Plan Review Details - Permit 18010834
Plan Review Stops For Permit 18010834
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-17 Cont ID  
Sent By jgomez Date 2018-05-17 Time 10:36 Rev Time 0.00
Received By jgomez Date 2018-05-17 Time 10:36 Sent To  
Notes
2018-05-17 10:47:10BUILDING REVIEW APPROVED WITH PROVISO:
  
 1-ELEVATION CERTIFICATE SUBMITTED: A) NEED ORIGINAL
 SEAL & SIGNATURE (NOT DIGITAL) AS REQ'D BY CHAPTER 472
 F.S. B) REVISE/CLARIFY THE LOWEST ADJACENT GRADE ( LAG
 13.9') AND THE HIGHEST ADJACENT GRADE (HAG 13.7").
 2- REVISE/CLARIFY ROOF LOADS. TALKED TO CORY CROSS
 (ARCH.) (REVISED DRAWING S-1 OK NOW 05/17/18).
 3- SUBMIT TRUSS DRAWINGS FOR REVIEW. NOTE:
 REVIEWED/APPROVED BY THE ARCHITECT.
 4- SURVEY SUBMITTED: REVISE FLOOD INFORMATION USING THE
 NEW FLOOD MAPS. AS OF OCTOBER 5TH, 2017 . NOTE: NEED TO
 COORDINATE WITH THE REQUIRED ELEVATION CERTIFICATES
 DURING CONSTRUCTION TO AVOID CONFLICTS/DELAYS.
 ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2018-05-14 Cont ID  
Sent By jgomez Date 2018-05-11 Time 17:11 Rev Time 0.00
Received By jgomez Date 2018-05-10 Time 18:21 Sent To  
Notes
2018-05-10 18:34:4005/14/18 TALKED TO CORY CROSS (ARCH.) TO GO OVER ROOF
 LOADS. WAITING FOR REVISED PLAN TO FINISH PROCESSING
 PERMIT.
  
  
 1-ELEVATION CERTIFICATE SUBMITTED: A) NEED ORIGINAL
 SEAL & SIGNATURE (NOT DIGITAL) AS REQ'D BY CHAPTER 472
 F.S. B) REVISE/CLARIFY THE LOWEST ADJACENT GRADE ( LAG
 13.9') AND THE HIGHEST ADJACENT GRADE (HAG 13.7").
 2- REVISE/CLARIFY ROOF LOADS. TALKED TO CORY CROSS
 (ARCH.)
 3- SUBMIT TRUSS DRAWINGS FOR REVIEW. NOTE:
 REVIEWED/APPROVED BY THE ARCHITECT.
 4- SURVEY SUBMITTED: REVISE FLOOD INFORMATION USING THE
 NEW FLOOD MAPS. AS OF OCTOBER 5TH, 2017 . NOTE: NEED TO
 COORDINATE WITH THE REQUIRED ELEVATION CERTIFICATES
 DURING CONSTRUCTION TO AVOID CONFLICTS/DELAYS.
 ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jgomez Date 2018-03-14 Time 16:23 Rev Time 0.00
Received By jgomez Date 2018-03-14 Time 10:27 Sent To  
Notes
2018-03-08 12:35:35RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- STRUCTURE IS LOCATED IN FLOOD ZONE AE (BFE:12.1).
 BASED ON THE VALUE OF THE EXISTING STRUCTURE, THE
 PROPOSED ADDITION IS CONSIDERED "SUBSTANTIAL
 IMPROVEMENT". THE ADDITION AND THE EXISTING STRUCTURE
 NEED TO BE RAISED 2 FEET ABOVE THE BASE FLOOD ELEVATION
 AS REQUIRED BY CITY ORDINANCE 4729-17. NOTE: PLANS TO
 SHOW COMPLIANCE WITH THE FLOOD RESISTANT CONSTRUCTION
 SEC. R322.1 FBC-RESIDENTIAL. AND, ALL PLANS, SURVEYS,
 ETC TO SPECIFY THE PROPOSED FINISH FLOOR ELEVATION
 BASED ON THE REVISED FLOOD MAPS OF 10/05/17.
  
 SUBSTANTIAL IMPROVEMENT DEFINITION:
 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIR, RECONSTRUCTION, REHABILITATION, ALTERATION,
 ADDITION, OR OTHER IMPROVEMENT OF A BUILDING OR
 STRUCTURE, FOR WHICH THE CUMULATIVE COST IN ANY FIVE
 YEAR PERIOD EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET
 VALUE OF THE BUILDING OR STRUCTURE AT THE END OF THE
 FIVE YEAR PERIOD AND BEFORE THE IMPROVEMENT OR REPAIR
 IS STARTED. IF THE STRUCTURE HAS INCURRED "SUBSTANTIAL
 DAMAGE," ANY REPAIRS ARE CONSIDERED SUBSTANTIAL
 IMPROVEMENT REGARDLESS OF THE ACTUAL REPAIR WORK
 PERFORMED.
  
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 CODE OF ORDINANCES
 / CHAPTER 18 - BUILDINGS AND BUILDING REGULATIONS
 / ARTICLE II. - BUILDING CODE
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET OR
 THE DESIGN FLOOD ELEVATION
  
 2- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 3- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 4- REVISE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS
 SHOWN ON SHEET A3. TAPERED BUCKS ARE NOT ALLOWED. SEC.
 R609.7.2 FBC-RESIDENTIAL.
  
 5- WINDOW SCHEDULE ON SHEET A1: CLEARLY SPECIFY TYPE OF
 WINDOW (FOR EXAMPLE SINGLE HUNG). SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- GRAVITY LOADS ON SHEET S1 ARE NOT CLEAR: CLEARLY
 SPECIFY ALL LIVE LOADS AND ALL DEAD LOADS AT TOP AND
 BOTTOM OF ROOF TRUSSES. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: SEE TABLE R301.5 FBC-RESIDENTIAL FOR REQUIRED
 LIVE LOADS. ALSO, COORDINATE WITH LIVE LOAD SPECIFIED
 ON NOTE BELOW THE TRUSS ANCHOR CONNECTOR ON SHEET S2.
  
 7- SURVEY SUBMITTED: REVISE FLOOD INFORMATION USING THE
 NEW FLOOD MAPS. AS OF OCTOBER 5TH, 2017 THE CITY HAS
 ADOPTED NEW FLOOD INSURANCE RATE MAPS WHICH USE NAVD 88
 AS THE VERTICAL DATUM. THE CITY ALSO ADOPTED A 2'
 FREEBOARD WHICH REQUIRES THE FINISH FLOOR AND EQUIPMENT
 TO BE A MINIMUM OF TWO FEET ABOVE THE BFE.
 CITY ORDINANCE 4729-17. SEE SURVEY NOTES. SURVEY CAN
 NOT BE USED FOR CONSTRUCTION PURPOSES.
  
 8- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) ITEM #10 IS INCORRECT. PLANS CALL FOR VENTED ATTIC.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B) ITEM #14 IS INCORRECT. CLARIFY WHY THE WATER HEATER
 SYSTEM IS NOT REQUIRED. THIS IS A NEW WATER HEATER.
 WATER HEATER IS REQUIRED. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) CEILING R-VALUE SHOWN ON PAGE 2 OF 4 IS INCORRECT.
 PLANS CALL FOR R-20 BATT INSULATION. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. NOTE:
 SEE EXTERIOR ELEVATIONS.
  
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-RESIDENTIAL.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) PEEL & STICK ROOF UNDERLAYMENT AS SPECIFIED ON WALL
 SECTIONS ON SHEET A3.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGN PROFESSIONAL TO LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By jpearson Date 2018-05-02 Time 11:08 Rev Time 0.00
Received By jpearson Date 2018-05-02 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By jpearson Date 2018-02-16 Time 11:23 Rev Time 0.00
Received By jpearson Date 2018-02-16 Time 11:23 Sent To  
Notes
2018-02-16 11:23:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A FEED FROM THE METER TO THE
 INTERIOR PANEL WHICH IS LOCATED IN THE HALLWAY.
 CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR
 DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE
 IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE
 OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB.
 IF CONDUCTORS ARE INSTALLED UNDER THE SLAB, THEN THERE
 SHOULD NOT BE AN EQUIPMENT GROUNDING CONDUCTOR IN THIS
 CONDUIT. PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE
 E3601.6
 2. AFCI PROTECTION NOTE DOES NOT COVER ALL AREAS
 REQUIRED PER NEW CODE. THIS NOTE AND ELECTRICAL NOTE 1
 ARE CONFLICTING AND SHOULD STATE: BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 3. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH WOULD REQUIRE A 25 AMP BREAKER.
 PROVIDE CORRECTION. NEC 422.13; FBC RE E3702.10
 4. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". BECAUSE THE LED
 FIXTURE IN THE MASTER CLOSET IS NOT SPECIFIED, PROVIDE
 NOTE THAT LIGHTING SHALL COMPLY WITH NEC 410.16; FBC RE
 E4003.12.
 5. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 7. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN
 PENINSULA. NEC 210.8, 210.52(C)(3); FBC RE E3901.4.3
 8. CIRCUIT FOR BATH 3 IS SHOWN WITH HALLWAY. A MINIMUM
 OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS. PROVIDE CORRECTION. NEC
 210.11(C)(3) , FBC RE E3703.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-17 Cont ID  
Sent By jgomez Date 2018-05-17 Time 10:51 Rev Time 0.00
Received By jgomez Date 2018-05-17 Time 10:35 Sent To  
Notes
2018-05-17 10:35:55MIKE SUBMITTED REVISED DRAWING S1.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-11 Cont ID  
Sent By jgomez Date 2018-05-11 Time 18:25 Rev Time 0.00
Received By jgomez Date 2018-04-12 Time 14:58 Sent To I
Notes
2018-04-13 14:58:50R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-14 Cont ID  
Sent By jgomez Date 2018-03-14 Time 16:30 Rev Time 0.00
Received By jgomez Date 2018-01-23 Time 14:18 Sent To I
Notes
2018-01-24 14:18:59R13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-05-18 Cont ID  
Sent By cthroop Date 2018-05-18 Time 16:06 Rev Time 0.00
Received By cthroop Date 2018-05-18 Time 16:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-05-11 Cont ID  
Sent By jgomez Date 2018-05-11 Time 18:09 Rev Time 0.00
Received By jgomez Date 2018-05-11 Time 18:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jgomez Date 2018-03-14 Time 12:26 Rev Time 0.00
Received By jgomez Date 2018-03-14 Time 12:26 Sent To  
Notes
2018-03-14 12:26:291- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-17 Cont ID  
Sent By cmontell Date 2018-04-17 Time 14:18 Rev Time 0.00
Received By cmontell Date 2018-04-17 Time 14:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-20 Cont ID  
Sent By cmontell Date 2018-02-20 Time 15:22 Rev Time 0.00
Received By cmontell Date 2018-02-20 Time 15:22 Sent To B
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2018-06-20 Cont ID  
Sent By jgomez Date 2018-06-20 Time 08:27 Rev Time 0.00
Received By jgomez Date 2018-06-20 Time 08:26 Sent To  
Notes
2019-10-23 16:56:49SUBSTANTIAL IMPROVEMENT; NEED ELEVATION CERTIFICATE;
 ADDITION NEEDS TO MATCH EXISTING, NEW MECHANICAL
 EQUIPMENT TO COMPLY W/DFE
 EMAILED REMINDER TO CONTRACTOR ON 10/23/19
2018-06-20 08:28:34ELEVATION CERTIFICATE FOR EXISTING HOUSE ONLY.

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-17 Cont ID  
Sent By jgomez Date 2018-05-17 Time 10:51 Rev Time 0.00
Received By jgomez Date 2018-05-17 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status   Date 2018-05-11 Cont ID  
Sent By jgomez Date 2018-05-11 Time 18:26 Rev Time 0.00
Received By jgomez Date 2018-05-11 Time 18:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-02-16 Cont ID  
Sent By thunt Date 2018-02-16 Time 14:26 Rev Time 0.00
Received By thunt Date 2018-02-16 Time 14:26 Sent To  
Notes
2018-02-16 14:26:56NEEDS SUB PERMITS FOR IRRIGATION AND IRRIGATION
 BACKFLOW.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-05-11 Cont ID  
Sent By jgomez Date 2018-05-11 Time 18:23 Rev Time 0.00
Received By jgomez Date 2018-05-11 Time 17:13 Sent To  
Notes
2018-05-11 18:25:08APPROVED:
 1) SHINGLES NOA 16-0425.01
 2- RIDGE VENT NOA: 14-1224.18.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jgomez Date 2018-03-14 Time 16:28 Rev Time 0.00
Received By jgomez Date 2018-03-14 Time 16:28 Sent To  
Notes
2018-03-14 16:29:541- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) PEEL & STICK ROOF UNDERLAYMENT AS SPECIFIED ON WALL
 SECTIONS ON SHEET A3.
  
  
  
 APPROVED:
 1) SHINGLES NOA 16-0425.01
 2- RIDGE VENT NOA: 14-1224.18.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-04-19 Cont ID  
Sent By awooten Date 2018-04-19 Time 14:10 Rev Time 0.00
Received By awooten Date 2018-04-19 Time 11:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By AW Date 2018-02-02 Time 13:22 Rev Time  
Received By awooten Date 2018-02-02 Time   Sent To  
Notes
2018-02-02 13:22:46***********************************ZONING REVIEW
 FAILED*****************************************
  
 THE VALUE OF THE WORK TRIGGERS THE LANDSCAPE CODE (MORE
 THAN 50% OF THE VALUE OF THE PROPERTY). THERE ARE
 LANDSCAPE PLANS INCLUDED WITH THIS PERMIT, BUT A
 SEPARATE LANDSCAPE AND IRRIGATION PERMIT ARE REQUIRED.
 THESE ARE THE LANDSCAPE REQUIREMENTS FOR A SINGLE
 FAMILY HOUSE.
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
  
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
  
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]