Plan Review Details - Permit 18010663
Plan Review Stops For Permit 18010663
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By rmcdouga Date 2018-03-06 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2018-03-06 Time 08:09 Sent To G
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By rmcdouga Date 2018-01-24 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2018-01-24 Time 11:35 Sent To  
Notes
2018-01-24 11:42:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED GENERATOR PAD
 AND ANCHORING DETAILS FOR 170 MPH VULT WIND SPEED IN
 EXPOSURE C. FBC-R301.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-01 Cont ID  
Sent By jleahy Date 2018-03-01 Time 15:34 Rev Time 0.00
Received By jleahy Date 2018-03-01 Time 15:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-01-31 Cont ID  
Sent By jleahy Date 2018-01-31 Time 11:56 Rev Time 0.00
Received By jleahy Date 2018-01-31 Time 11:56 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-03-07 Cont ID  
Sent By thunt Date 2018-03-07 Time 07:26 Rev Time 0.00
Received By thunt Date 2018-03-07 Time 07:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By thunt Date 2018-01-26 Time 06:53 Rev Time 0.00
Received By thunt Date 2018-01-26 Time 06:53 Sent To  
Notes
2018-01-26 07:10:4901/26/2018 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) CITY RECORDS DO NOT SHOW A POOL HEATER AS EVER BEING
 INSTALLED AND NOT ON ANY PREVIOUS ISOMETRIC PLANS. THE
 SYSTEM IS UNDERSIZED FOR THE EXISTING GAS METER MODEL
 AL-425 MAX BTU IS 865,000. .. NOTE: IF THE EXISTING
 SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE SYSTEM
 PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3
  
 2) YOU SHOW THE EXISTING GAS METER AT 7" WC FLOWING
 425,000. PLEASE EXPLAIN FBC107.2.1.
  
 3) YOU INCLUDED SPEC MANUAL FOR A PRESSURE REGULATOR
 BUT YOUR DESIGN PRESSURE IS .5 LB PLEASE EXPLAIN. FBC
 107.2.1
  
 4) PLEASE LIST CURRENT CODE AS FBC FUEL AND GAS 2017
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-07 Cont ID  
Sent By thunt Date 2018-03-07 Time 07:26 Rev Time 0.00
Received By thunt Date 2018-02-28 Time 13:19 Sent To I
Notes
2018-03-01 13:20:01RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-31 Cont ID  
Sent By jleahy Date 2018-01-31 Time 13:28 Rev Time 0.00
Received By jleahy Date 2018-01-18 Time 11:31 Sent To  
Notes
2018-01-19 11:32:03ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2018-01-23 Cont ID  
Sent By AW Date 2018-01-23 Time 09:57 Rev Time 0.00
Received By awooten Date 2018-01-22 Time 15:41 Sent To  
Notes
***NONE***