| Plan Review Stops For Permit 18011080 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-19 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-19 |
Time |
17:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-02-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-02-26 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-02-26 |
Time |
18:00 |
Sent To |
I |
|
| Notes |
| 2018-02-26 18:04:08 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWINGS HAVE SEVERAL REFERENCES | | | TO THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION | | | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW | | | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED | | | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION | | | (2017). | | | | | | 2) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | | AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR AND THE | | | TRANSFER SWITCH. FBC 107.2.1 | | | | | | 3) THE PROJECT IS LOCATED IN FLOOD ZONE AE, WHICH IS A | | | SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND EQUIPMENT | | | IS REQUIRED TO BE LOCATED ABOVE THE REQUIRED BASE FLOOD | | | ELEVATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-02-08 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-02-08 |
Time |
06:49 |
Sent To |
P |
|
| Notes |
| 2018-02-08 07:35:58 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWINGS HAVE SEVERAL REFERENCES | | | TO THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION | | | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW | | | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED | | | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION | | | (2017). | | | | | | 2) THE DRAWINGS FOR THE GENERATOR PAD ARE REQUIRED TO | | | BE SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER. | | | FBC 107.1 | | | | | | 3) THE AMERICAST GENERATOR PAD DRAWINGS THAT WERE | | | SUBMITTED ARE FROM AN ENGINEER WITH A LICENSE THAT HAS | | | BEEN REVOKED. RONALD H. WILSON'S FLORIDA PE LICENSE WAS | | | REVOKED ON 2/28/2017. | | | | | | 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | | AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR AND THE | | | TRANSFER SWITCH. FBC 107.2.1 | | | | | | 5) THE PROJECT IS LOCATED IN FLOOD ZONE AE, WHICH IS A | | | SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND EQUIPMENT | | | IS REQUIRED TO BE LOCATED ABOVE THE REQUIRED BASE FLOOD | | | ELEVATION. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-04-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-04-16 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-04-16 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2018-04-16 17:13:26 | PLEASE RAISE VALUE TO $20,000 PER FORMER NOTE TO | | | CONTRACTOR. JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-19 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-19 |
Time |
09:03 |
Sent To |
B |
|
| Notes |
| 2018-03-19 11:00:27 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASS ZONING FOR ELECTRICAL PASS. | | | | | | DID NOT REALIZE THAT THE PANELS WERE BEING CHANGED OUT | | | SO VALUE WILL BE RAISED TO $20,000 IIF NO CONTRACT IS | | | SUBMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-02-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-26 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-02-26 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2018-02-26 09:13:26 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | SUBMIT CUT SHEETS FOR THE GENERATOR AND TRANSFER | | | SWITCH. | | | | | | VALUE OF THE WORK TOO LOW BASED ON THE VALUE OF OTHER | | | PERMITS OF THIS SIZE GENERATOR. | | | | | | IF NO CONTRACT IS SUPPLIED A VALUE OF $12,000 WILL BE | | | ASSESSED TO THIS PERMIT. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-02-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-06 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-02-06 |
Time |
07:46 |
Sent To |
B |
|
| Notes |
| 2018-02-06 07:48:36 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE FOR WORK SHOWN IS LOW, PLEASE SUPPLY A SIGNED | | | CONTRACT. | | | | | | VALUATION | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-19 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-02 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2018-03-06 08:00:38 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-02-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-02-26 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-02-20 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2018-02-21 10:15:05 | RESUB ROUTED TO LLOUIE VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-02-08 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-01-26 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2018-01-29 12:51:48 | ROUTED TO ZONING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-08 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-02-08 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-02-08 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2018-02-08 13:17:00 | | | | A PLUMBING PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A PLUMBING PLAN REVIEW HAS NOT BEEN PERFORMED | | | AT THIS TIME. PLUMBING PERMIT IS REQUIRED FOR A | | | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE | | | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF | | | PLUMBING WORK TO BE DONE AT THIS TIME. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | | | | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BEIS | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE | | | ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | | | | | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2018-04-12 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2018-04-12 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-04-12 |
Time |
15:56 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2018-03-14 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2018-03-14 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-03-06 |
Time |
17:30 |
Sent To |
E |
|
| Notes |
| 2018-03-14 11:30:23 | 3/14/18- REPEAT COMMENT. GENERATOR CAN NOT BE PLACED | | | WITHIN THE UTILITY EASTMENT. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-02-22 |
|
|
Cont ID |
|
| Sent By |
LL |
Date |
2018-02-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-02-22 |
Time |
10:50 |
Sent To |
PC |
|
| Notes |
| 2018-02-22 15:34:30 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) LOCATION OF THE GENERATOR CANNOT BE PLACED WITHIN A | | | PUBLIC UTILITY EASEMENT. [REPEAT COMMENT FROM 2/2/18] | | | | | | NOTES: | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-02-02 |
|
|
Cont ID |
|
| Sent By |
LL |
Date |
2018-02-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-01-31 |
Time |
13:42 |
Sent To |
E |
|
| Notes |
| 2018-02-02 11:04:24 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) LOCATION OF THE GENERATOR CANNOT BE PLACED WITHIN A | | | PUBLIC UTILITY EASEMENT. | | | | | | NOTES: | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|