Plan Review Details - Permit 18010815
Plan Review Stops For Permit 18010815
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-16 Cont ID  
Sent By jwitmer Date 2018-02-16 Time 06:56 Rev Time 0.00
Received By jwitmer Date 2018-02-16 Time 06:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-29 Cont ID  
Sent By jwitmer Date 2018-01-29 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2018-01-26 Time 17:27 Sent To  
Notes
2018-01-29 06:58:192017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010815
 ADD: 2806 GIN BERRY WAY
 CONT: SOBEL CO.
 TEL: 954-410-9239
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 29/ 2018
 ACTION: DENIED
  
 1) THIS PLAN DOES NOT HAVE A STATE APPROVAL. SHEET C1
 AS BUILT NOTES REFERS TO THESE APPROVED PLANS ARE NO
 LONGER AVAILABLE AND REFERS TO RULE 9B-1 WHICH IS
 TRANSFERRED TO RULE 61G20-5.006. WHEN YOU GO BACK IN
 THE ADMINISTRATIVE CODE TO VIEW THIS RULE IT REFERS YOU
 BACK TO RULE 9B-1. PLEASE PROVIDE THE RULE AND LANGUAGE
 OF THE RULE. OTHERWISE THE SUBMITTED PLANS WILL BE
 VIEWED TO THE REQUIREMENTS OF :
  
 102.2 ( E ) MOBILE OR MODULAR STRUCTURES USED AS
 TEMPORARY OFFICES, EXCEPT THAT THE PROVISIONS OF PART V
 (SECTION 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES,
 AND PERMITS SHALL BE REQUIRED FOR STRUCTURAL SUPPORT
 AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
  
 THIS PERMIT APPLICATION IS FOR A TEMPORARY CONSTRUCTION
 TRAILER, PLANS SUBMITTED AFTER DEC. 31/2017 AND NEEDS
 TO BE DESIGNED TO THE 6TH EDITION OR THE 2017 FLORIDA
 BUILDING CODE. STATEWIDE ADOPTION DATE. PLEASE UPDATE
 THE PLANS TO THE CURRENT CODE EDITION.
  
 2) SHEET A4 NEEDS TO BE UPDATED TO THE CURRENT CODE THE
 2017 FBC-B . THE WIND DESIGN HAS STAYED THE SAME, ASCE
 7-10.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-02-23 Cont ID  
Sent By jpearson Date 2018-02-23 Time 14:30 Rev Time 0.00
Received By jpearson Date 2018-02-22 Time 14:30 Sent To  
Notes
2018-02-23 13:41:55CHANGED STATUS TO NOT REQUIRED ON 2-23-18. CONTRACTOR
 WILL APPLY SEPARATELY FOR ELECTRICAL PERMIT. THEREFORE,
 NO ELECTRICAL IS REVIEWED OR APPROVED ON THIS PERMIT
 NUMBER.
2018-02-22 14:31:30PREVIOUS COMMENTS NOT ADDRESSED, SEE BELOW.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE CORRECT CODE REFERENCES PER CURRENT ADOPTED
 CODES. SEE ABOVE FOR CURRENT CODES. FBC 107.2.1
 3. PROVIDE WEATHER PROOF GFCI RECEPTACLE AT SERVICE.
 NEC 210.64
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 6. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS.
 NEC 110.3, 110.9
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By jpearson Date 2018-02-08 Time 11:00 Rev Time 0.00
Received By jpearson Date 2018-02-08 Time 06:45 Sent To  
Notes
2018-02-08 11:00:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE CORRECT CODE REFERENCES PER CURRENT ADOPTED
 CODES. SEE ABOVE FOR CURRENT CODES. FBC 107.2.1
 3. PROVIDE WEATHER PROOF GFCI RECEPTACLE AT SERVICE.
 NEC 210.64
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 6. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS.
 NEC 110.3, 110.9
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-13 Cont ID  
Sent By pleduc Date 2018-02-13 Time   Rev Time 0.00
Received By pleduc Date 2018-02-13 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By pleduc Date 2018-01-24 Time   Rev Time 0.00
Received By pleduc Date 2018-01-24 Time 11:03 Sent To  
Notes
2018-01-24 15:15:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) A SITE PLAN IS REQUIRED INDICATED WHERE THE PROPOSED
 TRAILER WILL BE LOCATED. INCLUDE ALL DIMENSION TO THE
 NEAREST BUILDINGS, OTHER TRAILERS, PROPERTY LINES AND
 PROPOSED NEW BUILDINGS.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
  
  
 3) WILL THIS TRAILER BE USED BY THE GENERAL PUBLIC?
 WILL IT HAVE BUILT STAIRS/RALINGS, DECKING, RAMPS?
  
 PLEASE PROVIDE DETAILS AND/OR DRAWINGS.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-02 Cont ID  
Sent By cpuell Date 2018-03-02 Time 16:51 Rev Time 0.00
Received By cpuell Date 2018-02-09 Time 15:11 Sent To  
Notes
2018-02-12 15:11:40B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-09 Cont ID  
Sent By jroach Date 2018-02-09 Time 08:59 Rev Time 0.00
Received By jroach Date 2018-01-22 Time 15:59 Sent To  
Notes
2018-01-23 15:59:17B01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-02-20 Cont ID  
Sent By ccole Date 2018-02-20 Time 09:18 Rev Time 0.00
Received By ccole Date 2018-02-20 Time 09:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By ccole Date 2018-02-06 Time 17:38 Rev Time 0.00
Received By ccole Date 2018-02-06 Time 17:38 Sent To  
Notes
2018-02-06 17:44:181ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010815
 2/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C1: PLEASE UPDATE ALL APPLICABLE CODES TO THE
 FBC SIXTH EDITION 2017, AND SUBMIT AN UPDATED ENERGY
 COMPLIANCE FORM IN ACCORDANCE WITH SECTIONS C101.5 AND
 C101.5.1 FBC-17 ENERGY CONSERVATION.
  
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.3.
  
 4) PROVIDE A DUCT LAYOUT DRAWING. CLARIFY HOW SUPPLY
 AIR WILL BE EVENLY DISTRIBUTED THROUGHOUT THE OFFICE
 SPACE AND RETUNED TO THE AIR HANDLER.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE BARD UNITS ON THE EXTERIOR WALL- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-02-27 Cont ID  
Sent By lcrespo Date 2018-02-27 Time 06:57 Rev Time 0.00
Received By lcrespo Date 2018-02-27 Time 06:57 Sent To  
Notes
2018-02-27 06:59:0102/27/18 APPROVED BY PLUMBING AND PUT BACK IN B1, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-07 Cont ID  
Sent By gjohnson Date 2018-02-07 Time 16:05 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 16:05 Sent To  
Notes
2018-02-07 16:10:101ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SITE PLAN SHOWING WATER AND SANITARY. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-02 Cont ID  
Sent By jroach Date 2018-03-02 Time 14:53 Rev Time 0.00
Received By jroach Date 2018-03-02 Time 14:53 Sent To PC
Notes
2018-03-02 14:53:51PROVISO
  
 ALL CONSTRUCTION TRAILERS SHALL BE REMOVED WITHIN SEVEN
 DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE CITY
 AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By JR Date 2018-02-09 Time 08:59 Rev Time 0.00
Received By jroach Date 2018-02-08 Time 16:08 Sent To PC
Notes
***NONE***