Plan Review Details - Permit 18010802
Plan Review Stops For Permit 18010802
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 16:56 Rev Time 0.00
Received By shill Date 2018-06-16 Time 16:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By jwitmer Date 2018-03-08 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2018-03-06 Time 16:20 Sent To  
Notes
2018-03-06 16:25:562017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010802
 ADD: 2218 S. DIXIE HWY.
 CONT: PCN DEVELOPMENT INC.
 TEL: 561-302-4009
 E-MAIL: PATRICK@PCNDEVLOPMENT
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:TUES. MARCH 06/ 2018
 ACTION: DENIED
  
 1) IN BOTH SETS OF ARCHITECTURAL PLANS THE SHEET A2.01
 WERE SIGNED & DATED BUT NEVER STAMPED WITH THE
 ARCHITECTS SEAL. 61 G 1-16.003 USES OF SEAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By jwitmer Date 2018-01-26 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2018-01-26 Time 08:44 Sent To  
Notes
2018-01-26 13:12:222014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010802
 ADD: 2218 S. DIXIE HWY.
 CONT: PCN DEVELOPMENT INC.
 TEL: 561-302-4009
 E-MAIL: PATRICK@PCNDEVLOPMENT
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 26/ 2018
 ACTION: DENIED
  
 1) IN BOTH SETS OF ARCHITECTURAL PLANS THE SHEETS WERE
 SIGNED & DATED BUT NEVER STAMPED WITH THE ARCHITECTS
 SEAL. 61 G 1-16.003 USES OF SEAL.
  
 2) SHEET A1.01 THE COVERSHEET UNDER THE HEADING CODE
 INFORMATION LIST THE 2014 FBC AND FAMILY OF CODES. THE
 2017 FBC FAMILY OF CODES WAS ADOPTED DEC. 31/ 2017
 STATEWIDE. THE PLANS WERE SUBMITTED ON 1/22/2018
 REQUIRING THE PLANS TO BE CREATED UNDER THE 2017 FBC-B.
  
 3) SHEET A3.01 INDICATES A NEW STOREFRONT DOOR AND
 TRANSOM. SHEET A5.01 PROVIDES THE WIND DESIGN UNDER THE
 2014 FBC-B. PLEASE UPDATE THE PLANS TO THE 2017 FBC.
  
 4) SHEET A5.01 ALSO HAS THE POSITIVE AND NEGATIVE
 PRESSURES. UNDER THE WIND DESIGN CRITERIA IT HAS BOTH:
 VULT 170 MPH & VASD 132 MPH. THE PRESSURE THEMSELVES
 DOESN?T INDICATE IF THEY ARE IN VULT OR VASD.
 DEPENDING ON THE PRESSURES GIVEN SOME ARE LOW FOR VULT
 BUT HIGH FOR VASD. EXAMPLE;
 VASD/ 132 MPH. EXP. C MEAN ROOF 15 FT.
 WALL ZONE 4 @ 10 SQ. FT. -48.55. SHOULD BE -41.9 VASD.
 SHOULD BE -68.48 VULT.
 WALL ZONE 5 @ 10 SQ. FT. -67.58. SHOULD BE ?50.7 VASD.
 SHOULD BE -84.51 VULT.
 THIS IS TRUE FOR BOTH ROWS OF FIGURES.
  
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS & TRANSOM.
  
 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET A3.01 IN BOTH ROOMS THE BATHROOM 114 AND THE
 LAUNDRY ROOM 117BOTH OF THE DOORS SWING OUT OVER ? OF
 THE REQUIRED EXIT SEE SECTION 2017 FBC-B 1005.7.1
 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN
 ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY
 MORE THAN ONE-HALF.
  
 8) SHEET A3.01 DOES NOT SHOW THE LANDING ON THE
 EXTERIOR SIDE OF THE NEW DOOR AND COMPLIANCE WITH
 SECTION 404.2.4 MANEUVERING CLEARANCES OF THE 2017
 ACCESSIBILITY CODE.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 9) SHEET A3.01 HAS NOTES FOR THE ACCESSIBLE BREAK ROOM
 SINK AND MICROWAVE BUT THERE ARE NO DETAILS SHOWING
 CODE COMPLIANCE WITH: 2017 FBC-ACCESSIBILITY CODE 606.3
 HEIGHT.
  
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 THE MICROWAVE MUST COMPLY WITH THE 2017 ACCESSIBILITY
 CODE;
  
 REACH RANGES 308.2 FORWARD REACH AND OR 308.3 SIDE
 REACH AND
  
 309. OPERABLE PARTS.
 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED.
  
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-14 Cont ID  
Sent By ppetty Date 2018-06-14 Time 09:16 Rev Time 0.00
Received By ppetty Date 2018-06-14 Time 09:16 Sent To  
Notes
2018-06-14 14:54:10PROVISO
 SEE HI-LEG IN PANEL A
 FPL SERVICE STANDARDS 2 METERS IN ONE UNIT
 PP
 561-644-7305

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-09 Cont ID  
Sent By jpearson Date 2018-03-09 Time 13:41 Rev Time 0.00
Received By jpearson Date 2018-03-09 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By jpearson Date 2018-01-24 Time 08:10 Rev Time 0.00
Received By jpearson Date 2018-01-24 Time 08:10 Sent To  
Notes
2018-01-24 08:10:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE ABOVE)
 2. PROVIDE SIZE OF EXISTING MAIN 1 OF 2 AND FEEDERS
 SIZES TO VERIFY SIZE IS ADEQUATE. NEC 408.30, 230.79;
 FBC 107.2.1
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 4. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 7. THERE IS A NOTE THAT INDICATES SOME OF THE LIGHTING
 CIRCUITS WILL BE CONTROLLED THROUGH A TIME CLOCK, BUT
 THE CIRCUITS CONTROLLED ARE NOT IDENTIFIED. PROVIDE
 CORRECTION. FBC 107.2.1; FBC EC C405.2
 8. PROVIDE WEATHER PROOF GFCI RECEPTACLE AT SERVICE.
 NEC 210.64
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-08 Cont ID  
Sent By pleduc Date 2018-06-08 Time   Rev Time 0.00
Received By pleduc Date 2018-06-07 Time 12:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By pleduc Date 2018-03-06 Time   Rev Time 0.00
Received By pleduc Date 2018-03-05 Time 12:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-01-24 Cont ID  
Sent By pleduc Date 2018-01-24 Time   Rev Time 0.00
Received By pleduc Date 2018-01-24 Time 11:03 Sent To  
Notes
2018-01-24 14:40:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE LAUNDRY/CLSET ROOM DORR, # 16, SWING OUT INTO
 THE EXIT TRAVEL PATH. CHANGE TO IN-SWING OR ADD A DOOR
 CLOSER.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS :
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL NOT PROJECT MORE THAN 7 IN. (180 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OR A LANDING, UNLESS THE DOOR LEAF IS
 EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE AND IS
 NOT REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN
 THE DIRECTION OF EGRESS TRAVEL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-21 Cont ID  
Sent By gjohnson Date 2018-06-21 Time 11:26 Rev Time 0.00
Received By gjohnson Date 2018-06-05 Time 10:08 Sent To  
Notes
2018-06-06 09:40:25B12
2018-06-05 10:08:25LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-14 Cont ID  
Sent By gjohnson Date 2018-03-14 Time 12:22 Rev Time 0.00
Received By gjohnson Date 2018-03-01 Time 13:26 Sent To  
Notes
2018-03-02 13:26:14B33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-06 Cont ID  
Sent By gjohnson Date 2018-02-06 Time 10:19 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 15:50 Sent To  
Notes
2018-01-23 15:50:32B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-01-26 Cont ID  
Sent By jwitmer Date 2018-01-26 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2018-01-26 Time 13:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-06-12 Cont ID  
Sent By ccole Date 2018-06-12 Time 07:29 Rev Time 0.00
Received By ccole Date 2018-06-11 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By ccole Date 2018-03-08 Time 08:37 Rev Time 0.00
Received By ccole Date 2018-03-08 Time 08:27 Sent To  
Notes
2018-03-08 08:42:422ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010802
 3/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) THE 2014 ENERGYGAUGE COMPLIANCE SUBMITTAL IS
 OUTDATED. THE PLANS WERE SUBMITTED UNDER THE 2017
 FLORIDA BUILDING CODES. PLEASE PROVIDE AN UP-TO-DATE
 ENERGY REPORT- SECTION C101.5.1 FBC-17 ENERGY.
  
 2) AS PREVIOUSLY NOTED DUCT SMOKE DETECTORS ARE
 REQUIRED IN THE SUPPLY DUCTS OF THE 5-TON AIR HANDLERS.
 AN EXEMPTIOPN CAN BE APPLIED IF AIR HANDLER DATA SHEETS
 PROVIDED BY THE MANUFACTURER INDICATE THAT THE UNITS DO
 NOT HAVE THE CAPACITY TO PROVIDE OVER 2000 CFMS OF
 SUPPLY AIR AT ALL STATIC PRESSURES. PLEASE SUBMIT THE
 DATA SHEETS FROM THE MANUFACTURER OR PROVIDE THE DUCT
  
 SMOKE DETECTORS.
  
 3) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN
 ACCORDANCE WITH SECTION 602.2.1 FBC-17 MECHANICAL, AND
 SECTION C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-29 Cont ID  
Sent By ccole Date 2018-01-29 Time 16:26 Rev Time 0.00
Received By ccole Date 2018-01-29 Time 16:25 Sent To  
Notes
2018-01-29 17:02:531ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010802
 1/29/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY SIDE
 OF THE 5-TON AIR HANDLER PER SECTION 606.2.1. PLEASE
 NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATES THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 3) THE CORRIDOR SHALL NOT BE USED AS A RETURN AIR DUCT-
 SECTION 601.2. RELOCATE THE RETURN GRILL AND DUCT IN
 THE CORRIDOR BY BATH 116, OR EXTEND THE DUCT TO THE
 AHU-1 CLOSET.
  
 4) THE OUTDOOR AIR INTAKE DUCTS SHALL BE PROVIDED WITH
 EITHER MOTORIZED OR GRAVITY SHUTOFF DAMPERS- SECTION
 C404.2.4.3 FBC-17 ENERGY CONSERVATION
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-21 Cont ID  
Sent By gjohnson Date 2018-06-21 Time 11:26 Rev Time 0.00
Received By gjohnson Date 2018-06-21 Time 08:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-03-14 Cont ID  
Sent By gjohnson Date 2018-03-14 Time 12:10 Rev Time 0.00
Received By gjohnson Date 2018-03-14 Time 07:22 Sent To  
Notes
2018-03-14 12:20:422ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 1. SHT. A3.01 THE ACCESSIBLE SHOWER-APPEARS TO BE AN
 TRANSFER TYPE , IT SHALL HAVE A INSIDE CLEAR DIMENSIONS
 OF 36" X 36" THE DIMENSION ACROSS THE BACK WALL IS
 SHOWN AT 38 1/4" IT SHALL BE 36". PER FBC ACC 608.2.1
 608.2.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS
 SHALL BE 30 INCHES (760 MM) WIDE MINIMUM BY 60 INCHES
 (1525 MM) DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED
 AT CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 60
 INCHES (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE
 SHOWER COMPARTMENT.
  
  
 2. THE FBC PL 403.3 REQUIRES THAT SEPARATE FACILITIES
 BE PROVIDED FOR EACH SEX THAT MAKE BOTH BATHROOMS
 REQUIRED AND EACH SHALL COMPLY TO THE FBC ACC 213.2,
 603, 604, 606
  
 3. SHT. A5.01 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 REQUIREMENTS: FBC ACC
  
 A) WATER FOUNTAINS 602.2 CLEAR FLOOR SPACE.UNITS SHALL
 HAVE A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH AND CENTERED ON THE
 UNIT. KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED.
 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 INCHES (1090
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 B) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 C) 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305
 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL.
  
 E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
  
 F) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF
 THE SEAT.
  
 G) 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 H) BREAK ROOM SINK. 606.2 CLEAR FLOOR SPACE.A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 I) SHOW DIMENSIONS ON CLEAR FLOOR SPACE. 604.3.1
 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 J) 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.IN
 TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 K) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.IN
 TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE PROVIDED
 ACROSS THE CONTROL WALL AND BACK WALL TO A POINT 18
 INCHES (455 MM) FROM THE CONTROL WALL.
  
 L) 610.3 SHOWER COMPARTMENT SEATS. IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY.
 THE TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM
 FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR
 610.3.2.
  
  
 5. A WATER FOUNTAIN COMPILING WITH FBC PL [BE] 410.3 IS
 REQUIRED IN THIS OCCUPANCY PER FBC PL TABLE 403.1,
 SECTION 410.3 SHALL NOT APPLY TO THIS OCCUPANCY.
  
 6. SHT. P1.1 THE FIXTURE SCHEDULE IS CALLING OUT A SIDE
 CONNECT WATER HEATER-DETAIL #4 SHOWS A TOP FEED PLEASE
 PROVIDE A DETAIL THAT SHOWS A SIDE CONNECT WATER HEATER
 WITH THE REQUIRED VACUUM BREAKER ON THE SUPPLY SIDE.
 PER FBC PL 504.2
  
 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 10. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By gjohnson Date 2018-02-06 Time 09:09 Rev Time 0.00
Received By gjohnson Date 2018-02-02 Time 18:16 Sent To  
Notes
2018-02-06 10:19:411ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A3.01 THE ACCESSIBLE SHOWER-APPEARS TO BE AN
 TRANSFER TYPE , IT SHALL HAVE A INSIDE CLEAR DIMENSIONS
 OF 36" X 36" THE DIMENSION ACROSS THE BACK WALL IS
 SHOWN AT 38 1/4" IT SHALL BE 36". PER FBC ACC 608.2.1
  
 2. THE FBC PL 403.3 REQUIRES THAT SEPARATE FACILITIES
 BE PROVIDED FOR EACH SEX THAT MAKE BOTH BATHROOMS
 REQUIRED AND EACH SHALL COMPLY TO THE FBC ACC 213.2,
 603, 604, 606
  
 3. SHT. A5.01 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 REQUIREMENTS: FBC ACC
  
 A) WATER FOUNTAINS 602.2 CLEAR FLOOR SPACE.UNITS SHALL
 HAVE A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH AND CENTERED ON THE
 UNIT. KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED.
 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 INCHES (1090
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 B) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 C) 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305
 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL.
  
 E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
  
 F) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF
 THE SEAT.
  
 G) 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 H) BREAK ROOM SINK. 606.2 CLEAR FLOOR SPACE.A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 I) SHOW DIMENSIONS ON CLEAR FLOOR SPACE. 604.3.1
 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 J) 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.IN
 TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 K) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.IN
 TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE PROVIDED
 ACROSS THE CONTROL WALL AND BACK WALL TO A POINT 18
 INCHES (455 MM) FROM THE CONTROL WALL.
  
 L) 610.3 SHOWER COMPARTMENT SEATS. IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY.
 THE TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM
 FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR
 610.3.2.
  
 4. SHT.P1.1 UNDER PLUMBING NOTE THE CURRENT CODE THAT
 APPLIES TO THIS JOB SHALL BE THE FLORIDA BUILDING CODES
 2017 6TH EDITION WHICH WENT INTO EFFECT DEC. 31 2017.
 PLEASE CORRECT ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 5. A WATER FOUNTAIN COMPILING WITH FBC PL [BE] 410.3 IS
 REQUIRED IN THIS OCCUPANCY PER FBC PL TABLE 403.1,
 SECTION 410.3 SHALL NOT APPLY TO THIS OCCUPANCY.
  
 6. SHT. P1.1 THE FIXTURE SCHEDULE IS CALLING OUT A SIDE
 CONNECT WATER HEATER-DETAIL #4 SHOWS A TOP FEED PLEASE
 PROVIDE A DETAIL THAT SHOWS A SIDE CONNECT WATER HEATER
 WITH THE REQUIRED VACUUM BREAKER ON THE SUPPLY SIDE.
 PER FBC PL 504.2
  
 7. SHT. P1.2 THE SHOWER IS MISSING FROM THE SANITARY
 ISOMETRIC DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 8. A LINT TRAP OR SOLIDS INTERCEPTOR IS REQUIRED ON
 DISCHARGE OF THE WASHING MACHINE. PER FBC PL 1003.6
  
 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  