| 2018-02-09 13:06:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE 7 AND 8 ON SHEET E3.1 SHOWS 3 RUNS OF 500 KCMIL |
| | COPPER TO THE 1200 AMP MAIN DISCONNECT(MAIN 3 OF 3), |
| | AND THEN TO THE GUTTER. THE TOTAL AMPACITY OF THIS WIRE |
| | IS 380 X 3 = 1140 AMPS, WHICH IS UNDERSIZED. PROVIDE |
| | CORRECTION. NEC 240.4(C) |
| | 2. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE FOR THE SPACE |
| | WHERE THE REVISION OCCURS. FBC EC C405.4.2 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |