Plan Review Details - Permit 18011280
Plan Review Stops For Permit 18011280
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By rmcdouga Date 2018-03-15 Time 18:53 Rev Time 0.00
Received By rmcdouga Date 2018-03-15 Time 18:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2018-03-08 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By rmcdouga Date 2018-02-14 Time 07:18 Rev Time 0.00
Received By rmcdouga Date 2018-02-14 Time 06:41 Sent To  
Notes
2018-02-14 07:22:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE AMERICAST GENERATOR PAD PLANS HAVE SEVERAL
 REFERENCES TO THE FBC FIFTH EDITION (2014). THE FBC
 SIXTH EDITION (2017) WENT INTO EFFECT ON JANUARY 1,
 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE
 ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017).

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By jleahy Date 2018-02-15 Time 10:48 Rev Time 0.00
Received By jleahy Date 2018-02-15 Time 10:48 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By lcrespo Date 2018-03-15 Time 16:13 Rev Time 0.00
Received By lcrespo Date 2018-03-15 Time 16:13 Sent To B
Notes
2018-03-15 16:15:2503/15/18 APPROVED BY PLUMBING AND SENT TO BUILDING RM,
 LAC

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-07 Cont ID  
Sent By tklarge Date 2018-03-07 Time 10:28 Rev Time 0.00
Received By tklarge Date 2018-03-06 Time 06:36 Sent To  
Notes
2018-03-07 10:28:241) THE PIPING SYSTEM SHALL BE SIZED TO MEET THE MAXIMUM
 DEMAND TO EACH APPLIANCE. 2017 FBC-FUEL GAS SECS.
 402.1, 402.2.. THE GAS PLAN SHOWS A BTU LOAD OF 191,000
 BTU'S YET THE GENERATOR SPECS SHOW A BTU LOAD OF
 300,000 BTU'S AT FULL LOAD. THE GAS SYSTEM SHALL BE
 SIZED FOR THE 300,000 BTU LOAD.
 2) THE GAS PLAN SHOWS A 1/2 LB. PRESSURE GAS SYSTEM BUT
 THE SUBMITTED SITE PLAN SHOWS A 2 PSI GAS METER.
 CLARIFY.
 3) THE GAS PLAN SHOWS A NATURAL GAS METER AND NOTES A
 NATURAL GAS SYSTEM, BUT THE PLAN ALSO NOTES AN LP GAS
 SYSTEM. CLARIFY.
 4) IF THIS IS TO BE A 1/2 LB. GAS SYSTEM, THE ENTIRE
 PIPING SYSTEM IS UNDERSIZED. COMPLY WITH 2017 FBC-FUEL
 GAS SEC.402.3.
 5) THE SUBMITTED GAS TABLES ARE BOTH FOR LESS THAN A 2
 PSI SYSTEM, BUT THE SITE PLAN SHOWS A 2 PSI METER.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By thunt Date 2018-02-16 Time 07:08 Rev Time 0.00
Received By thunt Date 2018-02-16 Time 07:08 Sent To  
Notes
2018-02-16 07:26:4002/16/2018 GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) GAS REGULATOR MANUAL PROVIDED IS MISSING PAGES 4-10.
 COMPLETE MANUAL IS REQUIRED, 2017 FBC- FUEL GAS 410.1
  
 2) REQUIRED SEDIMENT TRAP FOR THE GENERATOR IS MISSING
 ON YOUR ISOMETRIC PLAM AND I WAS UNABLE TO LOCATE ONE
 BUILT IN THE GENERATOR FROM THE MANUAL SUPPLIED. 2017
 FBC FUEL GAS 408.4
  
 3) YOUR ISOMETRIC DRAWING LIST THE CORRECT 2017 FBC
 FUEL AND GAS CODE BUT THE COPIES OF THE SIZING CHARTS
 PROVIDED SHOW 2014. PROVIDE CORRECT COPIES LISTED AS
 2017. FBC 107.2.1
  
 4) YOUR ISOMETRIC PLAN SHOW A NEW 500 GALLON L.P TANK
 BUT ON YOUR FLAT DRAWING YOU SHOW A NEW NAT GAS METER
 AS BEING THE SOURCE OF GAS PROVIDED. PLEASE CLARIFY
 WHICH GAS IS BEING USED. FBC 107.2.1
  
 5) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 6) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED
 PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK
 SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT
 WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 7) ) SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW
 GRADE. COMPLY WITH NFPA 58 SEC. 6.6.6.1.
  
 8) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
  
 9) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 10) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-03-27 Cont ID  
Sent By lmarchan Date 2018-03-27 Time 13:17 Rev Time 0.00
Received By lmarchan Date 2018-03-21 Time 13:12 Sent To  
Notes
2018-03-22 13:12:51RESUB ROUTED TO PGREILIC VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-15 Cont ID  
Sent By rmcdouga Date 2018-03-15 Time 18:55 Rev Time 0.00
Received By rmcdouga Date 2018-03-13 Time 13:13 Sent To I
Notes
2018-03-14 13:13:18RESUB ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2018-02-27 Time 09:28 Sent To  
Notes
2018-02-28 09:28:51RESUB ROUTED TO PGREILIC VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-16 Cont ID  
Sent By thunt Date 2018-02-16 Time 07:26 Rev Time 0.00
Received By thunt Date 2018-02-16 Time 07:26 Sent To I
Notes
2018-02-01 11:24:46ROUTED TO ZONING

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2018-03-27 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-27 Time 08:37 Sent To  
Notes
2018-03-27 08:38:161.) PROVIDE REQUIRED LANDSCAPE SCREENING
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2018-03-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-14 Time 15:26 Sent To G
Notes
2018-03-14 15:27:151.) MECHANICAL EQUIPMENT CANNOT ENCROACH MORE THAN 4
 FEET INTO REQUIRED SETBACKS. 21 FEET MINIMUM NEEDED
 FROM NORTH AND SOUTH PROPERTY LINES
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-03-02 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-02 Time 10:55 Sent To G
Notes
2018-03-02 10:55:41FAILED
  
 1.) MECHANICAL EQUIPMENT SHALL NOT ENCROACH MORE THAN 4
 FEET INTO REQUIRED SETBACKS
 2.) LANDSCAPE SCREENING REQUIRED. SHOW ON PLAN
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-13 Cont ID  
Sent By PG Date 2018-02-13 Time 09:01 Rev Time 0.00
Received By pgreilic Date 2018-02-07 Time 10:35 Sent To  
Notes
2018-02-13 09:03:07FAILED
  
 1.) LABEL SETBACK FOR PROPOSED GENERATOR. MECHANICAL
 EQUIPMENT SHALL NOT ENCROACH MORE THAN 4 FEET INTO
 REQUIRED SIDE SETBACK
 2.) LANDSCAPE SCREENING REQUIRED. SHOW ON PLAN
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]