| Plan Review Stops For Permit 18010806 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-03-07 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-03-07 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-02-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-02-16 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-02-15 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2018-02-16 07:13:53 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 18010806 | | | ADD: 3068 GIN BERRY WAY | | | CONT: SOBEL CO. | | | TEL: 954-410-9239 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: FRI. FEB. 16/ 2018 | | | ACTION: DENIED | | | | | | 1) MISSING THE FOUNDATION PLAN, NEED 2 SIGNED AND | | | SEALED SHEETS A4. FL ADMIN CODE 61G15-23.002 ENGINEERS. | | | EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS | | | AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY | | | THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | | | | 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-29 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-29 |
Time |
06:59 |
Sent To |
|
|
| Notes |
| 2018-01-29 07:17:28 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 18010806 | | | ADD: 3068 GIN BERRY WAY | | | CONT: SOBEL CO. | | | TEL: 954-410-9239 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. JAN. 29/ 2018 | | | ACTION: DENIED | | | | | | 1) ) THIS PLAN DOES NOT HAVE A STATE APPROVAL. SHEET C1 | | | AS BUILT NOTES REFERS TO THESE APPROVED PLANS ARE NO | | | LONGER AVAILABLE AND REFERS TO RULE 9B-1 WHICH IS | | | TRANSFERRED TO RULE 61G20-5.006. WHEN YOU GO BACK IN | | | THE ADMINISTRATIVE CODE TO VIEW THIS RULE IT REFERS YOU | | | BACK TO RULE 9B-1. PLEASE PROVIDE THE RULE AND LANGUAGE | | | OF THE RULE. OTHERWISE THE SUBMITTED PLANS WILL BE | | | VIEWED TO THE REQUIREMENTS OF : | | | | | | THIS PERMIT APPLICATION IS FOR A TEMPORARY SALES OFFICE | | | PLANS SUBMITTED AFTER DEC. 31/2017 AND NEEDS TO BE | | | DESIGNED TO THE 6TH EDITION OR THE 2017 FLORIDA | | | BUILDING CODE. STATEWIDE ADOPTION DATE. PLEASE UPDATE | | | THE PLANS TO THE CURRENT 2017 FBC EDITION. | | | | | | 2) SHEET A1. PLEASE NOTE THIS UNIT IS TO BE USED AS A | | | SALES UNIT AND IS REQUIRED TO MEET THE REQUIREMENTS OF | | | THE 2017 FLORIDA ACCESSIBILITY CODE ACCESSIBILITY CODE | | | SECTION 604.3 CLEARANCE. CLEARANCES AROUND WATER | | | CLOSETS AND IN TOILET COMPARTMENTS SHALL COMPLY WITH | | | 604.3. | | | | | | 2017 ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A | | | WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM | | | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES | | | (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL. | | | | | | 3) SINCE THIS PLAN IS NOLONGER UNDER A STATE APPROVAL | | | PLEASE PROVIDE COMPLIANCE WITH COMPONENTS AND CLADDING: | | | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS | | | (B) WINDOWS & MULLIONS | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | 4) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2018-03-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-02 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-02 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-02-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-02-13 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-01-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-01-24 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2018-01-25 12:33:54 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) PROVIDE 1 - 2A, 10 B, C FIRE EXTINGUISHER. | | | | | | PER NFPA 101, CHAPTER 28, NEW BUSINESS OCCUPANCY | | | | | | 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE | | | EXTINGUISHERS SHALL BE PROVIDED IN EVERY BUSINESS | | | OCCUPANCY IN ACCORDANCE WITH SECTION 9.9. | | | | | | 9.9* PORTABLE FIRE EXTINGUISHERS. WHERE REQUIRED BY | | | ANOTHER SECTION OF THIS CODE, PORTABLE FIRE | | | EXTINGUISHERS SHALL BE SELECTED, INSTALLED, INSPECTED, | | | AND MAINTAINED IN ACCORDANCE WITH NFPA 10, STANDARD FOR | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-03-08 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-03-01 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-02-20 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-09 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-09 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-01-22 |
Time |
16:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-03-07 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-02-15 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2018-03-07 07:05:40 | SALES TRAILER FOR BANYAN TRAIL @ BANYAN CAY | | | PALM BEACH COUNTY IMPACT FEE OFFICE | | | RECEIPT NUMBER: 2018-0302-90 | | | TRACKING NUMBER: MU-2018-006251-0000 | | | FEES PAID: $1,941.52.CASHIERID: RTORRES |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-01-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-29 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-29 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2018-01-29 07:19:34 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2018-02-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-02-20 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-02-20 |
Time |
07:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-02-06 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-02-06 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2018-02-06 17:31:52 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #18010806 | | | 2/6/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET C1: THE PLANS HAVE BEEN DESIGNED IN ACCORDANCE | | | WITH THE FBC SIXTH EDITION 2017. PLEASE SUBMIT AN | | | UPDATED ENERGY COMPLIANCE FORM- SEE SECTIONS C101.5 AND | | | C101.5.1 FBC-17 ENERGY CONSERVATION. | | | | | | 2) SUBMIT AC COOLING AND HEATING CALCULATIONS IN | | | ACCORDANCE WITH SECTION C403.2.1. | | | | | | 3) PROVIDE MINIMUM VENTILATION CALCULATIONS IN | | | ACCORDANCE WITH TABLE 403.3. | | | | | | 4) PROVIDE A DUCT LAYOUT DRAWING. CLARIFY HOW SUPPLY | | | AIR WILL BE EVENLY DISTRIBUTED THROUGHOUT THE OFFICE | | | SPACE AND RETUNED TO THE AIR HANDLER. | | | | | | 5) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE BARD UNITS ON THE EXTERIOR WALL- SECTION 301.15 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-07 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-07 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2018-03-07 10:48:31 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | SANITARY FACILITY'S WILL BE PROVIDED WITH A SEPARATE | | | BATHROOM TRAILER UNDER SEPARATE PERMIT. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2018-03-07 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-03-07 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2018-03-07 13:39:59 | ZONING PLAN REVIEW | | | DATE OF REVIEW: 03.02.2018 | | | PERMIT NO.: 17120867 | | | | | | PASSED WITH PROVISOS | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. THE SALES OFFICE SHALL BE USED ONLY BY THE FIRMS AND | | | THEIR AGENTS CONSTRUCTING OR MARKETING DWELLING UNITS | | | WITHIN A DEVELOPMENT OR PROJECT. | | | | | | 2. THE SALES OFFICE SHALL NOT BE USED FOR MORE THAN 18 | | | MONTHS FROM THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | FOR SUCH FACILITY AND SHALL BE REMOVED AT THE END OF | | | THAT PERIOD. WITHIN 30 DAYS THE SITE SHALL BE BROUGHT | | | TO GRADE, BE TILLED AND PLANTED WITH GROUND COVER TO | | | INCLUDE SODDING OR SEEDING WHICH SHALL HAVE IRRIGATION. | | | SAID GROUND COVER SHALL BE MAINTAINED IN ACCORDANCE | | | WITH THE CITY?S ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | 3. TEMPORARY SALES OFFICES AND ASSOCIATED SIGNS AND | | | PARKING FACILITIES SHALL NOT BE ILLUMINATED OR USED FOR | | | ANY BUSINESS ACTIVITY LATER THAN 9:00 P.M. | | | | | | 4. EACH SALES OFFICE/MODEL DWELLING SHALL HAVE A SIGN | | | POSTED (MINIMUM OF 11IN X 17IN) THAT STATES THE | | | FOLLOWING... | | | | | | "NOTICE TO PARENTS OF SCHOOL AGE CHILDREN" | | | SCHOOL AGE CHILDREN MAY NOT BE ASSIGNED TO THE PUBLIC | | | SCHOOL CLOSEST TO THEIR RESIDENCES. SCHOOL BOARD | | | POLICIES REGARDING LEVELS OF SERVICE OR OTHER BOUNDARY | | | POLICY DECISIONS AFFECT SCHOOL BOUNDARIES. PLEASE | | | CONTACT THE PALM BEACH COUNTY SCHOOL DISTRICT BOUNDARY | | | OFFICE AT (561) 434-8100 FOR THE MOST CURRENT SCHOOL | | | ASSIGNMENT(S). | | | | | | 5. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY/COMPLETION, AT LEAST FIVE (5) OFF-STREET | | | PARKING SPACES SHALL BE PROVIDED FOR EACH TEMPORARY | | | SALES OFFICE AND FOR EACH THREE (3) MODEL DWELLING | | | UNITS. PARKING SPACES SHALL BE LOCATED ON THE SAME LOT, | | | OR ON A CONTIGUOUS LOT. SEPARATE PERMITS SHALL BE | | | OBTAINED FOR ALL PARKING LOT IMPROVEMENTS. | | | | | | 6. SEPARATE LANDSCAPE AND IRRIGATION PERMITS SHALL BE | | | ISSUED. ALL LANDSCAPING SHALL BE INSTALLED AND PASS | | | INSPECTION PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY/COMPLETION. | | | | | | 7. SEPARATE PERMITS SHALL BE REQUIRED FOR ANY SITE | | | LIGHTING. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-02-08 |
|
|
Cont ID |
|
| Sent By |
JR |
Date |
2018-02-08 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-02-08 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2018-02-08 15:03:11 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 02.08.2018 | | | PERMIT NO.: 18010806 | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. SALES OFFICES NOT LOCATED IN MODEL HOMES ARE | | | PERMITTED BUT SHALL BE USED ONLY BY THE FIRMS AND THEIR | | | AGENTS CONSTRUCTING OR MARKETING DWELLING UNITS WITHIN | | | A DEVELOPMENT OR PROJECT. | | | | | | 2. TEMPORARY SALES OFFICES NOT IN MODEL DWELLING UNITS | | | SHALL NOT BE USED FOR MORE THAN 18 MONTHS AND SHALL BE | | | REMOVED AT THE END OF THAT PERIOD. | | | | | | 3. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | | AT LEAST FIVE OFF-STREET PARKING SPACES SHALL BE | | | PROVIDED FOR EACH TEMPORARY SALES OFFICE AND FOR EACH | | | THREE MODEL DWELLING UNITS. PARKING SPACES SHALL BE | | | LOCATED ON THE SAME OR ON A CONTIGUOUS LOT. SEPARATE | | | PERMITS SHALL BE OBTAINED FOR ALL PARKING LOT | | | IMPROVEMENTS. | | | | | | 4. TEMPORARY MODEL DWELLING UNITS, SALES OFFICES AND | | | SIGNS SHALL NOT BE ILLUMINATED OR USED FOR ANY BUSINESS | | | ACTIVITY LATER THAN 9:00 P.M. | | | | | | 5. SEPARATE LANDSCAPE AND IRRIGATION PERMITS SHALL BE | | | ISSUED. ALL LANDSCAPING SHALL BE INSTALLED AND PASS | | | INSPECTION PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY / COMPLETION. | | | | | | 6. SEPARATE PERMITS SHALL BE REQUIRED FOR ANY SITE | | | LIGHTING. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|