| Plan Review Stops For Permit 18010595 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2018-08-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-08-23 |
Time |
03:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-08-23 |
Time |
03:42 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2018-08-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-08-08 |
Time |
05:37 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-08-08 |
Time |
04:57 |
Sent To |
I |
|
| Notes |
| 2018-08-08 05:36:41 | 1) THE SIZING TABLE THAT HAS BEEN SUBMITTED FOR THE PE | | | PIPE IS NOT FROM THE 2017 FBC-FUEL GAS CODE. SUBMIT TWO | | | COPIES FROM THE 2017 FBC. WPB AMEND. TO FBC SEC. 107.1, | | | 107.2.1. | | | 2) MANUFACTURER'S SPECIFICATIONS HAVE BEEN SUBMITTED | | | FOR TWO DIFFERENT GAS GRILLS. ONE SET IS FOR A WOLF | | | GRILL AND THE OTHER IS FOR AN ARTISAN. WHICH ONE IS | | | BEING INSTALLED? SUBMIT TWO COPIES OF THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE GRILL BEING | | | INSTALLED AND REMOVE THE SPECIFICATIONS THAT ARE NOT | | | APPLICABLE.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) THE PLANS SHOW AN EXISTING GRILL TO BE RELOCATED YET | | | YOU HAVE SUBMITTED SPECIFICATIONS FOR A NEW GRILL. WHAT | | | IS THE SCOPE OF WORK BEING DONE? IS THE GRILL NEW OR | | | EXISTING? AT THIS POINT, I HAVE NO IDEA AS TO WHAT THE | | | SCOPE OF WORK IS TO BE UNDER THIS PERMIT. SUBMIT TWO | | | COPIES OF PLANS AND SPECIFICATIONS THAT CLEARLY | | | REFLECTS THE ENTIRE SCOPE OF WORK TO BE DONE. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 4) SHOW THE CORRECT BTU LOAD OF THE GRILL ON THE FLOOR | | | PLAN AND THE GAS RISER.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | NOTE - I SUGGEST CONTACTING THIS RREVIEWER TO DISCUSS | | | THESE REVIEW COMMENTS SO I CAN ASSIST IN GETTING THIS | | | PERMIT ISSUED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2018-06-27 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-06-27 |
Time |
20:08 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-06-27 |
Time |
20:08 |
Sent To |
|
|
| Notes |
| 2018-06-27 20:17:18 | 06/27/2018 3RD GAS REVIEW**DENIED** | | | | | | YOU HAVE ANSWERED 1 OF 4 COMMENTS. IF THESE PLANS ARE | | | DENIED AGAIN A 4X PLAN REVIEW FEE WILL BE APPLIED. FL | | | ST. STAUTE 553.80 (2B). | | | | | | 1) THE NEW BBQ ARTISAN GRILL DOCUMENTS PROVIDED DOES | | | NOT SHOW IF COMPLIES WITH ANY SPECFIC CODE. YOUR | | | PROVIDE DOCS LIST 2 MODELS 36" AND 32". WHICH ONE? THIS | | | IS NOT THE BBQ THAT IS APPROVED UNDER THE MASTER | | | #17070628. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 (2ND | | | REQUEST) | | | | | | 2) THE VALUE OF THE APPROVED BBQ WAS $2,700.00 UNDER | | | PERMIT # 17070628.PROVIDE THE COST OF THIS BBQ GRILL. | | | THE VALUE OF THIS APPLICATION MUST BE CHANGED TO | | | INCLUDE THE COST DIFFERANCE IN EQUIPMENT. WPB AMEND TO | | | THE FBC 109.3. THE DIFFERENCE IN VALUE MUST BE APPLIED | | | TO THIS PERMIT OR A REVISION UNDER PERMIT # 17070628 . | | | | | | 3) A HOOD VENT IS REQUIRED AS THIS BBQ GRILL WILL BE | | | LOCATED UNDER A COVERED ROOF. THE FACT THAT IT HAS OPEN | | | SIDE DOES NOT COMPLY. THE MASTER PERMIT #17070628 DOES | | | NOT INCLUDE THE REQUIRED HOOD VENT IF BEING INSTALLED | | | UNDER A COVERED OPENING. YOU HAVE NOT INCLUDE THIS | | | INFORMATION IN YOUR APPLICATION EITHER. WHO WILL BE | | | INSTALLING THE HOOD VENT? FBC-FUEL GAS SECTION 623. A | | | SEPERATE MECHANICAL APPLICATION FOR PERMIT WILL BE | | | REQUIRED.FBC 105.1 | | | | | | | | | | | | PLEASE BE ADVISED IF YOU ARE TO RESUBMIT ANY DRAWINGS | | | THAT HAS A DESIGN PROFESSIONAL NAME AND TITLE BLOCK IT | | | IS REQUIRED UNDER FL . ADMIN CODE 61G15-23.001( | | | ENGINEERS) OR 61G1-16.001 (ARCH). | | | | | | PLEASE CONTACT FPU TO VERIFY THE SIZE OF THE GAS METER | | | CAN HANDLE THE REQUIRED BTU'S | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-05-01 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-05-01 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-05-01 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2018-05-01 16:24:23 | 05/01/2018 2ND GAS REVIEW**DENIED** | | | | | | 1) THE WOLF BBQ GRILL DOCUMENTS PROVIDED DOES NOT SHOW | | | IF COMPLIES WITH ANY SPECFIC CODE. THIS IS NOT THE BBQ | | | THAT IS APPROVED UNDER THE MASTER #17070628. SUBMIT | | | MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION | | | MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE | | | SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED. THE | | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT | | | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC | | | SEC.305.1, FBC-RES. SEC.G2408.1 (2ND REQUEST) | | | | | | 2) THE VALUE OF THE APPROVED BBQ WAS $2,700.00 UNDER | | | PERMIT # 17070628. THE BBQ UNDER YOUR PERMIT MSRP IS | | | $6,375.00. THE VALUE OF THIS APPLICATION MUST BE | | | CHANGED TO INCLUDE THE COST DIFFERANCE IN EQUIPMENT. | | | WPB AMEND TO THE FBC 109.3 | | | | | | 3) THE MASTER PERMIT #17070628 DOES NOT INCLUDE THE | | | REQUIRED HOOD VENT IF BEING INSTALLED UNDER A COVERED | | | OPENING. YOU HAVE NOT INCLUDE THIS INFORMATION IN YOUR | | | APPLICATION EITHER. WHO WILL BE INSTALLING THE HOOD | | | VENT? FBC-FUEL GAS SECTION 623. A SEPERATE MECHANICAL | | | APPLICATION FOR PERMIT WILL BE REQUIRED.FBC 105.1 | | | | | | 4) YOUR BTU (80,000) LISTED IS INCORRECT. THIS BBQ IS | | | 91,000BTU PER THE INSTALLATION MANUAL I WAS ABLE TO | | | PULL FROM WOLF. PLEASE REVISED ISOMETRIC TO REFLECT | | | THIS. FBC-FUEL GAS 402.1 | | | | | | PLEASE BE ADVISED IF YOU ARE TO RESUBMIT ANY DRAWINGS | | | THAT HAS A DESIGN PROFESSIONAL NAME AND TITLE BLOCK IT | | | IS REQUIRED UNDER FL . ADMIN CODE 61G15-23.001( | | | ENGINEERS) OR 61G1-16.001 (ARCH). | | | | | | PLEASE CONTACT FPU TO VERIFY THE SIZE OF THE GAS METER | | | CAN HANDLE THE REQUIRED BTU'S | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-01-22 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-22 |
Time |
05:28 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-22 |
Time |
05:28 |
Sent To |
|
|
| Notes |
| 2018-01-22 05:39:05 | 01/22/2018 GAS 1ST REVIEW**DENIED** | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | | | | 1) CITY RECORDS SHOW THE TOTAL EXISTING LOAD ON THE GAS | | | SYSTEM AS 1,410,000 BTU. PLEASE PROVIDE AN ACCURATE | | | ISOMETRIC DRAWING AND VERIFY THAT THE SYSTEM IS NOT | | | UNDERSIZED @ .5LB. FBC 107.2.14.LIST THE BTU LOAD OF | | | EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. | | | REFER TO THE 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 | | | AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. | | | SEC. G2413 | | | | | | 2) CITY RECORDS SHOWS THAT THE EXISTING GAS SYTEM WAS | | | SIZED BASED ON 402.2 (2) USING A PRESSURE DROP OF .5. | | | PLEASE RESUBMIT USING THE SAME TABLE AS EXISTING. FBC | | | 107.2.1. ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING | | | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON | | | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) | | | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN | | | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 | | | FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES | | | 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. | | | G2412.4, G2412.8, G2413.1, G2413.2, & G2413 | | | | | | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL NEW GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-08-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-08-23 |
Time |
03:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-08-14 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2018-08-15 16:05:43 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-08-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-08-08 |
Time |
05:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-08-02 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2018-08-03 11:31:49 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-06-27 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-06-27 |
Time |
20:17 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-06-15 |
Time |
15:52 |
Sent To |
I |
|
| Notes |
| 2018-06-18 15:52:35 | RESUB ROUTED TO THUNT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-05-01 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-05-01 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-04-30 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2018-05-01 13:08:09 | RESUB ROUTED TO THUNT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-22 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-22 |
Time |
05:39 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-17 |
Time |
11:13 |
Sent To |
I |
|
| Notes |
| 2018-01-18 11:14:12 | PLUMB <5K |
|
|