Plan Review Details - Permit 18011081
Plan Review Stops For Permit 18011081
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-02-20 Cont ID  
Sent By shill Date 2018-02-20 Time 08:32 Rev Time 0.00
Received By shill Date 2018-02-20 Time 06:24 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-14 Cont ID  
Sent By jpearson Date 2018-02-14 Time 14:50 Rev Time 0.00
Received By jpearson Date 2018-02-14 Time 07:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-01 Cont ID  
Sent By pleduc Date 2018-02-01 Time   Rev Time 0.00
Received By pleduc Date 2018-02-01 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-06 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-22 Time 15:21 Sent To  
Notes
2018-02-22 15:21:23RESUB OF REVISION ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-20 Cont ID  
Sent By shill Date 2018-02-20 Time 08:32 Rev Time 0.00
Received By shill Date 2018-01-26 Time 13:39 Sent To  
Notes
2018-01-31 13:39:25C16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By ccole Date 2018-03-06 Time 08:02 Rev Time 0.00
Received By ccole Date 2018-03-06 Time 07:13 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-12 Cont ID  
Sent By ccole Date 2018-02-12 Time 09:11 Rev Time 0.00
Received By ccole Date 2018-02-09 Time 16:44 Sent To  
Notes
2018-02-12 09:32:211ST REVIEW FBC-2014 MECHANICAL
 REVISION #18011081
 MASTER #16090832
 2/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-222: MISSING FIRE DAMPERS FOR DUCTS
 PENETRATING THE FIRE-RATED MECHANICAL ROOM/FUTURE
 EXPANSION AREA WALL- SECTION 607.5.2.
  
 2) SUBMIT TWO COPIES OF THE O/A LOUVER PRODUICT
 APPROVAL OR NOA WITH APPROVAL STAMP BY THE EOR.
  
 3) INDICATE COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION FOR REQUIRED AUTOMATIC CONTROL OF
 THE OUTSIDE AIRFLOW TO THE AIR HANDLER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  