Plan Review Details - Permit 18010961
Plan Review Stops For Permit 18010961
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2018-03-08 Time 07:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 18:33 Rev Time 0.00
Received By rmcdouga Date 2018-02-28 Time 18:33 Sent To I
Notes
2018-02-28 18:34:53PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE AMERICAST GENERATOR PAD PLANS HAVE SEVERAL
 REFERENCES TO THE FBC FIFTH EDITION (2014). THE FBC
 SIXTH EDITION (2017) WENT INTO EFFECT ON JANUARY 1,
 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE
 ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017). FS CHAPTER 553
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By rmcdouga Date 2018-02-08 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2018-02-08 Time 07:47 Sent To E
Notes
2018-02-08 07:49:07PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF GENERATOR ANCHORING AND GENERATOR
 PAD DETAILS. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-26 Cont ID  
Sent By jleahy Date 2018-02-26 Time 13:08 Rev Time 0.00
Received By jleahy Date 2018-02-26 Time 13:08 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By jleahy Date 2018-02-08 Time 08:17 Rev Time 0.00
Received By jleahy Date 2018-02-08 Time 08:17 Sent To I
Notes
2018-02-08 08:18:45FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TWO COPIES OF TRANSFER SWITCH CUT SHEETS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-02-26 Cont ID  
Sent By thunt Date 2018-02-26 Time 15:34 Rev Time 0.00
Received By thunt Date 2018-02-26 Time 15:34 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By tklarge Date 2018-02-08 Time 06:20 Rev Time 0.00
Received By tklarge Date 2018-02-07 Time 06:36 Sent To  
Notes
2018-02-08 05:52:241) SHOW THE DISTANCE OF THE GENERATOR FROM THE
 STRUCTURE ON BOTH COPIES OF THE SURVEY. THE GENERATOR
 DISTANCE SHALL COMPLY WITH MANUFACTURER'S INSTALLATION
 REQUIREMENTS AND NFPA 37.
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, FOR EACH PIPE SIZE. WPB AMENDMENTS TO FBC
 SEC.107.2.1.
 4) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2017 FBC-RES. SEC. G2413.
 5).SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4.
 9) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FGC SEC.410.1.
 10) THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL
 2200. THE SPECIFICATIONS FOR THE GENERATOR THAT THE
 LISTING IS FOR THE 60 HZ ONLY. INDICATE THE HZ OF THIS
 UNIT. 2017 FBC-FUEL GAS SEC. 616.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2018-03-06 Time 13:11 Sent To  
Notes
2018-03-07 13:11:44RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-28 Cont ID  
Sent By rmcdouga Date 2018-02-28 Time 18:33 Rev Time 0.00
Received By rmcdouga Date 2018-02-15 Time 13:12 Sent To  
Notes
2018-02-16 13:12:45RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-08 Cont ID  
Sent By jleahy Date 2018-02-08 Time 08:17 Rev Time 0.00
Received By jleahy Date 2018-01-25 Time 10:15 Sent To  
Notes
2018-01-26 10:15:17ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2018-02-22 Cont ID  
Sent By AW Date 2018-02-22 Time   Rev Time 0.00
Received By awooten Date 2018-02-22 Time 10:43 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By AW Date 2018-02-02 Time 12:10 Rev Time 0.00
Received By awooten Date 2018-01-31 Time 13:27 Sent To  
Notes
2018-02-02 12:10:03**************************ZONING REVIEW
 FAILED***********************************
  
 PLEASE INDICATE THE MINIMUM 5 FOOT REAR SETBACK FOR THE
 GENERATOR ON THE SURVEY.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]