| 2018-06-04 10:46:40 | 1ST REVIEW FBC-2017 MECHANICAL |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 515 FBC M AND REVCISE THE PLANS AND |
| | DETAILS TO SHOW THE REQUIRED RELIEF VENTING FOR THE |
| | MAUSOLEUM. |
| | |
| | MAUSOLEUM RELIEF VENT |
| | |
| | 515.1 GENERAL. |
| | A PRESSURE RELIEF VENT SHALL BE PROVIDED FOR EACH |
| | CRYPT. NICHES SHALL NOT REQUIRE PRESSURE RELIEF |
| | SYSTEMS. |
| | |
| | 515.2 MATERIALS. |
| | THE PRESSURE RELIEF VENT PIPE AND FITTINGS SHALL |
| | CONFORM TO ONE OF THE STANDARDS LISTED IN TABLES 515.2A |
| | AND 515.2B. |
| | |
| | TABLE 515.2A |
| | CRYPT PRESSURE RELIEF PIPE |
| | MATERIAL STANDARD |
| | ACRYLONITRILE BUTADIENE STYRENE (ABS) PLASTIC PIPE ASTM |
| | D2661, ASTM F628CSA B181.1, |
| | POLYLEFIN PIPE CSA CAN/CSA B181.3 |
| | POLYVINYL CHLORIDE (PVC) PLASTIC PIPE (TYPE DWV) ASTM |
| | D2665, ASTM D2949, ASTM F891 |
| | |
| | TABLE 515.2B |
| | CRYPT PRESSURE RELIEF FITTINGS |
| | MATERIAL STANDARD |
| | ACRYLONITRILE BUTADIENE STYRENE (ABS) PLASTIC PIPE ASTM |
| | D3311, CSA B181.1 |
| | POLYVINYL CHLORIDE (PVC) PLASTIC PIPE (TYPE DWV) ASTM |
| | D3311, ASTM D2949, ASTM F891 |
| | PLASTIC, GENERAL ASTM F409 |
| | |
| | 515.3 PRESSURE RELIEF VENT. |
| | |
| | FOR FAMILY MAUSOLEUM UNITS WHERE ALL CRYPTS ARE |
| | BORDERING AN EXTERIOR WALL, PRESSURE RELIEF VENTILATION |
| | SHALL BE PROVIDED FROM THE CRYPT TO THE OUTSIDE OF THE |
| | MAUSOLEUM THROUGH THE EXTERIOR WALL OR ROOF. FOR ALL |
| | OTHER MAUSOLEUM UNITS, EACH CRYPT SHALL HAVE A PRESSURE |
| | RELIEF VENT FROM THE CRYPT TO THE ROOF OF THE |
| | MAUSOLEUM. THE MINIMUM NOMINAL PIPE SIZE SHALL BE 1 |
| | INCH (25 MM). THE SYSTEM SHALL HAVE A MINIMUM OF |
| | ONE-EIGHTH UNIT VERTICAL TO 12 UNITS HORIZONTAL |
| | (1-PERCENT SLOPE). THE PIPING SHALL NOT BE TRAPPED OR |
| | INSTALLED TO TRAP WATER OR CONDENSATE. |
| | |
| | 515.4 TERMINATION. |
| | |
| | EXCEPT FOR FAMILY MAUSOLEUM UNITS WHERE ALL CRYPTS ARE |
| | BORDERING AN EXTERIOR WALL, CRYPT PRESSURE RELIEF |
| | SYSTEM SHALL EXTEND THROUGH THE ROOF AND TERMINATE AT |
| | LEAST 6 INCHES (152 MM) ABOVE THE ROOF AND AT LEAST 10 |
| | FEET (3048 MM) FROM ANY OPENABLE OPENING, AIR INTAKE OR |
| | PROPERTY LINE. THE TERMINATION OF THE RELIEF SYSTEM |
| | PIPE SHALL BE DONE BY A ROOF AND VENT CAP COMPATIBLE |
| | WITH THE RELIEF PRESSURE PIPE. THE ROOF AND VENT CAP |
| | SHALL BE WATERPROOF. FOR FAMILY MAUSOLEUM UNITS WHERE |
| | ALL CRYPTS ARE BORDERING AN EXTERIOR WALL, PRESSURE |
| | RELIEF VENTILATION SHALL BE PROVIDED FROM THE CRYPT TO |
| | THE OUTSIDE OF THE MAUSOLEUM THROUGH THE EXTERIOR WALL |
| | OR ROOF. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |