Plan Review Details - Permit 18010595
Plan Review Stops For Permit 18010595
Review Stop G GAS REVIEW
Rev No 5 Status P Date 2018-08-23 Cont ID  
Sent By tklarge Date 2018-08-23 Time 03:54 Rev Time 0.00
Received By tklarge Date 2018-08-23 Time 03:42 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2018-08-08 Cont ID  
Sent By tklarge Date 2018-08-08 Time 05:37 Rev Time 0.00
Received By tklarge Date 2018-08-08 Time 04:57 Sent To I
Notes
2018-08-08 05:36:411) THE SIZING TABLE THAT HAS BEEN SUBMITTED FOR THE PE
 PIPE IS NOT FROM THE 2017 FBC-FUEL GAS CODE. SUBMIT TWO
 COPIES FROM THE 2017 FBC. WPB AMEND. TO FBC SEC. 107.1,
 107.2.1.
 2) MANUFACTURER'S SPECIFICATIONS HAVE BEEN SUBMITTED
 FOR TWO DIFFERENT GAS GRILLS. ONE SET IS FOR A WOLF
 GRILL AND THE OTHER IS FOR AN ARTISAN. WHICH ONE IS
 BEING INSTALLED? SUBMIT TWO COPIES OF THE
 MANUFACTURER'S SPECIFICATIONS FOR THE GRILL BEING
 INSTALLED AND REMOVE THE SPECIFICATIONS THAT ARE NOT
 APPLICABLE.WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE PLANS SHOW AN EXISTING GRILL TO BE RELOCATED YET
 YOU HAVE SUBMITTED SPECIFICATIONS FOR A NEW GRILL. WHAT
 IS THE SCOPE OF WORK BEING DONE? IS THE GRILL NEW OR
 EXISTING? AT THIS POINT, I HAVE NO IDEA AS TO WHAT THE
 SCOPE OF WORK IS TO BE UNDER THIS PERMIT. SUBMIT TWO
 COPIES OF PLANS AND SPECIFICATIONS THAT CLEARLY
 REFLECTS THE ENTIRE SCOPE OF WORK TO BE DONE. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SHOW THE CORRECT BTU LOAD OF THE GRILL ON THE FLOOR
 PLAN AND THE GAS RISER.WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOTE - I SUGGEST CONTACTING THIS RREVIEWER TO DISCUSS
 THESE REVIEW COMMENTS SO I CAN ASSIST IN GETTING THIS
 PERMIT ISSUED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-06-27 Cont ID  
Sent By thunt Date 2018-06-27 Time 20:08 Rev Time 0.00
Received By thunt Date 2018-06-27 Time 20:08 Sent To  
Notes
2018-06-27 20:17:1806/27/2018 3RD GAS REVIEW**DENIED**
  
 YOU HAVE ANSWERED 1 OF 4 COMMENTS. IF THESE PLANS ARE
 DENIED AGAIN A 4X PLAN REVIEW FEE WILL BE APPLIED. FL
 ST. STAUTE 553.80 (2B).
  
 1) THE NEW BBQ ARTISAN GRILL DOCUMENTS PROVIDED DOES
 NOT SHOW IF COMPLIES WITH ANY SPECFIC CODE. YOUR
 PROVIDE DOCS LIST 2 MODELS 36" AND 32". WHICH ONE? THIS
 IS NOT THE BBQ THAT IS APPROVED UNDER THE MASTER
 #17070628. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 (2ND
 REQUEST)
  
 2) THE VALUE OF THE APPROVED BBQ WAS $2,700.00 UNDER
 PERMIT # 17070628.PROVIDE THE COST OF THIS BBQ GRILL.
 THE VALUE OF THIS APPLICATION MUST BE CHANGED TO
 INCLUDE THE COST DIFFERANCE IN EQUIPMENT. WPB AMEND TO
 THE FBC 109.3. THE DIFFERENCE IN VALUE MUST BE APPLIED
 TO THIS PERMIT OR A REVISION UNDER PERMIT # 17070628 .
  
 3) A HOOD VENT IS REQUIRED AS THIS BBQ GRILL WILL BE
 LOCATED UNDER A COVERED ROOF. THE FACT THAT IT HAS OPEN
 SIDE DOES NOT COMPLY. THE MASTER PERMIT #17070628 DOES
 NOT INCLUDE THE REQUIRED HOOD VENT IF BEING INSTALLED
 UNDER A COVERED OPENING. YOU HAVE NOT INCLUDE THIS
 INFORMATION IN YOUR APPLICATION EITHER. WHO WILL BE
 INSTALLING THE HOOD VENT? FBC-FUEL GAS SECTION 623. A
 SEPERATE MECHANICAL APPLICATION FOR PERMIT WILL BE
 REQUIRED.FBC 105.1
  
  
  
 PLEASE BE ADVISED IF YOU ARE TO RESUBMIT ANY DRAWINGS
 THAT HAS A DESIGN PROFESSIONAL NAME AND TITLE BLOCK IT
 IS REQUIRED UNDER FL . ADMIN CODE 61G15-23.001(
 ENGINEERS) OR 61G1-16.001 (ARCH).
  
 PLEASE CONTACT FPU TO VERIFY THE SIZE OF THE GAS METER
 CAN HANDLE THE REQUIRED BTU'S
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-01 Cont ID  
Sent By thunt Date 2018-05-01 Time 16:27 Rev Time 0.00
Received By thunt Date 2018-05-01 Time 16:10 Sent To  
Notes
2018-05-01 16:24:2305/01/2018 2ND GAS REVIEW**DENIED**
  
 1) THE WOLF BBQ GRILL DOCUMENTS PROVIDED DOES NOT SHOW
 IF COMPLIES WITH ANY SPECFIC CODE. THIS IS NOT THE BBQ
 THAT IS APPROVED UNDER THE MASTER #17070628. SUBMIT
 MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1 (2ND REQUEST)
  
 2) THE VALUE OF THE APPROVED BBQ WAS $2,700.00 UNDER
 PERMIT # 17070628. THE BBQ UNDER YOUR PERMIT MSRP IS
 $6,375.00. THE VALUE OF THIS APPLICATION MUST BE
 CHANGED TO INCLUDE THE COST DIFFERANCE IN EQUIPMENT.
 WPB AMEND TO THE FBC 109.3
  
 3) THE MASTER PERMIT #17070628 DOES NOT INCLUDE THE
 REQUIRED HOOD VENT IF BEING INSTALLED UNDER A COVERED
 OPENING. YOU HAVE NOT INCLUDE THIS INFORMATION IN YOUR
 APPLICATION EITHER. WHO WILL BE INSTALLING THE HOOD
 VENT? FBC-FUEL GAS SECTION 623. A SEPERATE MECHANICAL
 APPLICATION FOR PERMIT WILL BE REQUIRED.FBC 105.1
  
 4) YOUR BTU (80,000) LISTED IS INCORRECT. THIS BBQ IS
 91,000BTU PER THE INSTALLATION MANUAL I WAS ABLE TO
 PULL FROM WOLF. PLEASE REVISED ISOMETRIC TO REFLECT
 THIS. FBC-FUEL GAS 402.1
  
 PLEASE BE ADVISED IF YOU ARE TO RESUBMIT ANY DRAWINGS
 THAT HAS A DESIGN PROFESSIONAL NAME AND TITLE BLOCK IT
 IS REQUIRED UNDER FL . ADMIN CODE 61G15-23.001(
 ENGINEERS) OR 61G1-16.001 (ARCH).
  
 PLEASE CONTACT FPU TO VERIFY THE SIZE OF THE GAS METER
 CAN HANDLE THE REQUIRED BTU'S
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By thunt Date 2018-01-22 Time 05:28 Rev Time 0.00
Received By thunt Date 2018-01-22 Time 05:28 Sent To  
Notes
2018-01-22 05:39:0501/22/2018 GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1) CITY RECORDS SHOW THE TOTAL EXISTING LOAD ON THE GAS
 SYSTEM AS 1,410,000 BTU. PLEASE PROVIDE AN ACCURATE
 ISOMETRIC DRAWING AND VERIFY THAT THE SYSTEM IS NOT
 UNDERSIZED @ .5LB. FBC 107.2.14.LIST THE BTU LOAD OF
 EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
 REFER TO THE 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1
 AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES.
 SEC. G2413
  
 2) CITY RECORDS SHOWS THAT THE EXISTING GAS SYTEM WAS
 SIZED BASED ON 402.2 (2) USING A PRESSURE DROP OF .5.
 PLEASE RESUBMIT USING THE SAME TABLE AS EXISTING. FBC
 107.2.1. ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL NEW GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-08-23 Cont ID  
Sent By tklarge Date 2018-08-23 Time 03:54 Rev Time 0.00
Received By tklarge Date 2018-08-14 Time 16:05 Sent To  
Notes
2018-08-15 16:05:43RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-08 Cont ID  
Sent By tklarge Date 2018-08-08 Time 05:38 Rev Time 0.00
Received By tklarge Date 2018-08-02 Time 11:30 Sent To  
Notes
2018-08-03 11:31:49RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-27 Cont ID  
Sent By thunt Date 2018-06-27 Time 20:17 Rev Time 0.00
Received By thunt Date 2018-06-15 Time 15:52 Sent To I
Notes
2018-06-18 15:52:35RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-01 Cont ID  
Sent By thunt Date 2018-05-01 Time 16:59 Rev Time 0.00
Received By thunt Date 2018-04-30 Time 13:07 Sent To  
Notes
2018-05-01 13:08:09RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By thunt Date 2018-01-22 Time 05:39 Rev Time 0.00
Received By thunt Date 2018-01-17 Time 11:13 Sent To I
Notes
2018-01-18 11:14:12PLUMB <5K