 |
Plan Review Details - Permit 18010936
| Plan Review Stops For Permit 18010936 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-06-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-06-14 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-06-14 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2018-06-14 18:33:38 | BUILDING REVIEW APPROVED WITH PROVISO (DEFERRED | | | SUBMITTAL): | | | 1- SUBMIT ALL PRODUCT APPROVALS FOR ALL DOORS, WINDOWS, | | | MULLIONS, STOREFRONT, ETC. APPROVED BY THE ARCHITECT OF | | | RECORD. | | | NOTE: ENTRANCE DOOR NOA 17-1114.01 SUBMITTED. CLEARLY | | | SPECIFY DOOR AND GLASS TYPE AS REQUIRED BY THE | | | INSTRUCTIONS ON DRAWING W17-54 SUBMITTED. | | | | | | 2- CLEARLY IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY | | | ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER | | | OF RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER'S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-05-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-25 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-25 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2018-05-25 15:40:41 | CHANGE OF OF OCCUPANCY TO INSTITUTIONAL I-1 (CONDITION | | | 1) , THIRD BUILDING REVIEW CHECKLIST | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- ORIGINAL COMMENT: | | | THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM | | | CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE | | | COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE | | | ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED | | | LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY | | | EXCEEDS TWENTY-FOUR HOURS. | | | | | | RESPONSE: | | | REPEAT COMMENT. PARTIALLY ADDRESSED. PASSENGER LOADING | | | ZONE LOCATION WAS REVISED ON THE PLOT PLAN BUT NEEDS TO | | | COMPLY WITH THE LENGTH (SEC. 503.3.2), MARKING (SEC. | | | 503.3.3) AND FLOOR AND GROUND SURFACES. HANDICAP RAMP | | | DETAIL PROVIDED ON SHEET P-1 DOESN'T APPLY TO THE FLOOR | | | AND GROUND SURFACE SEC. 503.4. REVISE AS REQUIRED. | | | | | | 2- ORIGINAL COMMENT: | | | UNISEX RESTROOM AND ADJACENT BATHROOM DON'T COMPLY WITH | | | THE OVERLAP REQUIREMENTS OF SEC. 604.3.2 | | | FBC-ACCESSIBILITY. | | | AND WITH RESTROOM FIXTURE CLEARANCE DETAIL SHOWN ON | | | SHEET A-5. REVISE AS REQUIRED. | | | (NOTE: SHOWER IS NOT DRAWN TO SCALE IN THIS ROOM. ALSO, | | | SOME ROOMS AND CORRIDORS ARE NOT DRAWN TO THE SPECIFIED | | | DIMENSIONS. PLEASE VERIFY THAT ALL SPECIFIED DIMENSIONS | | | WILL BE PROVIDED IN FIELD TO AVOID CONFLICTS/DELAYS). | | | | | | RESPONSE: | | | REPEAT COMMENT. THE LAVATORY REVISED POSITION DOESN'T | | | ALLOW A FORWARD APPROACH AS REQUIRED BY SEC. 606.2 | | | FBC-ACCESSIBILITY. ALSO, UNISEX RESTROOM AND ADJACENT | | | BATHROOM DON'T COMPLY WITH THE OVERLAP REQUIREMENTS OF | | | SEC. 604.3.2 FBC-ACCESSIBILITY AND WITH RESTROOM | | | FIXTURE CLEARANCE DETAIL SHOWN ON SHEET A-5. REVISE AS | | | REQUIRED. THE DOTTED LINE SHOWING THE WATER CLOSET AND | | | LAVATORY CLEARANCE ARE NOT DRAWN TO SCALE. BESIDES, | | | SHEET A-2 DOESN'T PROVIDE THE DIMENSIONS FOR THESE | | | ROOMS. THEREFORE, I AM UNABLE TO VERIFY COMPLIANCE. | | | SCALING DRAWINGS IS NOT ALLOWED. WRITTEN DIMENSIONS | | | TAKE PRECEDENCE. REVISE PLANS AS REQUIRED. | | | NOTE: THERE ARE MANY AREAS IN THESE DRAWINGS THAT ARE | | | NOT DRAWN TO SCALE AND DON'T REFLECT THE GIVEN | | | DIMENSION. FOR EXAMPLE NOT ALL CORRIDORS MEASURE 60" AS | | | SPECIFIED ON SHEET A-4. THESE WAS NOTED ON PREVIOUS | | | COMMENT. | | | SPECIFY THE SIZE OF EXISTING DOOR #3. TO VERIFY | | | COMPLIANCE WITHOUT EH MINIMUM CLEAR WIDTH OPENING. | | | ALSO, CLARIFY WHY DOOR HARDWARE FOR THESE TWO BATHROOMS | | | IS DIFFERENT THAN THE OTHER BATHROOMS. CLEARLY SPECIFY | | | THE DOOR HARDWARE FOR ALL DOORS TO VERIFY COMPLIANCE | | | WITH SEC. 309 FBC-ACCESSIBLE. | | | | | | 3- ORIGINAL COMMENT: | | | THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE | | | MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED. | | | AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL | | | DESIGN PRESSURES (VASD). | | | | | | RESPONSE: | | | REPEAT COMMENT. PARTIALLY ADDRESSED. REVISED DESIGN | | | PRESSURES SHOWN ON SHEET A-4 ARE INCORRECT AND ARE NOT | | | CLEAR. CLARIFY WHY SPECIFYING TWO DIFFERENT MEAN ROOF | | | HEIGHTS. THE ADJUSTMENT FACTOR FOR A MEAN ROOF HEIGHT | | | OF 20' ' IS 1.29 NOT 1.21. AND THE ADJUSTMENT FACTOR | | | FOR A MEAN ROOF HEIGHT OF 24' IS 1.35 NOT 1.21. REVISE | | | AS REQUIRED. SEE TABLE 1609.7(2) FBC. | | | | | | 4- WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS | | | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & | | | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN | | | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF | | | INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | | | | 5- ORIGINAL COMMENT: | | | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS AND EXHAUST FANS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | RESPONSE: | | | A) ENTRANCE DOOR NOA 17-1114.01 SUBMITTED. CLEARLY | | | SPECIFY DOOR AND GLASS TYPE AS REQUIRED BY THE | | | INSTRUCTIONS ON DRAWING W17-54 SUBMITTED. | | | NOTE: PRODUCT APPROVAL MAY BE SUBMITTED LATER AS | | | "DEFERRED SUBMITTAL" AFTER THE PERMIT IS ISSUED, BUT | | | BEFORE ANY INSPECTIONS TO AVOID CONFLICT DELAYS. | | | | | | 6- ORIGINAL COMMENT: | | | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 7- ORIGINAL COMMENT: | | | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 8- BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 9- PLEASE NOTE A THOROUGH REVIEW COULD NOT BE COMPLETED | | | IN THIS REVIEW AND DEPENDING ON THE RESPONSE COMMENTS | | | ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING REVIEWS. | | | 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 10- WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | | | | NEW COMMENTS: | | | | | | 11- SLEEPING ROOMS NEED TO HAVE SEPARATION WALLS WITH | | | FIRE PARTITIONS AS REQUIRED BY SEC. 420..2 FBC. | | | IDENTIFY WALL IN PLANS AND PROVIDE FIRE RATED WALL | | | DETAIL AND SPECIFICATIONS. | | | NOTE: I APOLOGIZE. IT WAS OVERLOOKED ON PREVIOUS | | | REVIEW. I TAUGHT THEY WERE SPECIFIED AS FIRE RATED | | | WALLS. | | | | | | 12- PARKING CALCULATIONS INFORMATION ON SHEET P-1 NEEDS | | | TO BE REVISED TO REFLECT THE ACTUAL NUMBER OF PARKING | | | SPACES SHOWN ON-THE REVISED PLOT PLAN. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | 13-CLARIFICATION: MINIMUM REQUIRED CORRIDOR WIDTH IS | | | 44" NOT 42". TABLE 1020.2 FBC. REVISE INFORMATION ON | | | SHEET A-4 AS REQUIRED. | | | | | | 14- THE FENCED YARD NEEDS TO BE ACCESSIBLE. SEC. | | | 206.2.2 FBC ACCESSIBLE. | | | | | | 15- SINCE SOME AREAS OF THE FLOOR PLAN SUBMITTED ARE | | | NOT DRAWN TO A TRUE SCALE, THEN IS HARD TO VERIFY DOOR | | | MANEUVERING CLEARANCES BASED ON THE PUSH SIDE, PULL | | | SIDE APPROACH AND THE SPECIFIED DOOR HARDWARE. IT LOOKS | | | LIKE SOME AREAS MAY NOT COMPLY. PROVIDE DIMENSIONS ON | | | PLANS. CHECK THE KITCHEN AREA. CHECK IN-TAKE AND | | | NURSE/MED OFFICE AND CORRIDOR ON THE RIGHT HAND SIDE. | | | SEE FIGURE 404.2.4.1 FBC ACCESSIBLE AND REVISE AS | | | REQUIRED. | | | | | | | | | NOTE: | | | ARCHITECTS-ENGINEERS | | | FLORIDA STATUTE 553.80(2)(B): | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW | | | | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY | | | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-04-27 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-04-27 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2018-04-26 19:10:08 | SECOND BUILDING REVIEW CHECKLIST | | | CODE: FBC 6TH EDITION (2017). | | | | | | | | | 1) COMPLIED. | | | | | | 2) SHEET A-4/ BUILDING DATA & DESIGN: | | | 2A)COMPLIED. | | | | | | 2B)SEMI-COMPLIED. SPECIFY THE OCCUPANT LOAD OF THE | | | LIVING/DINING AREA. SEE TABLE 1004.1.2. CLARIFY WHAT IS | | | INSTITUTIONAL AREA?. CLEARLY OUTLINE ON PLAN EACH AREA. | | | REVISE TOTAL OCCUPANT LOAD AS REQUIRED. NOTE: ANY | | | FRACTION SHOWN ON THE OCCUPANT LOAD CALCULATIONS NEEDS | | | TO BE ROUNDED UP NOT ROUNDED DOWN. | | | | | | ORIGINAL COMMENT: | | | OCCUPANT LOAD FACTOR IS TAKEN AT 50 SQ. OCCUPANT. | | | PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2 | | | MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT | | | INPATIENT TREATMENT AREAS 240 GROSS | | | OUTPATIENT AREAS 100 GROSS | | | SLEEPING AREAS 120 GROSS | | | PLEASE UPDATE PLANS. | | | | | | 2C) SEMI-COMPLIED. INFORMATION SUBMITTED IS NOT CLEAR. | | | RESPONSE LETTER STATES I-1 ALCOHOL AND DRUG | | | CENTERS/CONGREGATE CARE FACILITIES AND INFORMATION ON | | | SHEET A-4 SPECIFIES "FIRE PREVENTION RESIDENTIAL | | | BOARDING & CARE". CLARIFY WHAT IS "FIRE PREVENTION | | | RESIDENTIAL BOARDING & CARE". AND, CLEARLY DEFINE | | | SPECIFIC USE. ALSO, NEED TO CLASSIFY WHICH I-1 | | | CONDITION IS PROPOSED AS REQUIRED BY SEC. 308.3 | | | FBC-BUILDING. CONDITION 1 OR CONDITION 2. | | | | | | ORIGINAL COMMENT: | | | THE BUILDING DATA LIST THIS OCCUPANCY AS AN I-2 | | | OCCUPANCY PLEASE DECLARE THE END USE? | | | FBC-B 308.4 INSTITUTIONAL GROUP I-2. DETOXIFICATION | | | FACILITY/ NURSING HOME | | | FBC-B 308.3 INSTITUTIONAL GROUP I-1. ALCOHOL AND DRUG | | | CENTERS / CONGREGATE CARE FACILITIES | | | FBC-B 310.6 RESIDENTIAL GROUP R-4. RESIDENTIAL GROUP | | | R-4. ALCOHOL AND DRUG CENTERS, CONGREGATE CARE | | | FACILITIES. RESIDENTIAL GROUP R-4 OCCUPANCY SHALL | | | INCLUDE BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR | | | MORE THAN FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING | | | STAFF, WHO RESIDE ON A 24-HOUR BASIS IN A SUPERVISED | | | RESIDENTIAL ENVIRONMENT AND RECEIVE CUSTODIAL CARE. | | | UNTIL THE END USE IS GIVEN THE LIFE SAFETY ISSUES | | | CANNOT BE DETERMINED. | | | FBC-B 407 GROUP I-2 DETOXIFICATION | | | FBC-B 420 I-1, R-3/ R-4. | | | | | | 2D) SEMI-COMPLIED. CLARIFY WHY THE FURNITURE LAYOUT | | | ONLY SHOW THE DESK IN THE OFFICES AND THE CHAIRS ARE | | | NOT SHOWN. | | | NOTE: KEEP IN MIND MANEUVERING CLEARANCES REQUIRED FOR | | | PROPER DOOR OPERATION. | | | | | | ORIGINAL COMMENT: | | | PLEASE PROVIDE A FLOOR PLANS SHOWING THE FURNITURE | | | LAYOUT INCLUDING BEDS TO SEE OCCUPANT LOADS FOR THE | | | SLEEPING ROOMS. TO HELP IN THE DEFINING OF THE END USE. | | | | | | 2E) COMPLIED. PLOT PLAN PROVIDED. | | | | | | 2F)COMPLIED. PLOT PLAN PROVIDED. | | | | | | 2G) PASSENGER LOADING ZONE SHOWN ON THE PLOT PLAN NEEDS | | | TO COMPLY WITH ALL THE REQUIREMENTS OF SEC. 503.3 | | | FBC-ACCESSIBILITY. SEE 503.1 THRU 503.4 AND REVISE PLOT | | | PLAN AS REQUIRED. ALSO, REVISE THE PARKING INFORMATION | | | SHOWN ON THE PLOT PLAN SUBMITTED. PROVIDE INFORMATION | | | THAT RELATES TO PROPOSED USE. THERE ARE NOT MEDICAL | | | OFFICES AND DOCTORS. | | | | | | ORIGINAL COMMENT: | | | THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM | | | CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE | | | COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE | | | ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED | | | LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY | | | EXCEEDS TWENTY-FOUR HOURS. | | | | | | 2H)SEMI-COMPLIED. UNITS COMPLYING WITH THE UNIT | | | MOBILITY TO CLEARLY SHOW COMPLIANCE WITH THE TURNING | | | SPACE SEC. 805.2 FBC-ACCESSIBILITY. REVISE THE TURNING | | | SPACE TO COMPLY WITH FIGURE 304.3.2 FBC-ACCESSIBILITY. | | | | | | ORIGINAL COMMENT: | | | THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 223.2 HOSPITALS, REHABILITATION | | | FACILITIES, PSYCHIATRIC FACILITIES AND DETOXIFICATION | | | FACILITIES. HOSPITALS, REHABILITATION FACILITIES, | | | PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES | | | SHALL COMPLY WITH 223.2. | | | ACCESS. CODE223.2.1 FACILITIES NOT SPECIALIZING IN | | | TREATING CONDITIONS THAT AFFECT MOBILITY. IN FACILITIES | | | NOT SPECIALIZING IN TREATING CONDITIONS THAT AFFECT | | | MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER THAN ONE, | | | OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE MOBILITY | | | FEATURES COMPLYING WITH 805. ACCESSIBLE PATIENT | | | BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS | | | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. | | | | | | 2I)805 MEDICAL CARE AND LONG-TERM CARE FACILITIES. | | | 805.1. COMPLIED. | | | | | | 805.2 SEMI-COMPLIED. REVISE T-SHAPED TURNING SPACE. SEE | | | FIGURE 304.3.2 FBC-ACCESSIBILITY. | | | | | | ORIGINAL COMMENT: | | | TURNING SPACE. TURNING SPACE COMPLYING WITH 304 SHALL | | | BE PROVIDED WITHIN THE ROOM. | | | | | | 805.3 . COMPLIED. | | | | | | 805.4. UNISEX RESTROOM AND ADJACENT BATHROOM DON'T | | | COMPLY WITH THE OVERLAP REQUIREMENTS OF SEC. 604.3.2 | | | FBC-ACCESSIBILITY. | | | AND WITH RESTROOM FIXTURE CLEARANCE DETAIL SHOWN ON | | | SHEET A-5. REVISE AS REQUIRED. | | | (NOTE: SHOWER IS NOT DRAWN TO SCALE IN THIS ROOM. ALSO, | | | SOME ROOMS AND CORRIDORS ARE NOT DRAWN TO THE SPECIFIED | | | DIMENSIONS. PLEASE VERIFY THAT ALL SPECIFIED DIMENSIONS | | | WILL BE PROVIDED IN FIELD TO AVOID CONFLICTS/DELAYS). | | | | | | ORIGINAL COMMENT: | | | TOILET AND BATHING ROOMS. TOILET AND BATHING ROOMS THAT | | | ARE PROVIDED AS PART OF A PATIENT OR RESIDENT SLEEPING | | | ROOM SHALL COMPLY WITH 603. WHERE PROVIDED, NO FEWER | | | THAN ONE WATER CLOSET, ONE LAVATORY, AND ONE BATHTUB OR | | | SHOWER SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF | | | 603 THROUGH 610. | | | | | | 2J)COMPLIED. | | | | | | 2K) THE CLEAR FLOOR SPACE DRAWN ON SHEET A-7 IS NOT TO | | | SCALE. IT DOESN'T MEASURE 30"X48". REVISE AS REQUIRED. | | | | | | ORIGINAL COMMENT: | | | THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE ) 226.1 WHERE DINING SURFACES ARE | | | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST | | | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT | | | THE DINING SURFACES SHALL COMPLY WITH 902. | | | | | | 2K(1) COMPLIED. | | | | | | 2K(2) COMPLIED. | | | | | | 2K)(3) COMPLIED. | | | | | | 2K)(4) COMPLIED. | | | | | | 3) SHEET A-4 CERTIFICATION FOR DESIGN COMPLIANCE: | | | 3A) COMPLIED. | | | | | | 3B) COMPLIED. | | | | | | 3C) COMPLIED. | | | | | | 3D) THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE | | | MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED. | | | AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL | | | DESIGN PRESSURES (VASD). | | | | | | ORIGINAL COMMENT: | | | PLEASE UPDATE WALL PRESSURES PROVIDE A CHART IN VASD | | | FOR 10 SQ. FT., 20 SQ. FT. 50 SQ. FT. & 100 SQ. FT. FOR | | | WALL ZONES 4 & 5. | | | | | | 3E) THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE | | | MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED. | | | AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL | | | DESIGN PRESSURES (VASD). | | | | | | ORIGINAL COMMENT: | | | THE DESIGN PRESSURE CHART FOR THE ROOF ZONES 1,2 & 3 IS | | | MARKED NOT APPLICABLE, THE PLANS INDICATE A MEAN ROOF | | | HEIGHT OF 20 FT. AND 4 FOOT PARAPET. ROOF ZONES 1, 2 & | | | 3 NOT APPLICABLE. PLEASE NOTE THE PARAPET ON THE NORTH | | | SIDE OF THE BUILDING IS BETWEEN 18 -24 INCHES TALL THUS | | | CREATING ROOF ZONE 3. | | | 2017 FBC-B TABLE 1609.6.2, ASCE 7-10. | | | | | | 3F) COORDINATE WITH ITEMS # 3D AND #3E ABOVE. | | | | | | ORIGINAL COMMENT: | | | PLEASE PROVIDE THE PRESSURES FOR ALL ROOF ZONES IN | | | VASD. THE MECHANICAL SHEET M3.3 SHOWS NEW ROOF TOP | | | CURBS AND DOWN UNITS AS WELL AS A/C STANDS IT APPEARS | | | THERE WILL BE ROOFING WORK INVOLVED AS WELL AS NEW ROOF | | | TOP OPENINGS. MECHANICAL SHEET M3.3 DETAILS I &J | | | INDICATE SEE ARCHITECTURAL SHEETS. 107.2.1.3 | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 4) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS | | | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & | | | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN | | | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF | | | INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | | | | 5) NEED ALL THE PRODUCT APPROVALS (2 COPIES). NOTE: | | | PRODUCT APPROVAL MAY BE SUBMITTED LATER AS "DEFERRED | | | SUBMITTAL" AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY | | | INSPECTIONS TO AVOID CONFLICT DELAYS. | | | | | | ORIGINAL COMMENT: | | | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS AND EXHAUST FANS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 6) COORDINATE WITH ITEM #5 ABOVE. | | | | | | ORIGINAL COMMENT: | | | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 7) COORDINATE WITH ITEM #5 ABOVE. | | | | | | ORIGINAL COMMENT: | | | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. | | | | | | 8) COORDINATE WITH ITEM #5 ABOVE. | | | | | | ORIGINAL COMMENT: | | | ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL | | | ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR | | | ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, | | | IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. | | | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH | | | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE | | | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION | | | PREPARED, SIGNED AND | | | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR | | | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & | | | CLADDING. | | | | | | 9)COORDINATE WITH ITEM #5 ABOVE. | | | | | | ORIGINAL COMMENT: | | | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP | | | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | | | | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | | | | 10) COORDINATE WITH ITEM #5 ABOVE. | | | | | | ORIGINAL COMMENT: | | | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED./ 2017 | | | FBC-B 1604.4 ANALYSIS. | | | FOR ROOF TOP A/C STAND PRODUCT APPROVAL PROVIDE A (2) | | | COPIES OF THE PRODUCT APPROVAL REVIEWED BY THE DESIGNER | | | OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS | | | CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP | | | COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF | | | HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED | | | THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT | | | VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND | | | TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY | | | THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO | | | THE BUILDING DEPARTMENT. | | | | | | 11) COORDINATE WITH ITEM #5 ABOVE. | | | | | | ORIGINAL COMMENT: | | | 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS | | | OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES | | | REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED | | | STRUCTURES AT A HEIGHT EXCEEDING 16 FEET , SUCH ACCESS | | | SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS OF | | | ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR | | | FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL | | | SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING | | | OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH OR | | | WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS | | | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). | | | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED | | | ACCESS. | | | | | | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 13) PLEASE NOTE A THOROUGH REVIEW COULD NOT BE | | | COMPLETED IN THIS REVIEW AND DEPENDING ON THE RESPONSE | | | COMMENTS ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING | | | REVIEWS. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | NOTE: | | | ARCHITECTS-ENGINEERS | | | FLORIDA STATUTE 553.80(2)(B): | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY | | | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-30 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-30 |
Time |
06:42 |
Sent To |
|
|
| Notes |
| 2018-01-30 09:39:14 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 18010936 | | | ADD: 4461 MEDICAL CENTER WAY | | | CONT: ERETZOR CONSTRUCTION LLC | | | TEL: 954-937-7041 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. JAN. 30/ 2018 | | | ACTION: DENIED | | | | | | 1) PLEASE CORRECT THE ADDRESS ON THE PERMIT APPLICATION | | | AND THE ARCHITECTURAL SHEETS. THE PCN NUMBER | | | 74-43-43-06-14-000-0012 IS 4461 MEDICAL CENTER WAY. | | | | | | 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED. 2017 FBC-B 101.2 ADDRESS | | | IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE | | | PROVIDED WITH APPROVED ADDRESS IDENTIFICATION. | | | | | | 2) SHEET A-4/ BUILDING DATA & DESIGN: | | | 2A) THE LAST KNOWN USE WAS A BUSINESS OCC. OCULOPLASTIC | | | & ORBITAL CONSULTANTS. THE PLAN LISTS THIS AS A LEVEL | | | II ALTERATION. THIS IS A CHANGE IN OCCUPANCY GOVERNED | | | BY THE 2017 FBC-EXISTING BUILDING CODE CHAPTER 10. SEE | | | 1001.2.2 CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP. | | | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING | | | CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012 | | | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY | | | CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN | | | OCCUPANCY CLASSIFICATION. | | | | | | 2B) OCCUPANT LOAD FACTOR IS TAKEN AT 50 SQ. OCCUPANT. | | | PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2 | | | MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT | | | INPATIENT TREATMENT AREAS 240 GROSS | | | OUTPATIENT AREAS 100 GROSS | | | SLEEPING AREAS 120 GROSS | | | PLEASE UPDATE PLANS. | | | | | | 2C) THE BUILDING DATA LIST THIS OCCUPANCY AS AN I-2 | | | OCCUPANCY PLEASE DECLARE THE END USE? | | | FBC-B 308.4 INSTITUTIONAL GROUP I-2. DETOXIFICATION | | | FACILITY/ NURSING HOME | | | FBC-B 308.3 INSTITUTIONAL GROUP I-1. ALCOHOL AND DRUG | | | CENTERS / CONGREGATE CARE FACILITIES | | | FBC-B 310.6 RESIDENTIAL GROUP R-4. RESIDENTIAL GROUP | | | R-4. ALCOHOL AND DRUG CENTERS, CONGREGATE CARE | | | FACILITIES. RESIDENTIAL GROUP R-4 OCCUPANCY SHALL | | | INCLUDE BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR | | | MORE THAN FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING | | | STAFF, WHO RESIDE ON A 24-HOUR BASIS IN A SUPERVISED | | | RESIDENTIAL ENVIRONMENT AND RECEIVE CUSTODIAL CARE. | | | UNTIL THE END USE IS GIVEN THE LIFE SAFETY ISSUES | | | CANNOT BE DETERMINED. | | | FBC-B 407 GROUP I-2 DETOXIFICATION | | | FBC-B 420 I-1, R-3/ R-4. | | | | | | 2D) PLEASE PROVIDE A FLOOR PLANS SHOWING THE FURNITURE | | | LAYOUT INCLUDING BEDS TO SEE OCCUPANT LOADS FOR THE | | | SLEEPING ROOMS. TO HELP IN THE DEFINING OF THE END USE. | | | | | | 2E) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 206.2.1 SITE ARRIVAL POINTS. | | | AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN | | | THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE | | | PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS; | | | AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE | | | BUILDING OR FACILITY ENTRANCE THEY SERVE. | | | | | | 2F) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 208.1 WHERE PARKING SPACES ARE | | | PROVIDED, PARKING SPACES SHALL BE PROVIDED IN | | | ACCORDANCE WITH 208. SEE SECTION 502.5 REQUIREMENTS FOR | | | VAN PARKING IN STRUCTURES. | | | | | | 2G) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM | | | CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE | | | COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE | | | ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED | | | LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY | | | EXCEEDS TWENTY-FOUR HOURS. | | | | | | 2H) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE 223.2 HOSPITALS, REHABILITATION | | | FACILITIES, PSYCHIATRIC FACILITIES AND DETOXIFICATION | | | FACILITIES. HOSPITALS, REHABILITATION FACILITIES, | | | PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES | | | SHALL COMPLY WITH 223.2. | | | ACCESS. CODE223.2.1 FACILITIES NOT SPECIALIZING IN | | | TREATING CONDITIONS THAT AFFECT MOBILITY. IN FACILITIES | | | NOT SPECIALIZING IN TREATING CONDITIONS THAT AFFECT | | | MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER THAN ONE, | | | OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE MOBILITY | | | FEATURES COMPLYING WITH 805. ACCESSIBLE PATIENT | | | BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS | | | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. | | | | | | 2I) 805 MEDICAL CARE AND LONG-TERM CARE FACILITIES. | | | 805.1. MEDICAL CARE FACILITY AND LONG-TERM CARE | | | FACILITY PATIENT OR RESIDENT SLEEPING ROOMS REQUIRED TO | | | PROVIDE MOBILITY FEATURES SHALL COMPLY WITH 805. | | | | | | 805.2 TURNING SPACE. TURNING SPACE COMPLYING WITH 304 | | | SHALL BE PROVIDED WITHIN THE ROOM. | | | | | | 805.3 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE | | | COMPLYING WITH 305 SHALL BE PROVIDED ON EACH SIDE OF | | | THE BED. THE CLEAR FLOOR SPACE SHALL BE POSITIONED FOR | | | PARALLEL APPROACH TO THE SIDE OF THE BED. | | | | | | | | | 805.4 TOILET AND BATHING ROOMS. TOILET AND BATHING | | | ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR | | | RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE | | | PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY, | | | AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE | | | APPLICABLE REQUIREMENTS OF 603 THROUGH 610. | | | | | | 2J) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH | | | FLOOR OR GROUND. | | | | | | TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES | | | (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND | | | SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST | | | TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE | | | BASELINE OF THE HIGHEST TACTILE CHARACTER. | | | | | | 2K) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017 | | | ACCESSIBILITY CODE ) 226.1 WHERE DINING SURFACES ARE | | | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST | | | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT | | | THE DINING SURFACES SHALL COMPLY WITH 902. | | | | | | 2K(1) 226.2 DISPERSION. DINING SURFACES AND WORK | | | SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED | | | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING | | | SURFACES AND WORK SURFACES. | | | | | | 2K(2) 902.1 .DINING SURFACES AND WORK SURFACES SHALL | | | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. | | | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, | | | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK | | | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, | | | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER | | | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON | | | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING | | | PROVISIONS, EMPLOYEE WORK STATIONS. | | | | | | 2K)(3) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 2K)(4) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | | | | 3) SHEET A-4 CERTIFICATION FOR DESIGN COMPLIANCE: | | | 3A) PLEASE NOTE THE RISK CATEGORY CHECKED OFF IS III. | | | IN THE 2017 FBC-B TABLE 1604.5 DOES INCLUDE GROUP I-2 | | | OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR MORE | | | RESIDENT CARE RECIPIENTS. THE OCCUPANT LOAD WILL BE | | | LESS THAN 50 WHEN CALCULATING THE FLOOR AREA STATED | | | ABOVE. RISK CATEGORY WILL BE CATEGORY II. | | | | | | 3B) THE WIND DESIGN IS GIVEN AS 160 MPH, VULT. PLEASE | | | REVIEW THE 2017 FBC-B FIGURE 1609.3(1) ULTIMATE DESIGN | | | WIND SPEED FOR RISK CATEGORY II BUILDINGS IS 170 MPH | | | VULT. | | | 3C) THE WIND DESIGN CRITERIA ALSO LIST THE EXPOSURE AS | | | B EXPOSURE. PLEASE UPDATE PLANS WHEN LOOKING AT WIND | | | YOU LOOK FROM ALL QUADRANTS AND THERE C ROUGHNESS. | | | 1609.4.3 2014 FBC-B THIS SURFACE ROUGHNESS SHALL ALSO | | | APPLY TO ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS | | | B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET | | | HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE | | | ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN | | | 600 FEET IN THE UPWIND DIRECTION AND A WIDTH GREATER | | | THAN 150 FEET. | | | 1609.4.3 2017 FBC-B SURFACE ROUGHNESS C. OPEN TERRAIN | | | WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY | | | LESS THAN 30 FEET . THIS CATEGORY INCLUDES FLAT OPEN | | | COUNTRY, AND GRASSLANDS. | | | | | | 3D) PLEASE UPDATE WALL PRESSURES PROVIDE A CHART IN | | | VASD FOR 10 SQ. FT., 20 SQ. FT. 50 SQ. FT. & 100 SQ. | | | FT. FOR WALL ZONES 4 & 5. | | | | | | 3E) THE DESIGN PRESSURE CHART FOR THE ROOF ZONES 1,2 & | | | 3 IS MARKED NOT APPLICABLE, THE PLANS INDICATE A MEAN | | | ROOF HEIGHT OF 20 FT. AND 4 FOOT PARAPET. ROOF ZONES 1, | | | 2 & 3 NOT APPLICABLE. PLEASE NOTE THE PARAPET ON THE | | | NORTH SIDE OF THE BUILDING IS BETWEEN 18 -24 INCHES | | | TALL THUS CREATING ROOF ZONE 3. | | | 2017 FBC-B TABLE 1609.6.2, ASCE 7-10. | | | | | | 3F) PLEASE PROVIDE THE PRESSURES FOR ALL ROOF ZONES IN | | | VASD. THE MECHANICAL SHEET M3.3 SHOWS NEW ROOF TOP | | | CURBS AND DOWN UNITS AS WELL AS A/C STANDS IT APPEARS | | | THERE WILL BE ROOFING WORK INVOLVED AS WELL AS NEW ROOF | | | TOP OPENINGS. MECHANICAL SHEET M3.3 DETAILS I &J | | | INDICATE SEE ARCHITECTURAL SHEETS. 107.2.1.3 | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 4) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS | | | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & | | | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN | | | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF | | | INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | | | | 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS AND EXHAUST FANS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. | | | | | | 8) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY | | | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES | | | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL | | | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF | | | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR | | | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN | | | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. | | | CALCULATION PREPARED, SIGNED AND | | | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR | | | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & | | | CLADDING. | | | | | | 9) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP | | | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | | | | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | | | | 10) 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED./ 2017 | | | FBC-B 1604.4 ANALYSIS. | | | FOR ROOF TOP A/C STAND PRODUCT APPROVAL PROVIDE A (2) | | | COPIES OF THE PRODUCT APPROVAL REVIEWED BY THE DESIGNER | | | OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS | | | CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP | | | COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF | | | HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED | | | THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT | | | VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND | | | TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY | | | THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO | | | THE BUILDING DEPARTMENT. | | | | | | 11) 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON | | | ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND | | | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR | | | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET , | | | SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED | | | MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM | | | GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? | | | LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE | | | CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH | | | OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS | | | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). | | | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED | | | ACCESS. | | | | | | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 13) PLEASE NOTE A THOROUGH REVIEW COULD NOT BE | | | COMPLETED IN THIS REVIEW AND DEPENDING ON THE RESPONSE | | | COMMENTS ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING | | | REVIEWS. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-04-30 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-04-30 |
Time |
13:42 |
Sent To |
I |
|
| Notes |
| 2018-04-30 13:55:15 | PROVISO ON PLAN FOR SEPARATE PERMIT REQUIREMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-02-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-02-05 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-02-05 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2018-02-05 12:47:41 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS | | | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF | | | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE | | | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, | | | 107.2.1 | | | 2. PROVIDE LOAD CALCULATION FOR WIREWAY, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | WIRE IS ADEQUATE. NEC 215.2, 220, 310.15(B)(16), 408.30 | | | 3. ALL RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION. | | | PROVIDE CORRECTION FOR FREEZER AND REFRIGERATOR. NEC | | | 210.8 | | | 4. OUTSIDE GFCI RECEPTACLES MUST BE WEATHERPROOF. | | | PROVIDE CORRECTION. NEC 406.9 | | | 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | | EC C405.6.1 | | | 6. PROVIDE NOTE FOR ELECTRIC WATER COOLER THAT THE GFCI | | | RECEPTACLE SHOWN SHALL BE READILY ACCESSIBLE. NEC 422.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2018-06-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-13 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-05-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-05-16 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-04-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-04-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-04-16 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-01-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-01-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-01-29 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2018-01-29 13:47:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET A 1 - THERE IS NO ADDRESS INDICATED WITHIN THE | | | TITLE BLOCK OF ANY PAGE. AN ADDRESS IS REQUIRED TO | | | ENSURE ACCURATE LOCATION IDENTIFICATION. | | | | | | ADDITIONALLY, PLEASE ENSURE THAT THE ADDRESS IS | | | CORRECT, THERE IS NO MEDICAL WAY IN WEST PALM BEACH. | | | THERE IS A MEDICAL CENTER WAY, PLEASE CLARIFY. | | | | | | PER NFPA 1: | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS ANDSPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | PLEASE PROVIDE AN ACCURATE ADDRESS. | | | | | | | | | | | | 2) SHEET A 4 - THERE IS NO INDICATION OF ANY COMPLIANCE | | | OF THE FLORIDA FIRE PREVENTION CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 6TH EDITION OF FLORIDA FIRE PREVENTIO | | | N CODE INCLUDING THE 2015 EDITION OF NFPA 1 AND NFPA | | | 101 AND ALL OTHER APPLICABLE CODES OR STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2013 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2013 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2013 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2013 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. | | | | | | PLEASE PROVIDE FOR THE REVIEW AND APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 3) SHEET A 4 - THERE IS AN INDICATION STATED THIS IS A | | | GRUOP: INSTITUTIONAL I2. WHAT WAS THE OCCUPANCY | | | PREVIOUSLY AND WHAT IS THE OCCUPANCY ACCORDING TO THE | | | FFPC. | | | | | | PER NFPA 1: | | | 1.7.12.5 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO | | | THE CHANGE OF OCCUPANCY OF ANY EXISTING BUILDING. | | | | | | PER NFPA 101: | | | 6.1 CLASSIFICATION OF OCCUPANCY. | | | 6.1.1 GENERAL. | | | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A | | | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR | | | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 | | | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE | | | SUBJECT TO THE RULING OF THE AUTHORITY HAVING | | | JURISDICTION WHERE THERE IS A QUESTION OF PROPER | | | CLASSIFICATION IN ANY INDIVIDUAL CASE. | | | | | | ADDITIONALLY, PLEASE ENSURE THAT ALL WINDOWS MEET THE | | | REQUIREMENTS PER THE APPLICABLE FFPC OCCUPANCY | | | CLASSIFICATION. | | | | | | PLEASE PROVIDE DETAILS OF WHAT THIS OCCUPANCY'S | | | ACTIVITIES AND THE OCCUPANCY CLASSIFICATION PER THE | | | FFPC. | | | | | | | | | | | | | | | 4) SHEET A 2 - THERE IS A REAR EXIT INDICATED LEADING | | | TO A FENCED-IN AREA WITH A GATE. THIS AREA IS NOT A | | | PUBLIC WAY, BUT EXIT ACCESS. THE GATE APPEARS TO BE THE | | | EXIT. DOES THIS GATE LEAD TO A PUBLIC WAY? | | | | | | PER NFPA 101: | | | | | | 7.7 DISCHARGE FROM EXITS. | | | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE | | | DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT | | | DISCHARGE, UNLESS OTHERWISE PROVIDED IN | | | 7.7.1.2 THROUGH 7.7.1.4. | | | 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS | | | OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH | | | AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO | | | A PUBLIC WAY. | | | | | | PLEASE PROVIDE DETAILS OF THE GATE AND ENTER THE GATE | | | INTO THE DOOR SCHEDULE WITH THE APPLICABLE | | | HARDWARE/LOACKING & LATCHING. | | | | | | | | | | | | | | | 5) SHEET A 2 - THE DOOR SCHEDULE INDICATED THE EXIT | | | DOORS # 3 - FRONT AND REAR AS EXISITNG; HOWEVER, NO | | | EXIT HARDWARE OF LOCKING TYPE IS INDICATED. | | | | | | PER NFPA 101 | | | 7.2 MEANS OF EGRESS COMPONENTS. | | | 7.2.1 DOOR OPENINGS. | | | 7.2.1.1 GENERAL. | | | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL | | | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND | | | TO THE SPECIAL REQUIREMENTS OF 7.2.1. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | | OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER | | | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE | | | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. | | | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 | | | SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 | | | THROUGH 23. | | | | | | PLEASE PROVIDE THE APPLICABLE INFORMATION AND AS | | | REQUIRED BY THE OCCUPANCY CLASSIFICATION TYPE OF # 3 | | | ABOVE. | | | | | | | | | | | | 6) SHEET A 2 - DOORS # 2 INDICATED IN THE EXIT PATH OF | | | TRAVEL AT THE CENTER CORRIDOR AT THE INTAKE AND | | | NURSE/MED ROOMS DO NOT HAVE THE DOOR HARDWARE NOTED. | | | | | | THESE DOORS CAN NOT BE LOCKED IN THE PATH OF EGRESS. | | | | | | PLEASE PROVIDE THE HARDWARE TYPE COMPLIANT WITH THE | | | EGRESS CODE. | | | | | | | | | | | | | | | 7) SHEET A 4 - THERE IS AN INDICATION THA THE BUILDING | | | IS FULLY SPRINKLER; HOWEVER, THERE ARE NO IDICATIONS OF | | | FIRE SPRINKLER WORK. | | | | | | PER NFPA 101 | | | 9.7 AUTOMATIC SPRINKLERS. | | | 9.7.1 GENERAL. | | | 9.7.1.1* EACH AUTOMATIC SPRINKLER SYSTEM REQUIRED BY | | | ANOTHER SECTION OF THIS CODE SHALL BE IN ACCORDANCE | | | WITH ONE OF THE FOLLOWING: | | | (1) NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER | | | SYSTEMS | | | (2) NFPA 13D, STANDARD FOR THE INSTALLATION OF | | | SPRINKLER SYSTEMS IN ONE- AND TWO-FAMILY DWELLINGS AND | | | MANUFACTURED HOMES | | | (3) NFPA 13R, STANDARD FOR THE INSTALLATION OF | | | SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES | | | | | | ALL WORK OF THE FIRE SPRINKLER SYSTEM SHALL BE DONE | | | THROUGH SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY | | | CONTRACTORS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AND | | | COMPLIANCE. | | | | | | | | | | | | | | | 8) SHEETS A 4 & E 1 - THERE ARE NO INDICATIONS OF FIRE | | | ALARM WORK. | | | | | | PER NFPA 101 | | | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | | 9.6.1* GENERAL. | | | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY | | | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS | | | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER | | | SYSTEM OR NEW FIRE ALARMSYSTEM IS REQUIRED BY THE | | | FLORIDA BUILDING CODE. | | | | | | 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL | | | BE INSTALLED, TESTED, AND MAINTAINED IN ACCORDANCE WITH | | | THE APPLICABLE REQUIREMENTS OF NFPA 70, NATIONAL | | | ELECTRICAL CODE, AND NFPA 72, NATIONAL FIRE ALARM AND | | | SIGNALING CODE, UNLESS IT IS AN APPROVED EXISTING | | | INSTALLATION, WHICH SHALL BE PERMITTED TO BE CONTINUED | | | IN USE. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AND | | | COMPLIANCE. | | | | | | | | | | | | | | | 9) SHEET E 3 - AN EXIT PATH OF TRAVEL IS INDICATED ON | | | SHEET A 4 LEADING FROM THE REAR CORRIDOR BY THE | | | NURSE/MED DOOR # 2; HOWEVER, THERE IS NO EXIT SIGN IN | | | THE REAR CORRIDOR LEADING IN THAT DIRECTION. | | | | | | PLEASE ADD AN EXIT SIGN IN THE REAR CORRIDOR AT THE | | | DOOR # 2 AT THE NURSE/MED ROOM AND SMALL CORRIDOR. | | | | | | | | | | | | 10) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS ON | | | ANY SHEET OF THE SUBMITTAL. | | | | | | PER NFPA 101 | | | PORTABLE FIRE EXTINGUISHERS. PORTABLE FIRE | | | EXTINGUISHERS SHALL BE PROVIDED IN ACCORDANCE WITH | | | SECTION 9.9. | | | | | | 9.9* PORTABLE FIRE EXTINGUISHERS. WHERE REQUIRED BY | | | ANOTHER SECTION OF THIS CODE, PORTABLE FIRE | | | EXTINGUISHERS SHALL BE SELECTED, INSTALLED,INSPECTED, | | | AND MAINTAINED IN ACCORDANCE WITH NFPA 10, STANDARD FOR | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | PLEASE PROVIDE LOCATIONS. | | | | | | | | | 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-06-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-22 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-22 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-04-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-24 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-24 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2018-04-24 12:51:45 | SEE NOTES AND RED LINES ON PLAN |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-02-15 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-02-15 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2018-02-15 14:43:45 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SHOW ON THE RISER TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, AND THE EHD NUMBER OF | | | CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE IF | | | BEING USED. WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 3. SHOW ON THE RISER TYPE OF GAS, (LP OR NATURAL). | | | | | | 5. SHOW ON THE RISER THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE | | | BUILDING AND/OR SYSTEM PER THE FBC-2014 FUEL GAS | | | APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4) & 2014 | | | FUEL GAS CODE SEC. 402.4.1. | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. PROVIDE A SINGLE DETAIL SHOWING THE TYPE, LOCATION, | | | LENGTH, SIZE AND TERMINATION OF THE GAS VENTS PER | | | FBC-2014 FUEL GAS CODE SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | | PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | | PER NFPA 58 SECTION 3-2.2.7(H). | | | | | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW | | | CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO | | | BE DOWN STREAM OF MANUAL VALVE. | | | | | | 13. SHOW THE REGULATORS ON RISER | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-06-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-22 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-08 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-05-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-26 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-07 |
Time |
15:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-04-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-04-12 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-02-15 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-24 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
5 |
Status |
P |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-27 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-27 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2018-07-27 11:34:55 | MU 2018 026280 0000, $4836.24 | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
F |
Date |
2018-06-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-06-14 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-06-14 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2018-06-14 18:50:06 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2018-05-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-26 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-26 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2018-05-26 17:01:50 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-04-30 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-04-30 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2018-04-30 11:34:49 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-01-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-30 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-30 |
Time |
06:42 |
Sent To |
|
|
| Notes |
| 2018-01-30 09:26:39 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-06-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-21 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-20 |
Time |
17:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-04-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-04-23 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-04-23 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-02-08 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-02-08 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2018-02-08 11:38:36 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18010936 | | | 2/8/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-2.2: THE MECHANICAL VENTILATION FOR THE | | | FACILITY SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE | | | WITH THE FBC-17 MECHANICAL, AND ASHRAE 170-2008- SEE | | | SECTION 407.1. PLEASE PROVIDE CALCULATIONS AND DESIGN | | | PARAMETERS FOR THE VENTILATION SYSTEM IN ACCORDANCE | | | WITH TABLE 7-1 ASHRAE 170. PLEASE NOTE THAT THE O/A | | | CALCULATION FOR AHU-4 ON THE PLANS IS NOT IN COMPLIANCE | | | WITH TABLE 403.1.1 FBC-17 MECHANICAL WHICH REQUIRES | | | DINING ROOMS TO BE CALCULATED AT 70 PERSONS PER 1000 | | | SQ. FT. AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SQ. FT. | | | | | | 2) M-2.2: PLEASE SHOW COMPLIANCE WITH SECTION 6.3.1 | | | ASHRAE 170-2008 WHICH REQUIRES THE O/A INTAKES TO BE | | | LOCATED A MINIMUM OF 25 FT. FROM EXHAUST AND VENT | | | DISCHARGES. | | | | | | 3) M-2.2: PERTAINING TO THE O/A INTAKES, INDICATE HOW | | | COMPLIANCE WITH SECTION 401.5 AND TABLE 401.5 WILL BE | | | MET. | | | | | | 4) INDICATE THE AIR FILTRATION SYSTEM AND SUPPLY AIR | | | OUTLETS ARE IN COMPLIANCE WITH TABLES 6-1 & 6-2 ASHRAE | | | 170. | | | | | | 5) M3-3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR | | | INSTALLATION OF THE CONDENSER STAND AND MOUNTING OF THE | | | CONDENSERS TO THE STAND. PROVIDE ENGINEERING FOR THE | | | STAND OR SUBMIT A VALID FL. PRODUCT APPROVAL OR | | | MIAMI-DADE NOA FOR THE STAND APPROVED BY THE EOR. SHOW | | | ON THE PLAN HOW THE STAND IS ATTACHED TO THE STRUCTURE- | | | SECTION 301.15. | | | | | | 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR | | | HANDLERS THAT INDICATES THE TYPES AND SIZES OF PIPINGS, | | | PIPING RUNS, AND TERMINATION LOCATIONS- SECTION 307. | | | | | | 7) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE | | | KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION SYSTEM. | | | PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.1.1 MAKEUP | | | AIR TEMPERATURE AND SECTION 301.15 WIND RESISTANCE WILL | | | BE REQUIRED. | | | | | | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | GAS-FIRED WATER HEATER AND COOKING APPLIANCES, AND | | | INDICATE HOW COMBUSTION AIR IS BEING PROVIDED. PROVIDE | | | THE MEANS AND THE CALCULATIONS IN ACCORDANCE WITH | | | SECTION FBC-17 FUEL GAS. | | | | | | 9) PROVIDE A VENTING PLAN FOR THE GAS WATER HEATER- | | | SECTION 503 FBC-17 FUEL GAS. SHOW THE TYPE AND SIZE OF | | | VENT FLUE, FLUE RUN AND TERMINATION LOCATION. ALL SHALL | | | BE IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND | | | PRODUCT LISTINGS. | | | | | | 10) PLEASE REFER TO SECTION C403.2.8 FBC-17 ENERGY | | | CONSERVATION AND SHOW COMPLIANCE: | | | | | | C403.2.8 KITCHEN EXHAUST SYSTEMS. REPLACEMENT AIR | | | INTRODUCED DIRECTLY INTO THE EXHAUST HOOD CAVITY SHALL | | | NOT BE GREATER THAN 10 PERCENT OF THE HOOD EXHAUST | | | AIRFLOW RATE. CONDITIONED SUPPLY AIR DELIVERED TO ANY | | | SPACE SHALL NOT EXCEED THE GREATER OF THE FOLLOWING: | | | | | | 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE | | | HEATING OR COOLING LOAD. | | | | | | 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER | | | AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS | | | CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT | | | REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS | | | RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION | | | OF ADJACENT SPACES. | | | | | | WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS | | | GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A | | | FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A | | | NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE | | | WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST | | | RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY | | | WITH ONE OF THE FOLLOWING: | | | | | | 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL | | | BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED. | | | | | | 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75 | | | PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS | | | THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT | | | AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY | | | TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION | | | AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE, | | | EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND | | | IDLE. | | | | | | 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT | | | RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON | | | NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW. | | | | | | WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER | | | APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM | | | ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL | | | BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE | | | DUTY RATING UNDER THE HOOD OR HOOD SECTION. | | | | | | EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE | | | REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE | | | EXHAUSTED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2018-06-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-22 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-22 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-23 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-22 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2018-05-23 08:41:07 | PROVISO: COMPLY PRIOR TO 1ST ROUGH INSPECTION. | | | | | | PREVIOUS COMMENT NOT COMPLIED 10. PROVIDE DETAIL FOR | | | THE SHOWER PANS. FBC PL 417.5.2 THE RESPONSE LETTER | | | FROM ENGINEER STATED THE ARCHITECT WOULD PROVIDE THAT | | | THE RESPONSE LETTER FROM THE ARCHITECT STATED THE | | | ENGINEER WOULD PROVIDE THE DETAIL. | | | PROVIDE MANUFACTURE SPECIFICATIONS FOR SHOWER PAN | | | LINER. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-04-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-24 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-24 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2018-04-24 12:19:08 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | PREVIOUS COMMENT NOT COMPLIED 10. PROVIDE DETAIL FOR | | | THE SHOWER PANS. 901.2.1 THE RESPONSE LETTER FROM | | | ENGINEER STATED THE ARCHITECT WOULD PROVIDE THAT THE | | | RESPONSE LETTER FROM THE ARCHITECT STATED THE ENGINEER | | | WOULD PROVIDE THE DETAIL. | | | | | | NEW COMMENT | | | 1. THE NEW SHOWER IN THE EXISTING BATHROOM 5+6 SHALL | | | COMPLY WITH ONE OF THE ACCESSIBLE SHOWER STALL | | | DIMENSIONS. THE DEPTH OF 36" BUT 48" DOES NOT COMPLY IT | | | SHALL BE 60"MIN OF 36" INSIDE DIMENSION. PER FBC ACC | | | 608.2.1 608.2.2, 608.2.3 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-02-15 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-02-14 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2018-02-15 14:32:31 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE OCCUPANT LOAD PLUMBING FIXTURE COUNT | | | BREAKDOWN FOR EMPLOYEES, VISITORS AND PATIENTS. PER FBC | | | TABLE 403.1 | | | | | | 2. WHAT TYPE OF FACILITY IS THIS GOING TO BE. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 3. SHOW COMPLIANCE WITH FBC ACC 610.3 SHOWER | | | COMPARTMENT SEATS. | | | WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER | | | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE | | | INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS, | | | AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3 | | | INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT | | | IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER | | | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE | | | INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND | | | SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT | | | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN | | | TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE | | | BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE | | | COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17 | | | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM | | | ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY | | | WITH 610.3.1 OR 610.3.2. | | | | | | 4. GRAB BARS SHALL BE FROM FINISH FLOOR MEASURED TO THE | | | TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 | | | | | | 5. PROVIDE THE DIMENSIONS FOR SHOWER ON EXTERIOR WALL | | | IN BATHROOM 5+6. 901.2.1 | | | | | | 6. SHOW COMPLIANCE WITH FBC ACC | | | 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS. | | | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, | | | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON | | | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) | | | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE | | | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL | | | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE | | | SEAT TOWARD THE SHOWER OPENING. | | | 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. | | | IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE | | | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE | | | LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 | | | INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT | | | IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY | | | UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO | | | THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM) | | | MAXIMUM FROM THE SEAT WALL. | | | | | | 7. SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER TYPE | | | SHOWER COMPARTMENTS. | | | IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE | | | PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A | | | POINT 18 INCHES (455 MM) FROM THE CONTROL WALL. | | | | | | 8. THE SHOWER IN BATHROOM 7+8 SHALL BE VENTED BEFORE IT | | | CONNECTS TO THE BUILDING DRAIN. PER FBC PL 901.2.1 | | | | | | 9. THE DETAILS FOR THE GREASE INTERCEPTOR SHALL COMPLY | | | WITH WPB UTILITIES DEPT STANDARD DETAIL GS-7 | | | | | | 10. PROVIDE DETAIL FOR THE SHOWER PANS. 901.2.1 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-04-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-27 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-27 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-02-15 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-02-15 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2018-02-15 14:36:02 | 1. THE DETAIL FOR GREASE INTERCEPTOR SHALL COMPLY WITH | | | WPB UTILITIES DEPT STANDARD DETAIL GS-7 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-06-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-06-15 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2018-06-20 15:37:34 | LANDSCAPE PERMIT REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-05-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-05-14 |
Time |
16:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-04-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-04-19 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2018-04-19 14:23:29 | FAILED | | | | | | 1.) WILL THE BUILDING FOOTPRINT BE ALTERED BY ANY OF | | | THE PROPOSED BUILDING IMPROVEMENTS? | | | 2.) PROVIDE A DESCRIPTION OF THE PROPOSED USE FOR THE | | | RENOVATED SPACE | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2018-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-02-13 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2018-02-13 10:11:04 | FAILED | | | | | | 1.) WILL THE BUILDING FOOTPRINT BE ALTERED BY ANY OF | | | THE PROPOSED BUILDING IMPROVEMENTS? | | | 2.) PROVIDE A DESCRIPTION OF THE PROPOSED USE FOR THE | | | RENOVATED SPACE | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |