Plan Review Details - Permit 18011084
Plan Review Stops For Permit 18011084
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-12 Cont ID  
Sent By jgomez Date 2018-03-12 Time 10:28 Rev Time 0.00
Received By jgomez Date 2018-03-12 Time 09:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-05 Cont ID  
Sent By jgomez Date 2018-03-05 Time 15:32 Rev Time 0.00
Received By jgomez Date 2018-03-05 Time 12:15 Sent To  
Notes
2018-03-05 12:32:20RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1-DRAWING 04 OF 13 OF ACCORDION SHUTTERS SUBMITTED
 DOESN'T CORRESPOND TO THE REST OF DRAWINGS SUBMITTED.
 DRAWING 04 OF 13 SUBMITTED CORRESPONDS TO DRAWING #
 15-112. THE DRAWING THAT CORRESPONDS TO FLORIDA PRODUCT
 APPROVAL FL 16893-R3 SUBMITTED IS DRAWING #17-666.
 PROVIDE COMPLETE AND CORRECT SET OF DRAWINGS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-01 Cont ID  
Sent By jgomez Date 2018-02-01 Time 11:45 Rev Time 0.00
Received By jgomez Date 2018-02-01 Time 11:26 Sent To  
Notes
2018-02-01 11:52:08RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- WIND LOAD CALCULATIONS SUBMITTED:
 A) NEED TO HAVE THE ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 B) REVISE THE MINIMUM EDGE DISTANCE. ACCORDING TO
 FOOTNOTE OF FIGURE R301.2(7) FBC-RESIDENTIAL, 6TH
 EDITION (2017) THE MINIMUM EDGE DISTANCE "A" IS 4'-0"
 IN ALL CASES NOT 3'-0". REVISE AS REQUIRED.
  
 2- REVISE INSTALLATION SCHEDULE SUBMITTED.
 A) OPENING #2 SPECIFY ANCHOR TYPE "A" WITH A SPACING OF
 14" O.C. AT THE BOTTOM. ACCORDING TO ANCHOR SCHEDULE
 TABLE ON PAGE 11 OF 13 OF ACCORDION SHUTTERS SUBMITTED
 THIS ANCHOR REQUIRES 3.000PSI CONCRETE STRENGTH. IT
 LOOKS LIKE THE BUILD OUT TRACK IS GOING TO BE MOUNTED
 ON THE EDGE OF THE CONCRETE SLAB. TYPICALLY THE
 CONCRETE SLABS FOR RESIDENTIAL PROJECTS ARE DESIGNED
 FOR 2500PSI CONCRETE STRENGTH. REVISE THE ANCHOR TYPE
 AND SPACING OR PROVIDE PROOF THAT THE CONCRETE STRENGTH
 IS 3.000PSI. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) INSTALLATION SCHEDULE IS MISSING THE EDGE DISTANCE
 DIMENSION. PROVIDE THE EDGE DISTANCE DIMENSION. NOTE:
 THE FASTENER EDGE DISTANCE EXCLUDES THE STUCCO FINISH.
 SEE NOTES ON ANCHOR SCHEDULE TABLE ON SHEET 11 OF 13.
 ADD THE STUCCO THICKNESS TO THE EDGE DISTANCE ON THE
 INSTALLATION SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) SPECIFY LENGTH OF ANCHORS TO VERIFY MINIMUM
 EMBEDMENT REQUIRED ON ANCHOR SCHEDULE TABLE ON SHEET 11
 OF 13. SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-12 Cont ID  
Sent By jgomez Date 2018-03-12 Time 10:28 Rev Time 0.00
Received By jgomez Date 2018-03-07 Time 10:04 Sent To I
Notes
2018-03-08 10:04:24RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-05 Cont ID  
Sent By jgomez Date 2018-03-05 Time 15:44 Rev Time 0.00
Received By jgomez Date 2018-02-23 Time 09:23 Sent To I
Notes
2018-02-26 09:23:30RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-01 Cont ID  
Sent By jgomez Date 2018-02-01 Time 11:52 Rev Time 0.00
Received By jgomez Date 2018-01-26 Time 11:26 Sent To I
Notes
2018-01-29 11:26:29BLDG <5K