Plan Review Details - Permit 18010787
Plan Review Stops For Permit 18010787
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 16:53 Rev Time 0.00
Received By shill Date 2018-06-30 Time 16:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-25 Cont ID  
Sent By cthroop Date 2018-05-25 Time 15:51 Rev Time 0.00
Received By cthroop Date 2018-05-25 Time 13:38 Sent To P
Notes
2018-05-25 15:55:40BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN WITH ORIGINAL SIGNATURE AND SEAL
 OF DESIGN PROFESSIONAL. DIGITAL SIGNATURES ARE NOT
 ACCEPTABLE ON PAPER PLANS.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF FLORIDA STATUTES ?
 471.025, AND RULE 61G15-23.001, F.A.C. MAY BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By cthroop Date 2018-02-08 Time 08:03 Rev Time 0.00
Received By cthroop Date 2018-02-01 Time 10:41 Sent To  
Notes
2018-02-08 08:23:57BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN. SHOW LOCATION OF PROPOSED
 STRUCTURE AND OTHER STRUCTURES IN NEAR PROXIMITY. STATE
 FINISHED FLOOR ELEVATION.
 2. PROVIDE FOUNDATION PLANS WITH DEMENSIONS.
 3. PROVIDE DESIGN WIND LOADS FOR CRYPT OPENINGS.
 4. PROVIDE DETAIL OF CRYPT OPENING PANEL ATTACHMENT.
 5. PROVIDE FASTENER SCHEDULE FOR MARBLE PANELS TO
 CONCRETE STRUCTURE.
 6. ROOFING PERMIT REQUIRED.
 7. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 8. DESIGN PROFESSIONAL TO SIGN AND SEAL ALL PLAN PAGES.
 9. DESIGN PROFESSIONALS SIGNATURE AND SEAL SHALL BE
 ORIGINAL.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 16:54 Rev Time 0.00
Received By shill Date 2018-06-12 Time 14:05 Sent To  
Notes
2018-06-13 14:05:47B18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-06-04 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-18 Time 13:24 Sent To  
Notes
2018-05-21 13:25:09RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-08 Cont ID  
Sent By cthroop Date 2018-02-08 Time 08:25 Rev Time 0.00
Received By cthroop Date 2018-01-22 Time 15:38 Sent To I
Notes
2018-01-23 15:39:03ROUTED TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-06-22 Cont ID  
Sent By ccole Date 2018-06-22 Time 08:15 Rev Time 0.00
Received By ccole Date 2018-06-21 Time 17:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-04 Cont ID  
Sent By ccole Date 2018-06-04 Time 10:41 Rev Time 0.00
Received By ccole Date 2018-06-04 Time 10:41 Sent To I
Notes
2018-06-04 10:46:401ST REVIEW FBC-2017 MECHANICAL
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 515 FBC M AND REVCISE THE PLANS AND
 DETAILS TO SHOW THE REQUIRED RELIEF VENTING FOR THE
 MAUSOLEUM.
  
 MAUSOLEUM RELIEF VENT
  
 515.1 GENERAL.
 A PRESSURE RELIEF VENT SHALL BE PROVIDED FOR EACH
 CRYPT. NICHES SHALL NOT REQUIRE PRESSURE RELIEF
 SYSTEMS.
  
 515.2 MATERIALS.
 THE PRESSURE RELIEF VENT PIPE AND FITTINGS SHALL
 CONFORM TO ONE OF THE STANDARDS LISTED IN TABLES 515.2A
 AND 515.2B.
  
 TABLE 515.2A
 CRYPT PRESSURE RELIEF PIPE
 MATERIAL STANDARD
 ACRYLONITRILE BUTADIENE STYRENE (ABS) PLASTIC PIPE ASTM
 D2661, ASTM F628CSA B181.1,
 POLYLEFIN PIPE CSA CAN/CSA B181.3
 POLYVINYL CHLORIDE (PVC) PLASTIC PIPE (TYPE DWV) ASTM
 D2665, ASTM D2949, ASTM F891
  
 TABLE 515.2B
 CRYPT PRESSURE RELIEF FITTINGS
 MATERIAL STANDARD
 ACRYLONITRILE BUTADIENE STYRENE (ABS) PLASTIC PIPE ASTM
 D3311, CSA B181.1
 POLYVINYL CHLORIDE (PVC) PLASTIC PIPE (TYPE DWV) ASTM
 D3311, ASTM D2949, ASTM F891
 PLASTIC, GENERAL ASTM F409
  
 515.3 PRESSURE RELIEF VENT.
  
 FOR FAMILY MAUSOLEUM UNITS WHERE ALL CRYPTS ARE
 BORDERING AN EXTERIOR WALL, PRESSURE RELIEF VENTILATION
 SHALL BE PROVIDED FROM THE CRYPT TO THE OUTSIDE OF THE
 MAUSOLEUM THROUGH THE EXTERIOR WALL OR ROOF. FOR ALL
 OTHER MAUSOLEUM UNITS, EACH CRYPT SHALL HAVE A PRESSURE
 RELIEF VENT FROM THE CRYPT TO THE ROOF OF THE
 MAUSOLEUM. THE MINIMUM NOMINAL PIPE SIZE SHALL BE 1
 INCH (25 MM). THE SYSTEM SHALL HAVE A MINIMUM OF
 ONE-EIGHTH UNIT VERTICAL TO 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). THE PIPING SHALL NOT BE TRAPPED OR
 INSTALLED TO TRAP WATER OR CONDENSATE.
  
 515.4 TERMINATION.
  
 EXCEPT FOR FAMILY MAUSOLEUM UNITS WHERE ALL CRYPTS ARE
 BORDERING AN EXTERIOR WALL, CRYPT PRESSURE RELIEF
 SYSTEM SHALL EXTEND THROUGH THE ROOF AND TERMINATE AT
 LEAST 6 INCHES (152 MM) ABOVE THE ROOF AND AT LEAST 10
 FEET (3048 MM) FROM ANY OPENABLE OPENING, AIR INTAKE OR
 PROPERTY LINE. THE TERMINATION OF THE RELIEF SYSTEM
 PIPE SHALL BE DONE BY A ROOF AND VENT CAP COMPATIBLE
 WITH THE RELIEF PRESSURE PIPE. THE ROOF AND VENT CAP
 SHALL BE WATERPROOF. FOR FAMILY MAUSOLEUM UNITS WHERE
 ALL CRYPTS ARE BORDERING AN EXTERIOR WALL, PRESSURE
 RELIEF VENTILATION SHALL BE PROVIDED FROM THE CRYPT TO
 THE OUTSIDE OF THE MAUSOLEUM THROUGH THE EXTERIOR WALL
 OR ROOF.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 14:58 Rev Time 0.00
Received By gjohnson Date 2018-06-29 Time 14:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 03:53 Rev Time 0.00
Received By tklarge Date 2018-06-02 Time 03:15 Sent To M
Notes
2018-06-02 03:53:421) SUBMIT ROOF DRAIN CALCULATIONS PER THE 2017
 FBC-PLUMBING SECS.1106.2, 1106.3. THE SIZING SHALL BE
 BASED ON 5 INCHES OF RAIN PER HOUR.
 2) SHOW PROVISIONS FOR SECONDARY (EMERGENCY) ROOF
 DRAINAGE PER 2017 FBC - -PLUMBING SEC.1108. SHT. A-5
 SHOWS WHAT APPEARS TO BE A RAISED ROOF CURB/EDGE AT THE
 PERIMETER OF THE ROOF. CLARIFY.
 3) PAPER PLANS CANNOT BE DIGITALLY SIGNED AND SEALED
 PER F.A.C. RULE 61G15-23.004, FL. STATUTE 471.025.
 4) SHT. 1 IS MISSING FROM ONE OF THE SET OF PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 16:57 Rev Time 0.00
Received By shill Date 2018-06-30 Time 16:57 Sent To  
Notes
2018-06-30 16:58:18SUBMIT PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 WITH ROOF PERMIT APPLICATION
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-06-18 Time   Rev Time 0.00
Received By pgreilic Date 2018-06-15 Time 11:48 Sent To  
Notes
2018-06-18 15:10:16PAUL GREILICH,SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By mc to pc Date 2018-05-22 Time   Rev Time 0.00
Received By   Date 2018-05-22 Time   Sent To  
Notes
2018-05-22 15:20:211.) INCLUDE APPROVED SITE PLAN IN PERMIT SET
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By PG Date 2018-01-30 Time 15:36 Rev Time 0.00
Received By pgreilic Date 2018-01-25 Time 11:26 Sent To B
Notes
2018-01-30 15:38:461.) INCLUDE APPROVED SITE PLAN IN PERMIT SET
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy