Plan Review Details - Permit 18010931
Plan Review Stops For Permit 18010931
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-02-02 Cont ID  
Sent By rmcdouga Date 2018-02-02 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2018-02-02 Time 13:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-02 Cont ID  
Sent By rmcdouga Date 2018-02-02 Time 07:14 Rev Time 0.00
Received By rmcdouga Date 2018-02-02 Time 06:18 Sent To I
Notes
2018-02-02 07:14:39PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (REPEAT COMMENT) SPECIFY WHICH ONE OF THE APPROVED
 SYSTEMS LISTED IN THE PRODUCT APPROVAL FOR THE
 CERTAINTEED COVENTIONAL BUILT UP ROOF SYSTEM WILL BE
 USED. SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 16 NOA NO. 13-0204.14.
 THE SYSTEM THAT YOU SELECTED ON PAGE 13 OF THE PRODUCT
 APPROVAL HAS A MAXIMUM DESIGN PRESSURE OF -45PSF AND
 CAN NOT BE ENHANCED TO MEET THE INCREASED PRESSURES AT
 THE PERIMETER AND CORNER AREAS OF THE ROOF PER
 LIMITATION #9. SELECT A SYSTEM WHICH ALLOWS ENHANCED
 FASTENING (LIMITATION #7) AND SUBMIT SIGNED AND SEALED
 RAS 117 CALCULATIONS IN ACCORDANCE WITH GENERAL
 LIMITATION #7 ON THE LAST PAGE OF THE PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By rmcdouga Date 2018-01-26 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2018-01-26 Time 17:06 Sent To I
Notes
2018-01-26 18:56:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS LISTED IN
 THE PRODUCT APPROVAL FOR THE CERTAINTEED COVENTIONAL
 BUILT UP ROOF SYSTEM WILL BE USED. SUBMIT TWO SETS OF
 RAS 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED
 BY LIMITATION NUMBER 7 ON PAGE 16 NOA NO. 13-0204.14.
  
 2) YOU INDICATED THAT THE SLOPED ROOF HAS A 3:12 SLOPE.
 FBC-R905.2.2 REQUIRES DOUBLE UNDERLAYMENT INSTALLED IN
 ACCORDANCE WITH FBC-R905.1.1 FOR ASPHALT SHINGLE ROOFS
 WITH SLOPES LESS THAN 4:12.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-01-25 Cont ID  
Sent By destabro Date 2018-01-25 Time 16:22 Rev Time 0.00
Received By destabro Date 2018-01-25 Time 11:26 Sent To B
Notes
2018-01-25 16:23:541/25/2018 - RE-ROOF IN KIND (SHINGLE TO SHINGLE, FLAT
 TO FLAT) MEETS DESIGN GUIDELINES OF HISTORIC DISTRICT.
 DLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-02 Cont ID  
Sent By rmcdouga Date 2018-02-02 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2018-02-02 Time 13:34 Sent To  
Notes
2018-02-02 13:35:25CONTRACTOR BROUGHT IN NEW PRODUCT APPROVALS FOR THE
 FLAT ROOF.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-02 Cont ID  
Sent By rmcdouga Date 2018-02-02 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2018-01-31 Time 13:35 Sent To  
Notes
2018-02-01 13:35:56RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-26 Cont ID  
Sent By rmcdouga Date 2018-01-26 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2018-01-24 Time 16:13 Sent To  
Notes
2018-01-24 16:14:10ROUTED TO HISTORIC VIA ZONING INBOX


Account Summary | Usage Policy | Privacy Policy