| 2018-02-02 10:00:56 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- EXTERIOR DOORS DRAWING NO JW142012FL SUBMITTED: |
| | A) THESE DOORS DON'T MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD. NEED TO PROVIDE |
| | PRODUCT APPROVAL (2 COPIES) OF DOORS THAT MEETS THE |
| | DESIGN PRESSURES CALCULATED BY THE ENGINEER ON SHEET |
| | A-1/3. |
| | SEC. R301.1 FB-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT |
| | CORRESPONDS TO DRAWING JW142012FL SUBMITTED. |
| | FAC 61G20-3.001 |
| | |
| | 2- CASEMENT WINDOWS NOA 14-0908.20 SUBMITTED: CLEARLY |
| | MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET |
| | A-1/3. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 3- SINGLE HUNG WINDOWS NOA 16-1003.01 SUBMITTED: |
| | CLEARLY MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING |
| | TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET |
| | A-1/3. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 4- FIXED WINDOWS NOA 17-0531.05 SUBMITTED: |
| | A) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR FIXED |
| | WINDOWS IF PLANS DON'T SPECIFY ANY FIXED WINDOWS. IF |
| | FIXED WINDOWS ARE GOING TO BE INSTALLED, THEN ENGINEER |
| | OF RECORD NEEDS TO REVISE PLANS ACCORDINGLY. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | B) IF INSTALLING FIXED WINDOWS, THEN CLEARLY MARK WHICH |
| | WINDOW SIZE AND GLASS TYPE IS GOING TO BE INSTALLED TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED |
| | BY THE ENGINEER OF RECORD ON SHEET A-1/3. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 6- NEED TO PROVIDE WINDOW MULLIONS PRODUCT APPROVALS (2 |
| | COPIES) AS REQUESTED ON PROVISO. NOTE: CLEARLY SPECIFY |
| | WINDOW SIZE TO BE INSTALLED TO VERIFY COMPLIANCE WITH |
| | THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF |
| | RECORD ON SHEET A-1/3. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |