| 2018-01-24 10:15:47 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE 22 KW GENERATOR SPECIFICATIONS THAT WERE | | | SUBMITTED ARE FOR TWO DIFFERENT GENERAC MODELS. REMOVE | | | THE SPECS. FOR THE ONE THAT WILL NOT BE INSTALLED FROM | | | THE SUBMITTAL. FBC 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR | | | THE AMERICAST GENERATOR PAD THAT LISTS THE SPECIFIC | | | MODEL GENERATOR THAT YOU PLAN TO INSTALL. FBC-R301.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-06 |
Time |
06:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-06 |
Time |
06:30 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-01-25 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-01-25 |
Time |
16:59 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-03-02 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-03-02 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-03-02 |
Time |
18:09 |
Sent To |
|
|
| Notes |
| 2018-03-02 18:44:20 | APPROVED BY PLUMBING AND PUT BACK IN GENERATOR BIN, LAC |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-01-26 |
Time |
06:00 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-01-26 |
Time |
05:22 |
Sent To |
I |
|
| Notes |
| 2018-01-26 06:00:27 | 1) THE GAS CODE IN EFFECT FOR THIS PERMIT IS THE 2017 | | | FBC-FUEL GAS, NOT THE 2014 AS NOTED ON THE PLANS AND | | | THE SUBMITTED SIZING TABLES. | | | 2) THE MANUFACTURER'S SPECIFICATIONS FOR THE 22 KW | | | GENERATOR SHOW THE BTU RATING OF THE THE GENERATOR AT | | | 100 % FULL LOAD 310,000 BTU'S BUT THE GAS PLAN SHOWS | | | 281,000 BTU'S. CLARIFY.SEE 2017 FBC-FUEL GAS SECS. | | | 402.1, 402.2. | | | 3) THE SIZE OF THE GAS LINE FROM THE OUTLET OF THE GAS | | | METER SHALL BE INCREASED TO 1 1/4 INCH PER 2017 | | | FBC-FUEL GAS TABLE 402.4 (2). THE MAXIMUM BTU LOAD THAT | | | CAN BE INSTALLED ON A 1/2 LB. GAS METER WITH A 1 INCH | | | LINE WITH A DISTANCE OF 45 FEET IS 284,000 BTU'S. THE | | | TOTAL BTU LOAD MUST BE TAKEN INTO ACCOUNT FOR THE | | | SIZING OF THE PIPE LINE AT THE OUTLET OF THE | | | METER.REFER TO 2017 FBC-FUEL GAS SECS.401.3, 401.4, | | | 401.8. | | | 4) THE GAS PLAN REFERENCES TABLE 402.4 (15) WHICH IS | | | FOR CSST BUT THERE IS NO CSST SHOWN ON THE GAS PLAN. | | | CLARIFY. | | | 5) IDENTIFY THE TYPE OF PIPE RUNNING THROUGH THE | | | GARAGE. IF IT IS CSST, SUBMIT THE CORRESPONDING EHD OF | | | THE SIZE CSST PIPE IN ACCORDANCE WITH TABLE 402.4 (15) | | | OF THE 2017 FBC-FUEL GAS CODE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-06 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-02-27 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2018-02-28 09:19:52 | RESUB ROUTED TO AWOOTEN VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-01-26 |
Time |
06:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-01-18 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2018-01-19 11:29:51 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-01 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-03-01 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-03-01 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-01-23 |
|
|
Cont ID |
|
| Sent By |
AW |
Date |
2018-01-23 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-01-22 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |