| 2018-02-07 11:43:20 | 1ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL, ENERGY |
| | CONSERVATION CODES |
| | PERMIT #18020031 |
| | 2/7/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE CONTRACTOR MUST PROVIDE HIS SIGNATURE AND DATE |
| | ON THE PLAN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC. |
| | |
| | 2) SHOW THE LOCATION AND DIMENSIONS OF THE REQUIRED |
| | ATTIC HATCH TO ACCESS THE AIR HANDLER- SEE SECTION |
| | R403.3.6 FBC-17 ENERGY CONSERVATION FOR ALL |
| | REQUIREMENTS. |
| | |
| | 3) PROVIDE A CONDENSATE DISPOSAL PLAN THAT SHOWS THE |
| | TYPE AND SIZE OF PIPING, AND THE PIPING RUN AND |
| | DISCHARGE LOCATION- M1411.3 FBC-17 RESIDENTIAL. |
| | |
| | 4) ENLARGE THE HURRICAN PAD SUBMITTAL AND INDICATE THE |
| | PAD MODEL NUMBER AND DIMENSIONS OF THE PAD. SUBMIT A |
| | FL. PRODUCT APPROVAL FOR THE TIE DOWN CLIPS. |
| | |
| | 5) AC CALCULATIONS PROJECT SUMMARY: PROVIDE THE MAKE |
| | AND MODEL OF THE THE CONDENSER AND AIR HANDLER IN THE |
| | COOLING EQUIPMENT SUMMARY- SECTION R403.7.1 FBC-17 |
| | ENERGY CONSERVATION. |
| | |
| | 6) THE OWNER/AGENT MUST PROVIDE HIS/HER SIGNATURE ON |
| | THE ENERGY COMPLIANCE FORM R405-2017. |
| | |
| | 7) ADVISORY: PLEASE REVIEW THE REQUIRED COMPLIANCE |
| | TESTS LISTED AT THE BOTTOM OF PAGE 1 OF FORM R405-2017. |
| | MANDATORY ENVELOPE AND DUCT LEAKAGE TESTS REQUIRED FOR |
| | COMPLIANCE WITH R405-2017. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |