Plan Review Details - Permit 18010825
Plan Review Stops For Permit 18010825
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 11:22 Rev Time 0.00
Received By dbattles Date 2018-10-30 Time 11:22 Sent To  
Notes
2018-10-30 11:23:17PROVISO:
 PROVIDE PRIVACY AT BATHROOMS.
 **REVISION MAY BE REQUIRED**

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-27 Cont ID  
Sent By dbattles Date 2018-07-27 Time 08:00 Rev Time 0.00
Received By dbattles Date 2018-07-23 Time 09:09 Sent To  
Notes
2018-07-27 08:00:35****CORRECTIONS****
 W.P.B. PERMIT: 18010825
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC EXISTING R504]UPDATE TO A ALTERATION-LEVEL 2.
 IT IS A LEVEL 2 DUE TO THE RE-CONFIGURING OF SPACES. IF
 THIS AFFECTS OVER 50% OF THE SPACE THAN PUT IT AS LEVEL
 3.
  
 2. CHANGE ADDRESS ON TITLE BLOCK TO THE CITY OF WEST
 PALM BEACH AND ADD UNIT #1.
  
 3. [FBC EXISTING 302.4]EXISTING FLOOR PLAN AND DEMO
 PLAN SHOW ARCHWAY OPENINGS. PLEASE SHOW EXISTING FLOOR
 PLAN AS IT WAS PRIOR TO WORK BEING PERFORMED. IF THESE
 ROOMS ARE TO HAVE TOILETS OPEN TO THE ROOM THEN SEE THE
 NEXT COMMENT #4. WHILE THIS ISN'T A NEW HOME, THE NEW
 WORK MUST COMPLY WITH EXISTING CODE.
  
 4.[FBC R320.1] ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES,
 TRIPLEXES, CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT
 LEAST ONE BATHROOM, LOCATED WITH MAXIMUM POSSIBLE
 PRIVACY, WHERE BATHROOMS ARE PROVIDED ON HABITABLE
 GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH (737 MM)
 CLEAR OPENING. HOWEVER, IF ONLY A TOILET ROOM IS
 PROVIDED AT GRADE LEVEL, SUCH TOILET ROOMS SHALL HAVE A
 CLEAR OPENING OF NOT LESS THAN 29 INCHES (737 MM).
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-20 Cont ID  
Sent By cthroop Date 2018-02-20 Time 14:12 Rev Time 0.00
Received By cthroop Date 2018-02-20 Time 11:56 Sent To  
Notes
2018-02-20 14:17:37BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE FLOOR PLAN. SHOW EXISTING CONDITIONS AND
 LOCATION OF PROPOSED WORK.
 2. PLANS SUBMITTED IN ERASABLE MEDIUM ARE NOT
 ACCEPTABLE.
 3. DESIGNER TO PRINT NAME AND SIGN PLAN.
 4. VALUE CANNOT BE DETERMINED AT THIS TIME.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-20 Cont ID  
Sent By jpearson Date 2018-07-20 Time 13:37 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 11:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By jpearson Date 2018-02-08 Time 15:52 Rev Time 0.00
Received By jpearson Date 2018-02-08 Time 15:52 Sent To  
Notes
2018-02-08 15:44:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN (2 COPIES) FOR REVIEW,
 SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 3. PROVIDE FULL FLOOR PLAN SHOWING THE SMOKE/CO ALARMS
 IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 08:56 Rev Time 0.00
Received By tklarge Date 2018-06-28 Time 15:43 Sent To  
Notes
2018-06-28 15:43:47R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-20 Cont ID  
Sent By cthroop Date 2018-02-20 Time 14:17 Rev Time 0.00
Received By cthroop Date 2018-01-23 Time 10:40 Sent To I
Notes
2018-01-24 10:40:47R03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-07-17 Cont ID  
Sent By cmontell Date 2018-07-17 Time 14:49 Rev Time 0.00
Received By cmontell Date 2018-07-17 Time 14:49 Sent To  
Notes
2018-07-17 14:50:39NO MECHANICAL WORK SEE SCOPE OF WORK
  
 CHRIS MONTELLO
 805 6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By cmontell Date 2018-02-15 Time 14:10 Rev Time 0.00
Received By cmontell Date 2018-02-15 Time 14:09 Sent To  
Notes
2018-02-15 14:13:11PROVIDE MECHANICAL DRAWINGS PER FLORIDA BUILDING CODE
 BUILDING SEC.107.1
  
 CHRISTOPHER MONTELLO
 [email protected]
 561-822-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 08:56 Rev Time 0.00
Received By tklarge Date 2018-07-28 Time 08:43 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By thunt Date 2018-02-09 Time 06:16 Rev Time 0.00
Received By thunt Date 2018-02-09 Time 06:16 Sent To  
Notes
2018-02-09 06:17:3302/09/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PLANS ARE NOT CLEAR AS TO WHERE THE EXISTING TUB IS
 AND NEW SHOWER WILL BE. PROVIDE A CLEAR DEMO AND NEW
 WORK FLOOR PLAN THAT IS DRAWN WITH PERMANENT MARKING
 SOURCE. (NO PENCIL) FBC 107.3.5
  
 2) PLUMBING ISOMETRIC IS REQUIRED. SHOW DISTANCE OF
 OFFSET FROM P-TRAP TO NEW SHOWER DRAIN LOCATION. FBC
 107.3.5 PLUMBING # 4 AND 13
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  