Plan Review Details - Permit 18011080
Plan Review Stops For Permit 18011080
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-19 Cont ID  
Sent By rmcdouga Date 2018-03-19 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2018-03-19 Time 17:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-26 Cont ID  
Sent By rmcdouga Date 2018-02-26 Time 18:04 Rev Time 0.00
Received By rmcdouga Date 2018-02-26 Time 18:00 Sent To I
Notes
2018-02-26 18:04:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS HAVE SEVERAL REFERENCES
 TO THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017).
  
 2) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR AND THE
 TRANSFER SWITCH. FBC 107.2.1
  
 3) THE PROJECT IS LOCATED IN FLOOD ZONE AE, WHICH IS A
 SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND EQUIPMENT
 IS REQUIRED TO BE LOCATED ABOVE THE REQUIRED BASE FLOOD
 ELEVATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By rmcdouga Date 2018-02-08 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2018-02-08 Time 06:49 Sent To P
Notes
2018-02-08 07:35:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS HAVE SEVERAL REFERENCES
 TO THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017).
  
 2) THE DRAWINGS FOR THE GENERATOR PAD ARE REQUIRED TO
 BE SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER.
 FBC 107.1
  
 3) THE AMERICAST GENERATOR PAD DRAWINGS THAT WERE
 SUBMITTED ARE FROM AN ENGINEER WITH A LICENSE THAT HAS
 BEEN REVOKED. RONALD H. WILSON'S FLORIDA PE LICENSE WAS
 REVOKED ON 2/28/2017.
  
 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR AND THE
 TRANSFER SWITCH. FBC 107.2.1
  
 5) THE PROJECT IS LOCATED IN FLOOD ZONE AE, WHICH IS A
 SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND EQUIPMENT
 IS REQUIRED TO BE LOCATED ABOVE THE REQUIRED BASE FLOOD
 ELEVATION.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-04-16 Cont ID  
Sent By jleahy Date 2018-04-16 Time 17:12 Rev Time 0.00
Received By jleahy Date 2018-04-16 Time 17:12 Sent To  
Notes
2018-04-16 17:13:26PLEASE RAISE VALUE TO $20,000 PER FORMER NOTE TO
 CONTRACTOR. JLEAHY

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-03-19 Cont ID  
Sent By jleahy Date 2018-03-19 Time 09:03 Rev Time 0.00
Received By jleahy Date 2018-03-19 Time 09:03 Sent To B
Notes
2018-03-19 11:00:27FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PASS ZONING FOR ELECTRICAL PASS.
  
 DID NOT REALIZE THAT THE PANELS WERE BEING CHANGED OUT
 SO VALUE WILL BE RAISED TO $20,000 IIF NO CONTRACT IS
 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-02-26 Cont ID  
Sent By jleahy Date 2018-02-26 Time 09:08 Rev Time 0.00
Received By jleahy Date 2018-02-26 Time 09:08 Sent To  
Notes
2018-02-26 09:13:26FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 SUBMIT CUT SHEETS FOR THE GENERATOR AND TRANSFER
 SWITCH.
  
 VALUE OF THE WORK TOO LOW BASED ON THE VALUE OF OTHER
 PERMITS OF THIS SIZE GENERATOR.
  
 IF NO CONTRACT IS SUPPLIED A VALUE OF $12,000 WILL BE
 ASSESSED TO THIS PERMIT.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By jleahy Date 2018-02-06 Time 07:49 Rev Time 0.00
Received By jleahy Date 2018-02-06 Time 07:46 Sent To B
Notes
2018-02-06 07:48:36FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR WORK SHOWN IS LOW, PLEASE SUPPLY A SIGNED
 CONTRACT.
  
 VALUATION
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-19 Cont ID  
Sent By rmcdouga Date 2018-03-19 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2018-03-02 Time 08:00 Sent To  
Notes
2018-03-06 08:00:38RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-26 Cont ID  
Sent By rmcdouga Date 2018-02-26 Time 18:04 Rev Time 0.00
Received By rmcdouga Date 2018-02-20 Time 10:14 Sent To  
Notes
2018-02-21 10:15:05RESUB ROUTED TO LLOUIE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-08 Cont ID  
Sent By rmcdouga Date 2018-02-08 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2018-01-26 Time 12:51 Sent To  
Notes
2018-01-29 12:51:48ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-02-08 Cont ID  
Sent By thunt Date 2018-02-08 Time 13:15 Rev Time 0.00
Received By thunt Date 2018-02-08 Time 13:15 Sent To  
Notes
2018-02-08 13:17:00 
 A PLUMBING PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A PLUMBING PLAN REVIEW HAS NOT BEEN PERFORMED
 AT THIS TIME. PLUMBING PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF
 PLUMBING WORK TO BE DONE AT THIS TIME. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BEIS
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2018-04-12 Cont ID  
Sent By ajones Date 2018-04-12 Time 15:56 Rev Time 0.00
Received By ajones Date 2018-04-12 Time 15:56 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2018-03-14 Cont ID  
Sent By ajones Date 2018-03-14 Time 11:29 Rev Time 0.00
Received By ajones Date 2018-03-06 Time 17:30 Sent To E
Notes
2018-03-14 11:30:233/14/18- REPEAT COMMENT. GENERATOR CAN NOT BE PLACED
 WITHIN THE UTILITY EASTMENT.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2018-02-22 Cont ID  
Sent By LL Date 2018-02-22 Time   Rev Time 0.00
Received By llouie Date 2018-02-22 Time 10:50 Sent To PC
Notes
2018-02-22 15:34:30** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) LOCATION OF THE GENERATOR CANNOT BE PLACED WITHIN A
 PUBLIC UTILITY EASEMENT. [REPEAT COMMENT FROM 2/2/18]
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By LL Date 2018-02-02 Time   Rev Time 0.00
Received By llouie Date 2018-01-31 Time 13:42 Sent To E
Notes
2018-02-02 11:04:24** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) LOCATION OF THE GENERATOR CANNOT BE PLACED WITHIN A
 PUBLIC UTILITY EASEMENT.
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  