) ENSURE THAT A FIRE ALARM TECH IS ON SITE WHEN THE
 FIRE INSPETION TEST IS SCHEDULED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-05-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-24 Time 11:47 Sent To  
Notes
2018-04-25 11:47:12RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-04-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-21 Time 13:19 Sent To  
Notes
2018-03-22 13:20:10RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-02-13 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-01 Time 10:21 Sent To  
Notes
2018-02-02 10:21:28ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-05-15 Cont ID  
Sent By ccole Date 2018-05-15 Time 15:15 Rev Time 0.00
Received By ccole Date 2018-05-15 Time 15:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-10 Cont ID  
Sent By ccole Date 2018-05-10 Time 11:16 Rev Time 0.00
Received By ccole Date 2018-05-10 Time 11:13 Sent To I
Notes
2018-05-10 11:24:133RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18020058
 5/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED LETTER FROM KAMM ENGINEERING IS
 ADDRESSING PRESSURIZATION OF THE SPACES RATHER THAN THE
 ISSUE OF TEMPERSATURE OF MAKEUP AIR. PLEASE NOTE THAT
 IF USING THE EXCEPTION IN 508.1.1 THAT THE ADDED
 COOLING LOAD FROM THE MAKEUP AIR DOES NOT EXCEED THE
 CAPACITY OF THE AC SYSTEM, PLEASE STATE THAT CLEARLY IN
 THE LETTER AND PROVIDE CALCULATIONS TO SHOW COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-03 Cont ID  
Sent By ccole Date 2018-04-03 Time 11:20 Rev Time 0.00
Received By ccole Date 2018-04-03 Time 10:58 Sent To I
Notes
2018-04-03 11:26:412ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18020058
 4/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LETTER FROM KAMM ENGINEERING THAT WAS SIGNED BY
 THE PROJECT MANAGER JOHN MAYR DOES NOT ADDRESS COMMENT
 #1 FROM THE 1ST REVIEW. THE SUBMITTED LETTER MAKES THIS
 GENERAL STATEMENT " THE HOOD SYSTEM HAS BEEN TAKEN INTO
 ACCOUNT DURING THE DESIGN OF THE BUILDING HVAC SYSTEM".
 HOWEVER NO EVIDENCE IN THE FORM OF CALCULATIONS, DATA,
 OR EXPLANATORY INFORMATION HAS BEEN PROVIDED TO SHOW
 THE ADDED COOLING LOAD OF THE MAKEUP AIR HAS BEEN
 CALCULATED INTO THE TOTAL DESIGN LOADS FOR SIZING OF
 THE HVAC SYSTEMS. PLEASE NOTE THAT GENERALLY ABOUT 20%
 OF THE SUPPLY AIR PROVIDED FOR THE HOOD IS DIFFUSED
 INTO THE SPACE. THAT IS THE BASIS OF THE REQUIRED
 CALCULATION. I HAVE REPRINTED THE COMMENT BELOW- PLEASE
 SHOW COMPLIANCE.
  
 1) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-13 Cont ID  
Sent By ccole Date 2018-02-13 Time 14:50 Rev Time 0.00
Received By ccole Date 2018-02-13 Time 14:50 Sent To I
Notes
2018-02-13 15:07:371ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18020058
 2/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 2) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOFTOP FANS- SEE SECTION 1609
 FBC-17 BUILDING.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DUCT
 WRAP WITH SHOP DRAWING STAMP BY THE EOR- SECTION
 506.3.11.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
 PLAN REVIEW RESULTS: DENIED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved