Plan Review Details - Permit 18011120
| Plan Review Stops For Permit 18011120 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-02-12 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-02-12 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-02-12 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2018-02-12 13:48:42 | 2/12/18 APPROVED BY PLUMBING AND SENT TO PROCESSING, | | | LAC |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-02-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-02-02 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-02-02 |
Time |
04:54 |
Sent To |
I |
|
| Notes |
| 2018-02-02 06:35:02 | 1) SUBMIT MANUFACTURING SPECIFICATIONS FOR THE | | | GENERATOR.WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) THE UNDERGROUND TANK IS SHOWN IN THE MIDDLE OF | | | DRIVEWAY ON THE SURVEY. INDICATE HOW THE LP TANK IS | | | GOING TO BE PROTECTED FROM DAMAGE. PROTECTION SHALL BE | | | PROVIDED IN ACCCORDANCE WITH 2014 NFPA 58 SEC.6.6.6.1 | | | (E). | | | NFPA 58 - 6.6.6.1* ASME CONTAINER ASSEMBLIES INTENDED | | | FOR UNDERGROUND INSTALLATION, INCLUDING INTERCHANGEABLE | | | ABOVEGROUND ? UNDERGROUND CONTAINER ASSEMBLIES, SHALL | | | BE INSTALLED UNDERGROUND IN ACCORDANCE WITH 6.6.6.1(A) | | | THROUGH 6.6.6.1(M). | | | (E) THE INSTALLATION OF A BURIED CONTAINER SHALL | | | INCLUDE PROTECTION | | | FOR THE CONTAINER AND PIPING AGAINST PHYSICAL DAMAGE | | | FROM VEHICULAR TRAFFIC. | | | 3) INDICATE HOW THE FIRST STAGE REGULATOR IS GOING TO | | | BE VENTED WHEN THE TANK IS IN THE MIDDLE OF THE | | | DRIVEWAY.THE VENT SHALL COMPLY WITH NFPA 58 SEC. | | | 6.6.6.1 ( H) - THE DISCHARGE OF THE REGULATOR VENT | | | SHALL BE ABOVE THE | | | HIGHEST PROBABLE WATER LEVEL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-02-12 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-02-12 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-02-07 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2018-02-08 10:16:09 | RESUB RUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-02-02 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-01-29 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2018-01-30 11:24:36 | ROUTED TO PLUMBING INBOX |
|
|
|