Plan Review Details - Permit 18010936
Plan Review Stops For Permit 18010936
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-06-14 Cont ID  
Sent By jgomez Date 2018-06-14 Time 18:25 Rev Time 0.00
Received By jgomez Date 2018-06-14 Time 17:14 Sent To  
Notes
2018-06-14 18:33:38BUILDING REVIEW APPROVED WITH PROVISO (DEFERRED
 SUBMITTAL):
 1- SUBMIT ALL PRODUCT APPROVALS FOR ALL DOORS, WINDOWS,
 MULLIONS, STOREFRONT, ETC. APPROVED BY THE ARCHITECT OF
 RECORD.
 NOTE: ENTRANCE DOOR NOA 17-1114.01 SUBMITTED. CLEARLY
 SPECIFY DOOR AND GLASS TYPE AS REQUIRED BY THE
 INSTRUCTIONS ON DRAWING W17-54 SUBMITTED.
  
 2- CLEARLY IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY
 ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER
 OF RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER'S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-26 Cont ID  
Sent By jgomez Date 2018-05-25 Time 18:07 Rev Time 0.00
Received By jgomez Date 2018-05-25 Time 15:29 Sent To  
Notes
2018-05-25 15:40:41CHANGE OF OF OCCUPANCY TO INSTITUTIONAL I-1 (CONDITION
 1) , THIRD BUILDING REVIEW CHECKLIST
 CODE: FBC 6TH EDITION (2017).
  
 1- ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM
 CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE
 COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE
 ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED
 LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY
 EXCEEDS TWENTY-FOUR HOURS.
  
 RESPONSE:
 REPEAT COMMENT. PARTIALLY ADDRESSED. PASSENGER LOADING
 ZONE LOCATION WAS REVISED ON THE PLOT PLAN BUT NEEDS TO
 COMPLY WITH THE LENGTH (SEC. 503.3.2), MARKING (SEC.
 503.3.3) AND FLOOR AND GROUND SURFACES. HANDICAP RAMP
 DETAIL PROVIDED ON SHEET P-1 DOESN'T APPLY TO THE FLOOR
 AND GROUND SURFACE SEC. 503.4. REVISE AS REQUIRED.
  
 2- ORIGINAL COMMENT:
 UNISEX RESTROOM AND ADJACENT BATHROOM DON'T COMPLY WITH
 THE OVERLAP REQUIREMENTS OF SEC. 604.3.2
 FBC-ACCESSIBILITY.
 AND WITH RESTROOM FIXTURE CLEARANCE DETAIL SHOWN ON
 SHEET A-5. REVISE AS REQUIRED.
 (NOTE: SHOWER IS NOT DRAWN TO SCALE IN THIS ROOM. ALSO,
 SOME ROOMS AND CORRIDORS ARE NOT DRAWN TO THE SPECIFIED
 DIMENSIONS. PLEASE VERIFY THAT ALL SPECIFIED DIMENSIONS
 WILL BE PROVIDED IN FIELD TO AVOID CONFLICTS/DELAYS).
  
 RESPONSE:
 REPEAT COMMENT. THE LAVATORY REVISED POSITION DOESN'T
 ALLOW A FORWARD APPROACH AS REQUIRED BY SEC. 606.2
 FBC-ACCESSIBILITY. ALSO, UNISEX RESTROOM AND ADJACENT
 BATHROOM DON'T COMPLY WITH THE OVERLAP REQUIREMENTS OF
 SEC. 604.3.2 FBC-ACCESSIBILITY AND WITH RESTROOM
 FIXTURE CLEARANCE DETAIL SHOWN ON SHEET A-5. REVISE AS
 REQUIRED. THE DOTTED LINE SHOWING THE WATER CLOSET AND
 LAVATORY CLEARANCE ARE NOT DRAWN TO SCALE. BESIDES,
 SHEET A-2 DOESN'T PROVIDE THE DIMENSIONS FOR THESE
 ROOMS. THEREFORE, I AM UNABLE TO VERIFY COMPLIANCE.
 SCALING DRAWINGS IS NOT ALLOWED. WRITTEN DIMENSIONS
 TAKE PRECEDENCE. REVISE PLANS AS REQUIRED.
 NOTE: THERE ARE MANY AREAS IN THESE DRAWINGS THAT ARE
 NOT DRAWN TO SCALE AND DON'T REFLECT THE GIVEN
 DIMENSION. FOR EXAMPLE NOT ALL CORRIDORS MEASURE 60" AS
 SPECIFIED ON SHEET A-4. THESE WAS NOTED ON PREVIOUS
 COMMENT.
 SPECIFY THE SIZE OF EXISTING DOOR #3. TO VERIFY
 COMPLIANCE WITHOUT EH MINIMUM CLEAR WIDTH OPENING.
 ALSO, CLARIFY WHY DOOR HARDWARE FOR THESE TWO BATHROOMS
 IS DIFFERENT THAN THE OTHER BATHROOMS. CLEARLY SPECIFY
 THE DOOR HARDWARE FOR ALL DOORS TO VERIFY COMPLIANCE
 WITH SEC. 309 FBC-ACCESSIBLE.
  
 3- ORIGINAL COMMENT:
 THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE
 MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED.
 AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL
 DESIGN PRESSURES (VASD).
  
 RESPONSE:
 REPEAT COMMENT. PARTIALLY ADDRESSED. REVISED DESIGN
 PRESSURES SHOWN ON SHEET A-4 ARE INCORRECT AND ARE NOT
 CLEAR. CLARIFY WHY SPECIFYING TWO DIFFERENT MEAN ROOF
 HEIGHTS. THE ADJUSTMENT FACTOR FOR A MEAN ROOF HEIGHT
 OF 20' ' IS 1.29 NOT 1.21. AND THE ADJUSTMENT FACTOR
 FOR A MEAN ROOF HEIGHT OF 24' IS 1.35 NOT 1.21. REVISE
 AS REQUIRED. SEE TABLE 1609.7(2) FBC.
  
 4- WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 5- ORIGINAL COMMENT:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 RESPONSE:
 A) ENTRANCE DOOR NOA 17-1114.01 SUBMITTED. CLEARLY
 SPECIFY DOOR AND GLASS TYPE AS REQUIRED BY THE
 INSTRUCTIONS ON DRAWING W17-54 SUBMITTED.
 NOTE: PRODUCT APPROVAL MAY BE SUBMITTED LATER AS
 "DEFERRED SUBMITTAL" AFTER THE PERMIT IS ISSUED, BUT
 BEFORE ANY INSPECTIONS TO AVOID CONFLICT DELAYS.
  
 6- ORIGINAL COMMENT:
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- ORIGINAL COMMENT:
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 8- BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 9- PLEASE NOTE A THOROUGH REVIEW COULD NOT BE COMPLETED
 IN THIS REVIEW AND DEPENDING ON THE RESPONSE COMMENTS
 ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING REVIEWS.
 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 10- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 NEW COMMENTS:
  
 11- SLEEPING ROOMS NEED TO HAVE SEPARATION WALLS WITH
 FIRE PARTITIONS AS REQUIRED BY SEC. 420..2 FBC.
 IDENTIFY WALL IN PLANS AND PROVIDE FIRE RATED WALL
 DETAIL AND SPECIFICATIONS.
 NOTE: I APOLOGIZE. IT WAS OVERLOOKED ON PREVIOUS
 REVIEW. I TAUGHT THEY WERE SPECIFIED AS FIRE RATED
 WALLS.
  
 12- PARKING CALCULATIONS INFORMATION ON SHEET P-1 NEEDS
 TO BE REVISED TO REFLECT THE ACTUAL NUMBER OF PARKING
 SPACES SHOWN ON-THE REVISED PLOT PLAN. SEC. 107.2.1
 CITY AMENDMENTS.
  
 13-CLARIFICATION: MINIMUM REQUIRED CORRIDOR WIDTH IS
 44" NOT 42". TABLE 1020.2 FBC. REVISE INFORMATION ON
 SHEET A-4 AS REQUIRED.
  
 14- THE FENCED YARD NEEDS TO BE ACCESSIBLE. SEC.
 206.2.2 FBC ACCESSIBLE.
  
 15- SINCE SOME AREAS OF THE FLOOR PLAN SUBMITTED ARE
 NOT DRAWN TO A TRUE SCALE, THEN IS HARD TO VERIFY DOOR
 MANEUVERING CLEARANCES BASED ON THE PUSH SIDE, PULL
 SIDE APPROACH AND THE SPECIFIED DOOR HARDWARE. IT LOOKS
 LIKE SOME AREAS MAY NOT COMPLY. PROVIDE DIMENSIONS ON
 PLANS. CHECK THE KITCHEN AREA. CHECK IN-TAKE AND
 NURSE/MED OFFICE AND CORRIDOR ON THE RIGHT HAND SIDE.
 SEE FIGURE 404.2.4.1 FBC ACCESSIBLE AND REVISE AS
 REQUIRED.
  
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By jgomez Date 2018-04-27 Time 18:20 Rev Time 0.00
Received By jgomez Date 2018-04-27 Time 09:03 Sent To  
Notes
2018-04-26 19:10:08SECOND BUILDING REVIEW CHECKLIST
 CODE: FBC 6TH EDITION (2017).
  
  
 1) COMPLIED.
  
 2) SHEET A-4/ BUILDING DATA & DESIGN:
 2A)COMPLIED.
  
 2B)SEMI-COMPLIED. SPECIFY THE OCCUPANT LOAD OF THE
 LIVING/DINING AREA. SEE TABLE 1004.1.2. CLARIFY WHAT IS
 INSTITUTIONAL AREA?. CLEARLY OUTLINE ON PLAN EACH AREA.
 REVISE TOTAL OCCUPANT LOAD AS REQUIRED. NOTE: ANY
 FRACTION SHOWN ON THE OCCUPANT LOAD CALCULATIONS NEEDS
 TO BE ROUNDED UP NOT ROUNDED DOWN.
  
 ORIGINAL COMMENT:
 OCCUPANT LOAD FACTOR IS TAKEN AT 50 SQ. OCCUPANT.
 PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2
 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
 INPATIENT TREATMENT AREAS 240 GROSS
 OUTPATIENT AREAS 100 GROSS
 SLEEPING AREAS 120 GROSS
 PLEASE UPDATE PLANS.
  
 2C) SEMI-COMPLIED. INFORMATION SUBMITTED IS NOT CLEAR.
 RESPONSE LETTER STATES I-1 ALCOHOL AND DRUG
 CENTERS/CONGREGATE CARE FACILITIES AND INFORMATION ON
 SHEET A-4 SPECIFIES "FIRE PREVENTION RESIDENTIAL
 BOARDING & CARE". CLARIFY WHAT IS "FIRE PREVENTION
 RESIDENTIAL BOARDING & CARE". AND, CLEARLY DEFINE
 SPECIFIC USE. ALSO, NEED TO CLASSIFY WHICH I-1
 CONDITION IS PROPOSED AS REQUIRED BY SEC. 308.3
 FBC-BUILDING. CONDITION 1 OR CONDITION 2.
  
 ORIGINAL COMMENT:
 THE BUILDING DATA LIST THIS OCCUPANCY AS AN I-2
 OCCUPANCY PLEASE DECLARE THE END USE?
 FBC-B 308.4 INSTITUTIONAL GROUP I-2. DETOXIFICATION
 FACILITY/ NURSING HOME
 FBC-B 308.3 INSTITUTIONAL GROUP I-1. ALCOHOL AND DRUG
 CENTERS / CONGREGATE CARE FACILITIES
 FBC-B 310.6 RESIDENTIAL GROUP R-4. RESIDENTIAL GROUP
 R-4. ALCOHOL AND DRUG CENTERS, CONGREGATE CARE
 FACILITIES. RESIDENTIAL GROUP R-4 OCCUPANCY SHALL
 INCLUDE BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR
 MORE THAN FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING
 STAFF, WHO RESIDE ON A 24-HOUR BASIS IN A SUPERVISED
 RESIDENTIAL ENVIRONMENT AND RECEIVE CUSTODIAL CARE.
 UNTIL THE END USE IS GIVEN THE LIFE SAFETY ISSUES
 CANNOT BE DETERMINED.
 FBC-B 407 GROUP I-2 DETOXIFICATION
 FBC-B 420 I-1, R-3/ R-4.
  
 2D) SEMI-COMPLIED. CLARIFY WHY THE FURNITURE LAYOUT
 ONLY SHOW THE DESK IN THE OFFICES AND THE CHAIRS ARE
 NOT SHOWN.
 NOTE: KEEP IN MIND MANEUVERING CLEARANCES REQUIRED FOR
 PROPER DOOR OPERATION.
  
 ORIGINAL COMMENT:
 PLEASE PROVIDE A FLOOR PLANS SHOWING THE FURNITURE
 LAYOUT INCLUDING BEDS TO SEE OCCUPANT LOADS FOR THE
 SLEEPING ROOMS. TO HELP IN THE DEFINING OF THE END USE.
  
 2E) COMPLIED. PLOT PLAN PROVIDED.
  
 2F)COMPLIED. PLOT PLAN PROVIDED.
  
 2G) PASSENGER LOADING ZONE SHOWN ON THE PLOT PLAN NEEDS
 TO COMPLY WITH ALL THE REQUIREMENTS OF SEC. 503.3
 FBC-ACCESSIBILITY. SEE 503.1 THRU 503.4 AND REVISE PLOT
 PLAN AS REQUIRED. ALSO, REVISE THE PARKING INFORMATION
 SHOWN ON THE PLOT PLAN SUBMITTED. PROVIDE INFORMATION
 THAT RELATES TO PROPOSED USE. THERE ARE NOT MEDICAL
 OFFICES AND DOCTORS.
  
 ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM
 CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE
 COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE
 ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED
 LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY
 EXCEEDS TWENTY-FOUR HOURS.
  
 2H)SEMI-COMPLIED. UNITS COMPLYING WITH THE UNIT
 MOBILITY TO CLEARLY SHOW COMPLIANCE WITH THE TURNING
 SPACE SEC. 805.2 FBC-ACCESSIBILITY. REVISE THE TURNING
 SPACE TO COMPLY WITH FIGURE 304.3.2 FBC-ACCESSIBILITY.
  
 ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 223.2 HOSPITALS, REHABILITATION
 FACILITIES, PSYCHIATRIC FACILITIES AND DETOXIFICATION
 FACILITIES. HOSPITALS, REHABILITATION FACILITIES,
 PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES
 SHALL COMPLY WITH 223.2.
 ACCESS. CODE223.2.1 FACILITIES NOT SPECIALIZING IN
 TREATING CONDITIONS THAT AFFECT MOBILITY. IN FACILITIES
 NOT SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER THAN ONE,
 OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE MOBILITY
 FEATURES COMPLYING WITH 805. ACCESSIBLE PATIENT
 BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 2I)805 MEDICAL CARE AND LONG-TERM CARE FACILITIES.
 805.1. COMPLIED.
  
 805.2 SEMI-COMPLIED. REVISE T-SHAPED TURNING SPACE. SEE
 FIGURE 304.3.2 FBC-ACCESSIBILITY.
  
 ORIGINAL COMMENT:
 TURNING SPACE. TURNING SPACE COMPLYING WITH 304 SHALL
 BE PROVIDED WITHIN THE ROOM.
  
 805.3 . COMPLIED.
  
 805.4. UNISEX RESTROOM AND ADJACENT BATHROOM DON'T
 COMPLY WITH THE OVERLAP REQUIREMENTS OF SEC. 604.3.2
 FBC-ACCESSIBILITY.
 AND WITH RESTROOM FIXTURE CLEARANCE DETAIL SHOWN ON
 SHEET A-5. REVISE AS REQUIRED.
 (NOTE: SHOWER IS NOT DRAWN TO SCALE IN THIS ROOM. ALSO,
 SOME ROOMS AND CORRIDORS ARE NOT DRAWN TO THE SPECIFIED
 DIMENSIONS. PLEASE VERIFY THAT ALL SPECIFIED DIMENSIONS
 WILL BE PROVIDED IN FIELD TO AVOID CONFLICTS/DELAYS).
  
 ORIGINAL COMMENT:
 TOILET AND BATHING ROOMS. TOILET AND BATHING ROOMS THAT
 ARE PROVIDED AS PART OF A PATIENT OR RESIDENT SLEEPING
 ROOM SHALL COMPLY WITH 603. WHERE PROVIDED, NO FEWER
 THAN ONE WATER CLOSET, ONE LAVATORY, AND ONE BATHTUB OR
 SHOWER SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 603 THROUGH 610.
  
 2J)COMPLIED.
  
 2K) THE CLEAR FLOOR SPACE DRAWN ON SHEET A-7 IS NOT TO
 SCALE. IT DOESN'T MEASURE 30"X48". REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE ) 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2K(1) COMPLIED.
  
 2K(2) COMPLIED.
  
 2K)(3) COMPLIED.
  
 2K)(4) COMPLIED.
  
 3) SHEET A-4 CERTIFICATION FOR DESIGN COMPLIANCE:
 3A) COMPLIED.
  
 3B) COMPLIED.
  
 3C) COMPLIED.
  
 3D) THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE
 MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED.
 AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL
 DESIGN PRESSURES (VASD).
  
 ORIGINAL COMMENT:
 PLEASE UPDATE WALL PRESSURES PROVIDE A CHART IN VASD
 FOR 10 SQ. FT., 20 SQ. FT. 50 SQ. FT. & 100 SQ. FT. FOR
 WALL ZONES 4 & 5.
  
 3E) THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE
 MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED.
 AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL
 DESIGN PRESSURES (VASD).
  
 ORIGINAL COMMENT:
 THE DESIGN PRESSURE CHART FOR THE ROOF ZONES 1,2 & 3 IS
 MARKED NOT APPLICABLE, THE PLANS INDICATE A MEAN ROOF
 HEIGHT OF 20 FT. AND 4 FOOT PARAPET. ROOF ZONES 1, 2 &
 3 NOT APPLICABLE. PLEASE NOTE THE PARAPET ON THE NORTH
 SIDE OF THE BUILDING IS BETWEEN 18 -24 INCHES TALL THUS
 CREATING ROOF ZONE 3.
 2017 FBC-B TABLE 1609.6.2, ASCE 7-10.
  
 3F) COORDINATE WITH ITEMS # 3D AND #3E ABOVE.
  
 ORIGINAL COMMENT:
 PLEASE PROVIDE THE PRESSURES FOR ALL ROOF ZONES IN
 VASD. THE MECHANICAL SHEET M3.3 SHOWS NEW ROOF TOP
 CURBS AND DOWN UNITS AS WELL AS A/C STANDS IT APPEARS
 THERE WILL BE ROOFING WORK INVOLVED AS WELL AS NEW ROOF
 TOP OPENINGS. MECHANICAL SHEET M3.3 DETAILS I &J
 INDICATE SEE ARCHITECTURAL SHEETS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 5) NEED ALL THE PRODUCT APPROVALS (2 COPIES). NOTE:
 PRODUCT APPROVAL MAY BE SUBMITTED LATER AS "DEFERRED
 SUBMITTAL" AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY
 INSPECTIONS TO AVOID CONFLICT DELAYS.
  
 ORIGINAL COMMENT:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 6) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 9)COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
  
 10) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED./ 2017
 FBC-B 1604.4 ANALYSIS.
 FOR ROOF TOP A/C STAND PRODUCT APPROVAL PROVIDE A (2)
 COPIES OF THE PRODUCT APPROVAL REVIEWED BY THE DESIGNER
 OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 11) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FEET , SUCH ACCESS
 SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS OF
 ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH OR
 WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) PLEASE NOTE A THOROUGH REVIEW COULD NOT BE
 COMPLETED IN THIS REVIEW AND DEPENDING ON THE RESPONSE
 COMMENTS ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING
 REVIEWS. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By jwitmer Date 2018-01-30 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2018-01-30 Time 06:42 Sent To  
Notes
2018-01-30 09:39:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010936
 ADD: 4461 MEDICAL CENTER WAY
 CONT: ERETZOR CONSTRUCTION LLC
 TEL: 954-937-7041
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 30/ 2018
 ACTION: DENIED
  
 1) PLEASE CORRECT THE ADDRESS ON THE PERMIT APPLICATION
 AND THE ARCHITECTURAL SHEETS. THE PCN NUMBER
 74-43-43-06-14-000-0012 IS 4461 MEDICAL CENTER WAY.
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. 2017 FBC-B 101.2 ADDRESS
 IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE
 PROVIDED WITH APPROVED ADDRESS IDENTIFICATION.
  
 2) SHEET A-4/ BUILDING DATA & DESIGN:
 2A) THE LAST KNOWN USE WAS A BUSINESS OCC. OCULOPLASTIC
 & ORBITAL CONSULTANTS. THE PLAN LISTS THIS AS A LEVEL
 II ALTERATION. THIS IS A CHANGE IN OCCUPANCY GOVERNED
 BY THE 2017 FBC-EXISTING BUILDING CODE CHAPTER 10. SEE
 1001.2.2 CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 2B) OCCUPANT LOAD FACTOR IS TAKEN AT 50 SQ. OCCUPANT.
 PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2
 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
 INPATIENT TREATMENT AREAS 240 GROSS
 OUTPATIENT AREAS 100 GROSS
 SLEEPING AREAS 120 GROSS
 PLEASE UPDATE PLANS.
  
 2C) THE BUILDING DATA LIST THIS OCCUPANCY AS AN I-2
 OCCUPANCY PLEASE DECLARE THE END USE?
 FBC-B 308.4 INSTITUTIONAL GROUP I-2. DETOXIFICATION
 FACILITY/ NURSING HOME
 FBC-B 308.3 INSTITUTIONAL GROUP I-1. ALCOHOL AND DRUG
 CENTERS / CONGREGATE CARE FACILITIES
 FBC-B 310.6 RESIDENTIAL GROUP R-4. RESIDENTIAL GROUP
 R-4. ALCOHOL AND DRUG CENTERS, CONGREGATE CARE
 FACILITIES. RESIDENTIAL GROUP R-4 OCCUPANCY SHALL
 INCLUDE BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR
 MORE THAN FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING
 STAFF, WHO RESIDE ON A 24-HOUR BASIS IN A SUPERVISED
 RESIDENTIAL ENVIRONMENT AND RECEIVE CUSTODIAL CARE.
 UNTIL THE END USE IS GIVEN THE LIFE SAFETY ISSUES
 CANNOT BE DETERMINED.
 FBC-B 407 GROUP I-2 DETOXIFICATION
 FBC-B 420 I-1, R-3/ R-4.
  
 2D) PLEASE PROVIDE A FLOOR PLANS SHOWING THE FURNITURE
 LAYOUT INCLUDING BEDS TO SEE OCCUPANT LOADS FOR THE
 SLEEPING ROOMS. TO HELP IN THE DEFINING OF THE END USE.
  
 2E) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 206.2.1 SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 2F) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 208.1 WHERE PARKING SPACES ARE
 PROVIDED, PARKING SPACES SHALL BE PROVIDED IN
 ACCORDANCE WITH 208. SEE SECTION 502.5 REQUIREMENTS FOR
 VAN PARKING IN STRUCTURES.
  
 2G) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM
 CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE
 COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE
 ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED
 LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY
 EXCEEDS TWENTY-FOUR HOURS.
  
 2H) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 223.2 HOSPITALS, REHABILITATION
 FACILITIES, PSYCHIATRIC FACILITIES AND DETOXIFICATION
 FACILITIES. HOSPITALS, REHABILITATION FACILITIES,
 PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES
 SHALL COMPLY WITH 223.2.
 ACCESS. CODE223.2.1 FACILITIES NOT SPECIALIZING IN
 TREATING CONDITIONS THAT AFFECT MOBILITY. IN FACILITIES
 NOT SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER THAN ONE,
 OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE MOBILITY
 FEATURES COMPLYING WITH 805. ACCESSIBLE PATIENT
 BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 2I) 805 MEDICAL CARE AND LONG-TERM CARE FACILITIES.
 805.1. MEDICAL CARE FACILITY AND LONG-TERM CARE
 FACILITY PATIENT OR RESIDENT SLEEPING ROOMS REQUIRED TO
 PROVIDE MOBILITY FEATURES SHALL COMPLY WITH 805.
  
 805.2 TURNING SPACE. TURNING SPACE COMPLYING WITH 304
 SHALL BE PROVIDED WITHIN THE ROOM.
  
 805.3 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED ON EACH SIDE OF
 THE BED. THE CLEAR FLOOR SPACE SHALL BE POSITIONED FOR
 PARALLEL APPROACH TO THE SIDE OF THE BED.
  
  
 805.4 TOILET AND BATHING ROOMS. TOILET AND BATHING
 ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR
 RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE
 PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 2J) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND.
  
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 2K) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE ) 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2K(1) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2K(2) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 2K)(3) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2K)(4) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  
 3) SHEET A-4 CERTIFICATION FOR DESIGN COMPLIANCE:
 3A) PLEASE NOTE THE RISK CATEGORY CHECKED OFF IS III.
 IN THE 2017 FBC-B TABLE 1604.5 DOES INCLUDE GROUP I-2
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR MORE
 RESIDENT CARE RECIPIENTS. THE OCCUPANT LOAD WILL BE
 LESS THAN 50 WHEN CALCULATING THE FLOOR AREA STATED
 ABOVE. RISK CATEGORY WILL BE CATEGORY II.
  
 3B) THE WIND DESIGN IS GIVEN AS 160 MPH, VULT. PLEASE
 REVIEW THE 2017 FBC-B FIGURE 1609.3(1) ULTIMATE DESIGN
 WIND SPEED FOR RISK CATEGORY II BUILDINGS IS 170 MPH
 VULT.
 3C) THE WIND DESIGN CRITERIA ALSO LIST THE EXPOSURE AS
 B EXPOSURE. PLEASE UPDATE PLANS WHEN LOOKING AT WIND
 YOU LOOK FROM ALL QUADRANTS AND THERE C ROUGHNESS.
 1609.4.3 2014 FBC-B THIS SURFACE ROUGHNESS SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS
 B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET IN THE UPWIND DIRECTION AND A WIDTH GREATER
 THAN 150 FEET.
 1609.4.3 2017 FBC-B SURFACE ROUGHNESS C. OPEN TERRAIN
 WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY
 LESS THAN 30 FEET . THIS CATEGORY INCLUDES FLAT OPEN
 COUNTRY, AND GRASSLANDS.
  
 3D) PLEASE UPDATE WALL PRESSURES PROVIDE A CHART IN
 VASD FOR 10 SQ. FT., 20 SQ. FT. 50 SQ. FT. & 100 SQ.
 FT. FOR WALL ZONES 4 & 5.
  
 3E) THE DESIGN PRESSURE CHART FOR THE ROOF ZONES 1,2 &
 3 IS MARKED NOT APPLICABLE, THE PLANS INDICATE A MEAN
 ROOF HEIGHT OF 20 FT. AND 4 FOOT PARAPET. ROOF ZONES 1,
 2 & 3 NOT APPLICABLE. PLEASE NOTE THE PARAPET ON THE
 NORTH SIDE OF THE BUILDING IS BETWEEN 18 -24 INCHES
 TALL THUS CREATING ROOF ZONE 3.
 2017 FBC-B TABLE 1609.6.2, ASCE 7-10.
  
 3F) PLEASE PROVIDE THE PRESSURES FOR ALL ROOF ZONES IN
 VASD. THE MECHANICAL SHEET M3.3 SHOWS NEW ROOF TOP
 CURBS AND DOWN UNITS AS WELL AS A/C STANDS IT APPEARS
 THERE WILL BE ROOFING WORK INVOLVED AS WELL AS NEW ROOF
 TOP OPENINGS. MECHANICAL SHEET M3.3 DETAILS I &J
 INDICATE SEE ARCHITECTURAL SHEETS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 9) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
  
 10) 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED./ 2017
 FBC-B 1604.4 ANALYSIS.
 FOR ROOF TOP A/C STAND PRODUCT APPROVAL PROVIDE A (2)
 COPIES OF THE PRODUCT APPROVAL REVIEWED BY THE DESIGNER
 OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 11) 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET ,
 SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM
 GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES?
 LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) PLEASE NOTE A THOROUGH REVIEW COULD NOT BE
 COMPLETED IN THIS REVIEW AND DEPENDING ON THE RESPONSE
 COMMENTS ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING
 REVIEWS. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 14:06 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 13:42 Sent To I
Notes
2018-04-30 13:55:15PROVISO ON PLAN FOR SEPARATE PERMIT REQUIREMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-05 Cont ID  
Sent By jpearson Date 2018-02-05 Time 12:47 Rev Time 0.00
Received By jpearson Date 2018-02-05 Time 06:46 Sent To  
Notes
2018-02-05 12:47:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. PROVIDE LOAD CALCULATION FOR WIREWAY, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 WIRE IS ADEQUATE. NEC 215.2, 220, 310.15(B)(16), 408.30
 3. ALL RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION FOR FREEZER AND REFRIGERATOR. NEC
 210.8
 4. OUTSIDE GFCI RECEPTACLES MUST BE WEATHERPROOF.
 PROVIDE CORRECTION. NEC 406.9
 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 6. PROVIDE NOTE FOR ELECTRIC WATER COOLER THAT THE GFCI
 RECEPTACLE SHOWN SHALL BE READILY ACCESSIBLE. NEC 422.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-06-14 Cont ID  
Sent By pleduc Date 2018-06-14 Time   Rev Time 0.00
Received By pleduc Date 2018-06-13 Time 15:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-05-16 Cont ID  
Sent By pleduc Date 2018-05-16 Time   Rev Time 0.00
Received By pleduc Date 2018-05-16 Time 09:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-16 Cont ID  
Sent By pleduc Date 2018-04-16 Time   Rev Time 0.00
Received By pleduc Date 2018-04-16 Time 13:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-01-29 Cont ID  
Sent By pleduc Date 2018-01-29 Time   Rev Time 0.00
Received By pleduc Date 2018-01-29 Time 11:54 Sent To  
Notes
2018-01-29 13:47:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1 - THERE IS NO ADDRESS INDICATED WITHIN THE
 TITLE BLOCK OF ANY PAGE. AN ADDRESS IS REQUIRED TO
 ENSURE ACCURATE LOCATION IDENTIFICATION.
  
 ADDITIONALLY, PLEASE ENSURE THAT THE ADDRESS IS
 CORRECT, THERE IS NO MEDICAL WAY IN WEST PALM BEACH.
 THERE IS A MEDICAL CENTER WAY, PLEASE CLARIFY.
  
 PER NFPA 1:
  
 1.7.12 PLANS AND SPECIFICATIONS.
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS ANDSPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE AN ACCURATE ADDRESS.
  
  
  
 2) SHEET A 4 - THERE IS NO INDICATION OF ANY COMPLIANCE
 OF THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTIO
 N CODE INCLUDING THE 2015 EDITION OF NFPA 1 AND NFPA
 101 AND ALL OTHER APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE PROVIDE FOR THE REVIEW AND APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) SHEET A 4 - THERE IS AN INDICATION STATED THIS IS A
 GRUOP: INSTITUTIONAL I2. WHAT WAS THE OCCUPANCY
 PREVIOUSLY AND WHAT IS THE OCCUPANCY ACCORDING TO THE
 FFPC.
  
 PER NFPA 1:
 1.7.12.5 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE CHANGE OF OCCUPANCY OF ANY EXISTING BUILDING.
  
 PER NFPA 101:
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
  
 ADDITIONALLY, PLEASE ENSURE THAT ALL WINDOWS MEET THE
 REQUIREMENTS PER THE APPLICABLE FFPC OCCUPANCY
 CLASSIFICATION.
  
 PLEASE PROVIDE DETAILS OF WHAT THIS OCCUPANCY'S
 ACTIVITIES AND THE OCCUPANCY CLASSIFICATION PER THE
 FFPC.
  
  
  
  
 4) SHEET A 2 - THERE IS A REAR EXIT INDICATED LEADING
 TO A FENCED-IN AREA WITH A GATE. THIS AREA IS NOT A
 PUBLIC WAY, BUT EXIT ACCESS. THE GATE APPEARS TO BE THE
 EXIT. DOES THIS GATE LEAD TO A PUBLIC WAY?
  
 PER NFPA 101:
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN
 7.7.1.2 THROUGH 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH
 AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO
 A PUBLIC WAY.
  
 PLEASE PROVIDE DETAILS OF THE GATE AND ENTER THE GATE
 INTO THE DOOR SCHEDULE WITH THE APPLICABLE
 HARDWARE/LOACKING & LATCHING.
  
  
  
  
 5) SHEET A 2 - THE DOOR SCHEDULE INDICATED THE EXIT
 DOORS # 3 - FRONT AND REAR AS EXISITNG; HOWEVER, NO
 EXIT HARDWARE OF LOCKING TYPE IS INDICATED.
  
 PER NFPA 101
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE SPECIAL REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
  
 PLEASE PROVIDE THE APPLICABLE INFORMATION AND AS
 REQUIRED BY THE OCCUPANCY CLASSIFICATION TYPE OF # 3
 ABOVE.
  
  
  
 6) SHEET A 2 - DOORS # 2 INDICATED IN THE EXIT PATH OF
 TRAVEL AT THE CENTER CORRIDOR AT THE INTAKE AND
 NURSE/MED ROOMS DO NOT HAVE THE DOOR HARDWARE NOTED.
  
 THESE DOORS CAN NOT BE LOCKED IN THE PATH OF EGRESS.
  
 PLEASE PROVIDE THE HARDWARE TYPE COMPLIANT WITH THE
 EGRESS CODE.
  
  
  
  
 7) SHEET A 4 - THERE IS AN INDICATION THA THE BUILDING
 IS FULLY SPRINKLER; HOWEVER, THERE ARE NO IDICATIONS OF
 FIRE SPRINKLER WORK.
  
 PER NFPA 101
 9.7 AUTOMATIC SPRINKLERS.
 9.7.1 GENERAL.
 9.7.1.1* EACH AUTOMATIC SPRINKLER SYSTEM REQUIRED BY
 ANOTHER SECTION OF THIS CODE SHALL BE IN ACCORDANCE
 WITH ONE OF THE FOLLOWING:
 (1) NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS
 (2) NFPA 13D, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS IN ONE- AND TWO-FAMILY DWELLINGS AND
 MANUFACTURED HOMES
 (3) NFPA 13R, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES
  
 ALL WORK OF THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 THROUGH SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AND
 COMPLIANCE.
  
  
  
  
 8) SHEETS A 4 & E 1 - THERE ARE NO INDICATIONS OF FIRE
 ALARM WORK.
  
 PER NFPA 101
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS
 CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER
 SYSTEM OR NEW FIRE ALARMSYSTEM IS REQUIRED BY THE
 FLORIDA BUILDING CODE.
  
 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL
 BE INSTALLED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 THE APPLICABLE REQUIREMENTS OF NFPA 70, NATIONAL
 ELECTRICAL CODE, AND NFPA 72, NATIONAL FIRE ALARM AND
 SIGNALING CODE, UNLESS IT IS AN APPROVED EXISTING
 INSTALLATION, WHICH SHALL BE PERMITTED TO BE CONTINUED
 IN USE.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AND
 COMPLIANCE.
  
  
  
  
 9) SHEET E 3 - AN EXIT PATH OF TRAVEL IS INDICATED ON
 SHEET A 4 LEADING FROM THE REAR CORRIDOR BY THE
 NURSE/MED DOOR # 2; HOWEVER, THERE IS NO EXIT SIGN IN
 THE REAR CORRIDOR LEADING IN THAT DIRECTION.
  
 PLEASE ADD AN EXIT SIGN IN THE REAR CORRIDOR AT THE
 DOOR # 2 AT THE NURSE/MED ROOM AND SMALL CORRIDOR.
  
  
  
 10) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS ON
 ANY SHEET OF THE SUBMITTAL.
  
 PER NFPA 101
 PORTABLE FIRE EXTINGUISHERS. PORTABLE FIRE
 EXTINGUISHERS SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 9.9.
  
 9.9* PORTABLE FIRE EXTINGUISHERS. WHERE REQUIRED BY
 ANOTHER SECTION OF THIS CODE, PORTABLE FIRE
 EXTINGUISHERS SHALL BE SELECTED, INSTALLED,INSPECTED,
 AND MAINTAINED IN ACCORDANCE WITH NFPA 10, STANDARD FOR
 PORTABLE FIRE EXTINGUISHERS.
  
 PLEASE PROVIDE LOCATIONS.
  
  
 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-06-22 Cont ID  
Sent By gjohnson Date 2018-06-22 Time 10:18 Rev Time 0.00
Received By gjohnson Date 2018-06-22 Time 10:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-04-24 Cont ID  
Sent By gjohnson Date 2018-04-24 Time 12:50 Rev Time 0.00
Received By gjohnson Date 2018-04-24 Time 12:50 Sent To  
Notes
2018-04-24 12:51:45SEE NOTES AND RED LINES ON PLAN

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 14:36 Rev Time 0.00
Received By gjohnson Date 2018-02-15 Time 14:36 Sent To  
Notes
2018-02-15 14:43:451ST REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW ON THE RISER TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE EHD NUMBER OF
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE IF
 BEING USED. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. SHOW ON THE RISER TYPE OF GAS, (LP OR NATURAL).
  
 5. SHOW ON THE RISER THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER THE FBC-2014 FUEL GAS
 APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4) & 2014
 FUEL GAS CODE SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. PROVIDE A SINGLE DETAIL SHOWING THE TYPE, LOCATION,
 LENGTH, SIZE AND TERMINATION OF THE GAS VENTS PER
 FBC-2014 FUEL GAS CODE SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
 13. SHOW THE REGULATORS ON RISER
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-22 Cont ID  
Sent By gjohnson Date 2018-06-22 Time 10:18 Rev Time 0.00
Received By gjohnson Date 2018-06-08 Time 13:30 Sent To  
Notes
2018-06-11 13:30:13C03

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-26 Cont ID  
Sent By jgomez Date 2018-05-26 Time 18:58 Rev Time 0.00
Received By jgomez Date 2018-05-07 Time 15:21 Sent To  
Notes
2018-05-08 15:21:15C07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-12 Time 15:04 Sent To  
Notes
2018-04-13 15:05:03C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 14:44 Rev Time 0.00
Received By gjohnson Date 2018-01-24 Time 14:58 Sent To  
Notes
2018-01-25 14:58:17C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2018-07-27 Cont ID  
Sent By shill Date 2018-07-27 Time 11:34 Rev Time 0.00
Received By shill Date 2018-07-27 Time 11:34 Sent To  
Notes
2018-07-27 11:34:55MU 2018 026280 0000, $4836.24
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2018-06-14 Cont ID  
Sent By jgomez Date 2018-06-14 Time 18:49 Rev Time 0.00
Received By jgomez Date 2018-06-14 Time 18:49 Sent To  
Notes
2018-06-14 18:50:06BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-05-26 Cont ID  
Sent By jgomez Date 2018-05-26 Time 17:01 Rev Time 0.00
Received By jgomez Date 2018-05-26 Time 17:01 Sent To  
Notes
2018-05-26 17:01:50BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By jgomez Date 2018-04-30 Time 11:34 Rev Time 0.00
Received By jgomez Date 2018-04-30 Time 11:34 Sent To  
Notes
2018-04-30 11:34:49BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By jwitmer Date 2018-01-30 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2018-01-30 Time 06:42 Sent To  
Notes
2018-01-30 09:26:39BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-06-21 Cont ID  
Sent By ccole Date 2018-06-21 Time 07:35 Rev Time 0.00
Received By ccole Date 2018-06-20 Time 17:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-23 Cont ID  
Sent By ccole Date 2018-04-23 Time 16:24 Rev Time 0.00
Received By ccole Date 2018-04-23 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By ccole Date 2018-02-08 Time 11:05 Rev Time 0.00
Received By ccole Date 2018-02-08 Time 11:05 Sent To  
Notes
2018-02-08 11:38:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010936
 2/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2.2: THE MECHANICAL VENTILATION FOR THE
 FACILITY SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH THE FBC-17 MECHANICAL, AND ASHRAE 170-2008- SEE
 SECTION 407.1. PLEASE PROVIDE CALCULATIONS AND DESIGN
 PARAMETERS FOR THE VENTILATION SYSTEM IN ACCORDANCE
 WITH TABLE 7-1 ASHRAE 170. PLEASE NOTE THAT THE O/A
 CALCULATION FOR AHU-4 ON THE PLANS IS NOT IN COMPLIANCE
 WITH TABLE 403.1.1 FBC-17 MECHANICAL WHICH REQUIRES
 DINING ROOMS TO BE CALCULATED AT 70 PERSONS PER 1000
 SQ. FT. AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SQ. FT.
  
 2) M-2.2: PLEASE SHOW COMPLIANCE WITH SECTION 6.3.1
 ASHRAE 170-2008 WHICH REQUIRES THE O/A INTAKES TO BE
 LOCATED A MINIMUM OF 25 FT. FROM EXHAUST AND VENT
 DISCHARGES.
  
 3) M-2.2: PERTAINING TO THE O/A INTAKES, INDICATE HOW
 COMPLIANCE WITH SECTION 401.5 AND TABLE 401.5 WILL BE
 MET.
  
 4) INDICATE THE AIR FILTRATION SYSTEM AND SUPPLY AIR
 OUTLETS ARE IN COMPLIANCE WITH TABLES 6-1 & 6-2 ASHRAE
 170.
  
 5) M3-3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSER STAND AND MOUNTING OF THE
 CONDENSERS TO THE STAND. PROVIDE ENGINEERING FOR THE
 STAND OR SUBMIT A VALID FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE STAND APPROVED BY THE EOR. SHOW
 ON THE PLAN HOW THE STAND IS ATTACHED TO THE STRUCTURE-
 SECTION 301.15.
  
 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLERS THAT INDICATES THE TYPES AND SIZES OF PIPINGS,
 PIPING RUNS, AND TERMINATION LOCATIONS- SECTION 307.
  
 7) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION SYSTEM.
 PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.1.1 MAKEUP
 AIR TEMPERATURE AND SECTION 301.15 WIND RESISTANCE WILL
 BE REQUIRED.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED WATER HEATER AND COOKING APPLIANCES, AND
 INDICATE HOW COMBUSTION AIR IS BEING PROVIDED. PROVIDE
 THE MEANS AND THE CALCULATIONS IN ACCORDANCE WITH
 SECTION FBC-17 FUEL GAS.
  
 9) PROVIDE A VENTING PLAN FOR THE GAS WATER HEATER-
 SECTION 503 FBC-17 FUEL GAS. SHOW THE TYPE AND SIZE OF
 VENT FLUE, FLUE RUN AND TERMINATION LOCATION. ALL SHALL
 BE IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND
 PRODUCT LISTINGS.
  
 10) PLEASE REFER TO SECTION C403.2.8 FBC-17 ENERGY
 CONSERVATION AND SHOW COMPLIANCE:
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS. REPLACEMENT AIR
 INTRODUCED DIRECTLY INTO THE EXHAUST HOOD CAVITY SHALL
 NOT BE GREATER THAN 10 PERCENT OF THE HOOD EXHAUST
 AIRFLOW RATE. CONDITIONED SUPPLY AIR DELIVERED TO ANY
 SPACE SHALL NOT EXCEED THE GREATER OF THE FOLLOWING:
  
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
  
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
  
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
  
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
  
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
  
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
  
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-06-22 Cont ID  
Sent By gjohnson Date 2018-06-22 Time 10:18 Rev Time 0.00
Received By gjohnson Date 2018-06-22 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-23 Cont ID  
Sent By gjohnson Date 2018-05-23 Time 08:36 Rev Time 0.00
Received By gjohnson Date 2018-05-22 Time 16:49 Sent To  
Notes
2018-05-23 08:41:07PROVISO: COMPLY PRIOR TO 1ST ROUGH INSPECTION.
  
 PREVIOUS COMMENT NOT COMPLIED 10. PROVIDE DETAIL FOR
 THE SHOWER PANS. FBC PL 417.5.2 THE RESPONSE LETTER
 FROM ENGINEER STATED THE ARCHITECT WOULD PROVIDE THAT
 THE RESPONSE LETTER FROM THE ARCHITECT STATED THE
 ENGINEER WOULD PROVIDE THE DETAIL.
 PROVIDE MANUFACTURE SPECIFICATIONS FOR SHOWER PAN
 LINER.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-24 Cont ID  
Sent By gjohnson Date 2018-04-24 Time 12:06 Rev Time 0.00
Received By gjohnson Date 2018-04-24 Time 12:06 Sent To  
Notes
2018-04-24 12:19:082ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED 10. PROVIDE DETAIL FOR
 THE SHOWER PANS. 901.2.1 THE RESPONSE LETTER FROM
 ENGINEER STATED THE ARCHITECT WOULD PROVIDE THAT THE
 RESPONSE LETTER FROM THE ARCHITECT STATED THE ENGINEER
 WOULD PROVIDE THE DETAIL.
  
 NEW COMMENT
 1. THE NEW SHOWER IN THE EXISTING BATHROOM 5+6 SHALL
 COMPLY WITH ONE OF THE ACCESSIBLE SHOWER STALL
 DIMENSIONS. THE DEPTH OF 36" BUT 48" DOES NOT COMPLY IT
 SHALL BE 60"MIN OF 36" INSIDE DIMENSION. PER FBC ACC
 608.2.1 608.2.2, 608.2.3
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 13:50 Rev Time 0.00
Received By gjohnson Date 2018-02-14 Time 11:08 Sent To  
Notes
2018-02-15 14:32:311ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE OCCUPANT LOAD PLUMBING FIXTURE COUNT
 BREAKDOWN FOR EMPLOYEES, VISITORS AND PATIENTS. PER FBC
 TABLE 403.1
  
 2. WHAT TYPE OF FACILITY IS THIS GOING TO BE. PER WPB
 AMEND TO FBC 107.2.1
  
 3. SHOW COMPLIANCE WITH FBC ACC 610.3 SHOWER
 COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
  
 4. GRAB BARS SHALL BE FROM FINISH FLOOR MEASURED TO THE
 TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 5. PROVIDE THE DIMENSIONS FOR SHOWER ON EXTERIOR WALL
 IN BATHROOM 5+6. 901.2.1
  
 6. SHOW COMPLIANCE WITH FBC ACC
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 7. SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER TYPE
 SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
  
 8. THE SHOWER IN BATHROOM 7+8 SHALL BE VENTED BEFORE IT
 CONNECTS TO THE BUILDING DRAIN. PER FBC PL 901.2.1
  
 9. THE DETAILS FOR THE GREASE INTERCEPTOR SHALL COMPLY
 WITH WPB UTILITIES DEPT STANDARD DETAIL GS-7
  
 10. PROVIDE DETAIL FOR THE SHOWER PANS. 901.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2018-04-27 Cont ID  
Sent By gjohnson Date 2018-04-27 Time 11:04 Rev Time 0.00
Received By gjohnson Date 2018-04-27 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 14:34 Rev Time 0.00
Received By gjohnson Date 2018-02-15 Time 14:34 Sent To  
Notes
2018-02-15 14:36:021. THE DETAIL FOR GREASE INTERCEPTOR SHALL COMPLY WITH
 WPB UTILITIES DEPT STANDARD DETAIL GS-7
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2018-06-20 Time   Rev Time 0.00
Received By pgreilic Date 2018-06-15 Time 11:50 Sent To  
Notes
2018-06-20 15:37:34LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-05-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-05-14 Time 16:05 Sent To  
Notes
2018-05-14 16:06:21PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-04-19 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-19 Time 14:23 Sent To  
Notes
2018-04-19 14:23:29FAILED
  
 1.) WILL THE BUILDING FOOTPRINT BE ALTERED BY ANY OF
 THE PROPOSED BUILDING IMPROVEMENTS?
 2.) PROVIDE A DESCRIPTION OF THE PROPOSED USE FOR THE
 RENOVATED SPACE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-02-13 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-13 Time 09:31 Sent To  
Notes
2018-02-13 10:11:04FAILED
  
 1.) WILL THE BUILDING FOOTPRINT BE ALTERED BY ANY OF
 THE PROPOSED BUILDING IMPROVEMENTS?
 2.) PROVIDE A DESCRIPTION OF THE PROPOSED USE FOR THE
 RENOVATED SPACE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved