Plan Review Details - Permit 18010630
Plan Review Stops For Permit 18010630
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By spalmer Date 2018-04-09 Time 15:00 Rev Time 0.00
Received By spalmer Date 2018-04-09 Time 15:00 Sent To  
Notes
2018-04-09 15:01:19OKAY PER MASTER18010629
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-06 Cont ID  
Sent By lcrespo Date 2018-02-06 Time 16:36 Rev Time 0.00
Received By lcrespo Date 2018-02-05 Time 15:49 Sent To  
Notes
2018-02-06 16:36:24DENIED
  
 1. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS; PROVIDE DOCUMENTATION FROM THE
 MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. REGULATORS INSTALLED OUTDOORS SHALL BE
 DESIGNED, INSTALLED OR PROTECTED SO THEIR OPERATION
 WILL NOT BE AFFECTED BY THE ELEMENTS. 2017 FGC SEC.
 G2421.1.
  
 2. PLEASE CLARIFY WHAT IS MEANT BY 1? RIDGED, WHAT TYPE
 OF PIPE, THE SIZE OF PIPE TO EXISTING LOADS AND THE
 DISTANCE, SIZE AND TYPE OF PIPE FROM NATURAL GAS METER
 TO REGULATOR FOR EXISTING LOADS. 2017 FGC SEC. G2415.14
  
 3. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE
 TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. THESE REQUIREMENTS
 ALSO APPLY TO A NEW GAS SYSTEM. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FBC 2017 R SEC. G2412.4, G2412.8,
 G2413.1, G2413.2, G2413.3.
  
 4. NFPA 37 SEC. 4.1.4 REQUIRES 5? FROM THE EXTERIOR
 WALL NOT RATED FOR 1 HR / OR SUBMIT INSTALLATION MANUAL
 FROM GENERAC SHOWING MIN DISTANCE FROM WALL PER
 MANUFACTURES INSTALLATION INSTRUCTIONS.
  
 5. NEED SEPARATE PERMIT APPLICATION FOR GAS IS REQUIRED
 WPB FBC A 105.3
  
 NFPA 37 SEC. 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES,
 AND THEIR WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-06 Cont ID  
Sent By lcrespo Date 2018-02-06 Time 16:36 Rev Time 0.00
Received By lcrespo Date 2018-02-05 Time 15:49 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved