Plan Review Details - Permit 18011284
Plan Review Stops For Permit 18011284
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2018-02-28 Time 19:00 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By rmcdouga Date 2018-02-15 Time 07:45 Rev Time 0.00
Received By rmcdouga Date 2018-02-15 Time 07:19 Sent To E
Notes
2018-02-15 07:45:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE AMERICAST GENERATOR PAD DRAWINGS HAVE SEVERAL
 REFERENCES TO THE FBC FIFTH EDITION (2014). THE FBC
 SIXTH EDITION (2017) WENT INTO EFFECT ON JANUARY 1,
 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE
 ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017).HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By jleahy Date 2018-02-15 Time 10:44 Rev Time 0.00
Received By jleahy Date 2018-02-15 Time 10:44 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-02-14 Cont ID  
Sent By lcrespo Date 2018-02-14 Time 15:47 Rev Time 0.00
Received By lcrespo Date 2018-02-14 Time 15:47 Sent To  
Notes
2018-02-14 15:52:042/14/18 APPROVED BY PLUMBING, PUT BACK IN GENERATOR
 BIN, LAC

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-09 Cont ID  
Sent By cpuell Date 2018-03-09 Time 14:55 Rev Time 0.00
Received By cpuell Date 2018-03-07 Time 10:12 Sent To  
Notes
2018-03-08 10:13:04RESUB ROUTED TO PGREILIC VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2018-02-21 Time 11:40 Sent To  
Notes
2018-02-22 11:40:24RESUB ROUTED TO PGREILIC VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-15 Cont ID  
Sent By jleahy Date 2018-02-15 Time 10:45 Rev Time 0.00
Received By jleahy Date 2018-01-31 Time 11:27 Sent To  
Notes
2018-02-01 11:28:03ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-03-09 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-09 Time 09:08 Sent To  
Notes
2018-03-09 09:09:191.) LANDSDCAPE SCREENING REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-02-27 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-26 Time 15:58 Sent To B
Notes
2018-02-27 15:28:10REPEAT COMMENT
  
 SEC. 94-305. - SETBACKS.
 (4) MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW
 AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18
 INCHES INTO A REQUIRED SIDE SETBACK
  
 SEC. 94-81. - HISTORIC SINGLE-FAMILY HIGH DENSITY
 RESIDENTIAL, CONTEXT 2 (SF14-C2, MF14-C2).
 (2) MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 A. FRONT: THE FRONT SETBACK SHALL BE A CONTEXTUAL FRONT
 SETBACK PROVIDED IN ACCORDANCE WITH SECTION 94-79(B).
 WHERE A CONTEXTUAL FRONT SETBACK HAS NOT BEEN
 ESTABLISHED, THE MINIMUM FRONT SETBACK SHALL BE 25
 FEET. B. CORNER: 1. FOR LOTS UP TO 4,999 SQUARE FEET:
 10 FEET; 2. FOR LOTS 5,000 TO 7,499 SQUARE FEET: 12.5
 FEET; 3. FOR LOTS 7,500 SQUARE FEET AND OVER: 15 FEET.
 C. REAR: 15 FEET, OR 10 PERCENT OF THE LOT DEPTH,
 WHICHEVER IS LESS. D. SIDE MINIMUM (ONE SIDE ONLY): 1.
 FOR LOTS UP TO 7,499 SQUARE FEET: 5 FEET; 2. FOR LOTS
 7,500 SQUARE FEET AND OVER: 10 FEET. E. SIDE MINIMUM
 CUMULATIVE (BOTH SIDES): 1. FOR LOTS UP TO 7,499 SQUARE
 FEET: 15 FEET; 2. FOR LOTS 7,500 SQUARE FEET AND OVER:
 20 FEET.
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By PG Date 2018-02-09 Time 11:15 Rev Time 0.00
Received By pgreilic Date 2018-02-07 Time 10:36 Sent To  
Notes
2018-02-09 11:17:02SEC. 94-305. - SETBACKS.
  
  
 (4) MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW
 AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18
 INCHES INTO A REQUIRED SIDE SETBACK
  
  
 SEC. 94-81. - HISTORIC SINGLE-FAMILY HIGH DENSITY
 RESIDENTIAL, CONTEXT 2 (SF14-C2, MF14-C2).
  
 (2) MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 A. FRONT: THE FRONT SETBACK SHALL BE A CONTEXTUAL FRONT
 SETBACK PROVIDED IN ACCORDANCE WITH SECTION 94-79(B).
 WHERE A CONTEXTUAL FRONT SETBACK HAS NOT BEEN
 ESTABLISHED, THE MINIMUM FRONT SETBACK SHALL BE 25
 FEET. B. CORNER: 1. FOR LOTS UP TO 4,999 SQUARE FEET:
 10 FEET; 2. FOR LOTS 5,000 TO 7,499 SQUARE FEET: 12.5
 FEET; 3. FOR LOTS 7,500 SQUARE FEET AND OVER: 15 FEET.
 C. REAR: 15 FEET, OR 10 PERCENT OF THE LOT DEPTH,
 WHICHEVER IS LESS. D. SIDE MINIMUM (ONE SIDE ONLY): 1.
 FOR LOTS UP TO 7,499 SQUARE FEET: 5 FEET; 2. FOR LOTS
 7,500 SQUARE FEET AND OVER: 10 FEET. E. SIDE MINIMUM
 CUMULATIVE (BOTH SIDES): 1. FOR LOTS UP TO 7,499 SQUARE
 FEET: 15 FEET; 2. FOR LOTS 7,500 SQUARE FEET AND OVER:
 20 FEET.
  
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]