Plan Review Details - Permit 18010661
Plan Review Stops For Permit 18010661
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By rmcdouga Date 2018-03-06 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2018-03-06 Time 07:13 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By rmcdouga Date 2018-01-24 Time 08:53 Rev Time 0.00
Received By rmcdouga Date 2018-01-24 Time 07:59 Sent To E
Notes
2018-01-24 10:15:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE 22 KW GENERATOR SPECIFICATIONS THAT WERE
 SUBMITTED ARE FOR TWO DIFFERENT GENERAC MODELS. REMOVE
 THE SPECS. FOR THE ONE THAT WILL NOT BE INSTALLED FROM
 THE SUBMITTAL. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR
 THE AMERICAST GENERATOR PAD THAT LISTS THE SPECIFIC
 MODEL GENERATOR THAT YOU PLAN TO INSTALL. FBC-R301.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By jleahy Date 2018-03-06 Time 06:30 Rev Time 0.00
Received By jleahy Date 2018-03-06 Time 06:30 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-01-25 Cont ID  
Sent By jleahy Date 2018-01-25 Time 16:59 Rev Time 0.00
Received By jleahy Date 2018-01-25 Time 16:59 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-03-02 Cont ID  
Sent By lcrespo Date 2018-03-02 Time 18:09 Rev Time 0.00
Received By lcrespo Date 2018-03-02 Time 18:09 Sent To  
Notes
2018-03-02 18:44:20APPROVED BY PLUMBING AND PUT BACK IN GENERATOR BIN, LAC

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By tklarge Date 2018-01-26 Time 06:00 Rev Time 0.00
Received By tklarge Date 2018-01-26 Time 05:22 Sent To I
Notes
2018-01-26 06:00:271) THE GAS CODE IN EFFECT FOR THIS PERMIT IS THE 2017
 FBC-FUEL GAS, NOT THE 2014 AS NOTED ON THE PLANS AND
 THE SUBMITTED SIZING TABLES.
 2) THE MANUFACTURER'S SPECIFICATIONS FOR THE 22 KW
 GENERATOR SHOW THE BTU RATING OF THE THE GENERATOR AT
 100 % FULL LOAD 310,000 BTU'S BUT THE GAS PLAN SHOWS
 281,000 BTU'S. CLARIFY.SEE 2017 FBC-FUEL GAS SECS.
 402.1, 402.2.
 3) THE SIZE OF THE GAS LINE FROM THE OUTLET OF THE GAS
 METER SHALL BE INCREASED TO 1 1/4 INCH PER 2017
 FBC-FUEL GAS TABLE 402.4 (2). THE MAXIMUM BTU LOAD THAT
 CAN BE INSTALLED ON A 1/2 LB. GAS METER WITH A 1 INCH
 LINE WITH A DISTANCE OF 45 FEET IS 284,000 BTU'S. THE
 TOTAL BTU LOAD MUST BE TAKEN INTO ACCOUNT FOR THE
 SIZING OF THE PIPE LINE AT THE OUTLET OF THE
 METER.REFER TO 2017 FBC-FUEL GAS SECS.401.3, 401.4,
 401.8.
 4) THE GAS PLAN REFERENCES TABLE 402.4 (15) WHICH IS
 FOR CSST BUT THERE IS NO CSST SHOWN ON THE GAS PLAN.
 CLARIFY.
 5) IDENTIFY THE TYPE OF PIPE RUNNING THROUGH THE
 GARAGE. IF IT IS CSST, SUBMIT THE CORRESPONDING EHD OF
 THE SIZE CSST PIPE IN ACCORDANCE WITH TABLE 402.4 (15)
 OF THE 2017 FBC-FUEL GAS CODE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-06 Cont ID  
Sent By rmcdouga Date 2018-03-06 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2018-02-27 Time 09:19 Sent To  
Notes
2018-02-28 09:19:52RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-26 Cont ID  
Sent By tklarge Date 2018-01-26 Time 06:01 Rev Time 0.00
Received By tklarge Date 2018-01-18 Time 11:29 Sent To  
Notes
2018-01-19 11:29:51ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status N Date 2018-03-01 Cont ID  
Sent By awooten Date 2018-03-01 Time 15:14 Rev Time 0.00
Received By awooten Date 2018-03-01 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-01-23 Cont ID  
Sent By AW Date 2018-01-23 Time 09:03 Rev Time 0.00
Received By awooten Date 2018-01-22 Time 15:41 Sent To  
Notes
***NONE***