| 2018-02-06 16:38:09 | DENIED |
| | |
| | 1. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS; PROVIDE DOCUMENTATION FROM THE |
| | MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| | EXTERIOR USE. REGULATORS INSTALLED OUTDOORS SHALL BE |
| | DESIGNED, INSTALLED OR PROTECTED SO THEIR OPERATION |
| | WILL NOT BE AFFECTED BY THE ELEMENTS. 2017 FGC SEC. |
| | G2421.1. |
| | |
| | 2. PLEASE CLARIFY WHAT IS MEANT BY 1? RIDGED, WHAT TYPE |
| | OF PIPE, THE SIZE OF PIPE TO EXISTING LOADS AND THE |
| | DISTANCE, SIZE AND TYPE OF PIPE FROM NATURAL GAS METER |
| | TO REGULATOR FOR EXISTING LOADS. 2017 FGC SEC. G2415.14 |
| | |
| | 3. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE |
| | TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. THESE REQUIREMENTS |
| | ALSO APPLY TO A NEW GAS SYSTEM. IF UNDERSIZED, THE |
| | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. FBC 2017 R SEC. G2412.4, G2412.8, |
| | G2413.1, G2413.2, G2413.3. |
| | |
| | 4. NFPA 37 SEC. 4.1.4 REQUIRES 5? FROM THE EXTERIOR |
| | WALL NOT RATED FOR 1 HR / OR SUBMIT INSTALLATION MANUAL |
| | FROM GENERAC SHOWING MIN DISTANCE FROM WALL PER |
| | MANUFACTURES INSTALLATION INSTRUCTIONS. |
| | |
| | 5. NEED SEPARATE PERMIT APPLICATION FOR GAS IS REQUIRED |
| | WPB FBC A 105.3 |
| | |
| | NFPA 37 SEC. 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, |
| | AND THEIR WEATHERPROOF |
| | HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS |
| | SHALL |
| | BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS |
| | AND AT |
| | LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE |
| | WALLS. A |
| | MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER |
| | OF THE |
| | FOLLOWING CONDITIONS EXIST: |
| | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5 |
| | M (5 FT) |
| | FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING |
| | OF |
| | AT LEAST 1 HOUR. |
| | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NONCOMBUSTIBLE |
| | MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE |
| | WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS |
| | OUTSIDE THE ENCLOSURE. |
| | |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | [email protected] |
| | 561-805-6720 |