Plan Review Details - Permit 18010592
| Plan Review Stops For Permit 18010592 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-08-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-14 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-14 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-07-17 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-07-17 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2019-07-17 17:57:39 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING PLAN (WINDOW RESUBMITTAL) REVIEW DENIED: | | | | | | FBC B 107.2.1 PLEASE PROVIDE LOCATIONS AND WINDOW TYPES | | | THAT ARE TO BE ELIMINATED. THE WINDOW ELIMINATIONS NEED | | | TO BE CLEARLY IDENTIFIED ON WINDOW SCHEDULE AND ON | | | FLOOR PLAN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-05 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-05 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-02-21 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-02-20 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2018-02-21 10:26:49 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017 | | | FLORIDA BUILDING CODE, 6TH EDITION. | | | | | | 1. PROVIDE SOILS REPORT. | | | 2. THIS PROJECT IS NOT LOCATED IN A SPECIAL FLOOD | | | HAZARD AREA (SFHA). FLOOD ZONE - X. PROPOSED FLOOD | | | VENTS IN GARAGE ARE OPTIONAL. | | | 3. PROVIDE SITE DRAINAGE PLAN. | | | 4. PROVIDE SURVEY WITH FINISHED FLOOR ELEVATION. | | | 5. VALUE ADJUSTED FROM $610,000 STATED TO $697,232 | | | BASED ON ICC BUILDING EVALUATION DATA. | | | 6. OWNER/ AGENT TO SIGN ENERGY SUBMITTAL. | | | 7. PRODUCT APPROVALS WILL BE DEFERRED. INCLUDED ICYNENE | | | INSULATION SUBMITTAL. | | | 8. STATED CONSTRUCTION TYPE ON PLAN PAGE A-0 IS TYPE IV | | | (HEAVY TIMBER). THIS TYPE OF CONSTRUCTION SHOULD BE | | | CLASSIFIED AS TYPE V UNPROTECTED. PLEASE CLARIFY. | | | | | | R401.4 SOIL TESTS. | | | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL | | | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, | | | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE | | | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL | | | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE | | | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. | | | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN | | | APPROVED METHOD. | | | | | | FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, | | | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE | | | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE | | | SURVEY. | | | | | | CITY OF WPB CHPT. 1 ? VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION | | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 602.5 TYPE V. | | | TYPE V CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN | | | WHICH THE STRUCTURAL ELEMENTS, EXTERIOR WALLS AND | | | INTERIOR WALLS ARE OF ANY MATERIALS PERMITTED BY THIS | | | CODE | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-07-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-16 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-16 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-11-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-09 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-09 |
Time |
13:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-30 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-30 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2018-10-30 13:25:22 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | ALL PREVIOUS COMMENTS ADDRESSED EXCEPT THE FOLLOWING | | | (SEE FURTHER COMMENTS IN PARENTHESES): | | | | | | 1. 1ST AND 2ND FLOOR | | | | | | SMOKE ALARMS AND CO ALARM REQUIRED R314, R315 | | | (IT APPEARS THAT THE CORRECTIONS NOTED TO BE ON SHEET | | | E4 WERE NOT SUBMITTED. THE E4 IN THE PACKAGE IS THE | | | OLDER VERSION. PROVIDE CORRECTION.) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-02-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-08 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-02-08 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2018-02-09 07:17:44 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-1 | | | | | | LAUNDRY AREA | | | | | | GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN | | | THIS AREA. | | | | | | E3902.9 LAUNDRY AREAS. | | | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES | | | INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT | | | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. | | | [210.8(A)(9)] | | | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, | | | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] | | | | | | | | | KITCHEN | | | | | | GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN | | | THIS AREA. | | | COUNTER ON LEFT SIDE NEEDS OUTLETS PER CODE 210.52 | | | DISHWASHER NEEDS TO BE GFCI PROTECTED. | | | | | | E3902.6 KITCHEN RECEPTACLES. | | | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES | | | THAT SERVE COUNTERTOP SURFACES SHALL HAVE GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. | | | [210.8(A)(6)] | | | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, | | | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] | | | E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. | | | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE | | | PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN | | | DWELLING UNIT LOCATIONS. [210.8(D)] | | | E3901.4 COUNTERTOP RECEPTACLES. | | | IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND | | | SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR | | | COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH | | | SECTIONS E3901.4.1 THROUGH E3901.4.5 | | | | | | | | | OUTDOOR PATIO (GRILL AREA) | | | | | | GFCI PROTECTION ON ALL 15 AND 20A OUTLETS INSTALLED | | | OUTSIDE. | | | | | | E3902.3 OUTDOOR RECEPTACLES. | | | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES | | | INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. | | | [210.8(A)(3)] | | | | | | | | | | | | MEDIA ROOM | | | | | | OUTLET SPACING DOES NOT APPEAR TO MEET CODE | | | E3901.2.1 SPACING. | | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE | | | OUTLET. [210.52(A)(1)] | | | | | | | | | | | | GARAGE | | | | | | DOOR OPENERS TO BE GFCI PROTECTED | | | | | | E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES. | | | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES | | | INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF | | | UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK | | | AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER | | | PROTECTION FOR PERSONNEL. [210.8(A)(2)] | | | | | | BATH #2 | | | | | | NO OUTLET INSTALLED | | | | | | E3901.6 BATHROOM. | | | AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED | | | IN BATHROOMS AND SUCH OUTLET SHALL BE LOCATED WITHIN 36 | | | INCHES (914 MM) OF THE OUTSIDE EDGE OF EACH LAVATORY | | | BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL | | | OR PARTITION THAT IS ADJACENT TO THE LAVATORY BASIN | | | LOCATION, LOCATED ON THE COUNTERTOP, OR INSTALLED ON | | | THE SIDE OR FACE OF THE BASIN CABINET. THE RECEPTACLE | | | SHALL BE LOCATED NOT MORE THAN 12 INCHES (305 MM) BELOW | | | THE TOP OF THE BASIN. RECEPTACLE OUTLETS SHALL NOT BE | | | INSTALLED IN A FACE-UP POSITION IN THE WORK SURFACES OR | | | COUNTERTOPS IN A BATHROOM BASIN LOCATION. RECEPTACLE | | | OUTLET ASSEMBLIES INSTALLED IN COUNTERTOPS SHALL BE | | | LISTED FOR THE APPLICATION. [210.52( | | | | | | | | | 1ST AND 2ND FLOOR | | | | | | SMOKE ALARMS AND CO ALARM REQUIRED R314, R315 | | | | | | PAGE -E-2 | | | | | | BATH #1 | | | | | | NEEDS A LIGHT AND SWITCH AT EXTERIOR DOOR. | | | | | | E3903.3 ADDITIONAL LOCATIONS. | | | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED | | | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT | | | LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL | | | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR | | | SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL | | | ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED | | | GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A | | | VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN | | | OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS | | | ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A | | | WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT | | | INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS | | | WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE | | | RISERS. [210.70(A)(2)] | | | | | | | | | | | | | | | PAGE E-5 | | | | | | RISER DIAGRAM SHOWS 1/0 ON 200A MAIN AS A FEED TO PANEL | | | "B" | | | | | | E3603.1.2 UNGROUNDED FEEDER CONDUCTORS. | | | FOR A FEEDER RATED AT 100 THROUGH 400 AMPERES, THE | | | FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED | | | WITH A ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS | | | SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL | | | DWELLING UNIT IN A TWO-FAMILY DWELLING, SHALL HAVE AN | | | AMPACITY OF NOT LESS THAN 83 PERCENT OF THE FEEDER | | | RATING | | | | | | NEED INTER SYSTEM BONDING STRIP 250.94 | | | | | | E3609.3 BONDING FOR OTHER SYSTEMS. | | | AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING | | | INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER | | | SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE | | | SERVICE EQUIPMENT OR METERING EQUIPMENT ENCLOSURE AND | | | AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS | | | OR STRUCTURES. | | | | | | | | | NOTES HAVE REFERENCES TO 2008 AND 2011 CODES WE ARE | | | USING THE 2014 NEC. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-04 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-04 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2018-12-04 13:33:20 | GAS COMMENTS: APPROVED | | | PROVISO | | | 1. A REVISION IS REQUIRED AS FOLLOWS: | | | A) RECONCILE RED LINED ITEMS ON P-1 TO MATCH P-3. | | | REVISION IS REQUIRED TO BE IN PLACE PRIOR TO FINAL | | | INSPECTION. | | | 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-02-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-02-14 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-02-14 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2018-02-14 08:23:19 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. THE DEVELOPED LENGTH TO TH FURTHEST APPLIANCE ON THE | | | GAS RISER ADDS UP TO 165' UNDER THE GAS RISER NOTES IT | | | IS LISTED AT 150 PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 2. THE SIZING TABLES ARE LISTED UNDER THE FBC 2014 THE | | | CURRENT CODE IS THE FBC FG 2017 PLEASE CORRECT ON PLAN. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND | | | INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND | | | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 6. THE FUTURE POOL HEATER IS MISSING FROM THE GAS LOAD | | | CALCULATIONS PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 7. THE BBQ GRILLE IS SHOWN AS 100,000 ON THE GAS RISER | | | AND IS LISTED AS 75,000 ON THE GAS LOAD CALCULATION | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 8. THE FUTURE GENERATOR IS SHOWN AS 22,100 ON THE RISER | | | AND 221,000 ON THE GAS LOAD CALCULATION PLEASE CLARIFY. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 9. THE TANKLESS WATER HEATER IS SHOWN AS 199,000 ON THE | | | RISER AND 130,000 ON THE GAS LOAD CALCULATION PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 10. THE TOTAL GAS LOAD CALCULATION I CAME UP WITH IS | | | 1,320,000 THE PLAN SHOWS 826,00 PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 11. THE RISER IS SHOWING THE BRANCH TO THE WATER | | | HEATER, DRYER AND FIRE PLACE AS UNDERGROUND PE WITCH IS | | | NOT ALLOWED UNDER STRUCTURES THE FLOOR PLAN SHOWS ABOVE | | | CLG SCH 40 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 12. SHOW THE TRANSITION FROM PE TO SCH 40 ABOVE THE | | | GROUND AT THE FIRST BRANCH. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 13. THE CONNECTION FOR THE GENERATOR SHALL BE A MIN. OF | | | 3/4 ON THE .05LB SIDE OF THE REGULATOR. PER FBC FG | | | TABLE 402.4(2) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-07-17 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-21 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-12-20 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-10-17 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2018-12-08 10:33:44 | 12/8 ROUTED TO ZONING BOX, SENT EMAIL | | | | | | | | 2018-10-19 14:10:06 | R28 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-02-21 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-01-17 |
Time |
15:40 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2018-02-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-02-21 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-02-20 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2018-12-05 08:24:55 | MU 2018-1534 FEES PAID $21.91 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-11-05 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-11-05 |
Time |
12:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-02-15 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-02-15 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-02-15 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-04 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-04 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2018-12-04 13:26:16 | PLUMBING COMMENTS: APPROVED | | | PLUMBING PROVISO | | | 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-02-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-02-14 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-02-13 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2018-02-14 07:20:41 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE WASHING MACHINE BOX IS NOT VENTED. PER FBC RES | | | P3101.2.1 | | | | | | 2. THE BAR SINK SHALL CONNECT TO THE BRANCH DRAIN OR | | | BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP IT CAN | | | NOT CONNECT TO THE HORIZONTAL WET DRAIN OF THE BATHROOM | | | GROUP. P3108.1 | | | | | | 3. THE AAV ON THE BATHROOM #2 SHOWER SHALL BE | | | ACCESSIBLE. FBC RES P3114.5 ACCESS AND VENTILATION. | | | ACCESS SHALL BE PROVIDED TO AIR ADMITTANCE VALVES. SUCH | | | VALVES SHALL BE INSTALLED IN A LOCATION THAT ALLOWS AIR | | | TO ENTER THE VALVE. | | | | | | 4. BATHROOM #2 IS LABELED AS LAUNDRY-ON THE ISOMETRIC | | | DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. PROVIDE THE SQFT ON THE ROOF DRAINS. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-12-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-05 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-05 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-02-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-02-21 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-02-21 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2018-02-21 10:10:13 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017 | | | FLORIDA BUILDING CODE, 6TH EDITION. | | | | | | 1. ROOFING PERMIT REQUIRED. | | | 2. ALL SUBMITTALS WILL BE DEFERRED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-07-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2019-07-10 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2019-07-10 12:54:55 | 1.) PLEASE NOTE MAX DRIVEWAY WIDTH IS 20 FEET, SEPARATE | | | PERMIT REQUIRED | | | | | | 2.) LANDSCAPE PERMIT REQUIRED, PLEASE SUBMIT | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-12-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-12-20 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2018-12-20 10:18:42 | 1.) PLEASE NOTE MAX DRIVEWAY WIDTH IS 20 FEET, SEPARATE | | | PERMIT REQUIRED | | | | | | 2.) LANDSCAPE PERMIT REQUIRED, PLEASE SUBMIT | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-02-02 |
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2018-02-02 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-01-30 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2018-02-02 13:25:46 | FAILED | | | | | | 1.) LABEL SETBACKS FOR ALL PROPOSED MECHANICAL | | | EQUIPMENT | | | 2.) SEPARATE PERMITS REQUIRED FOR LANDSCAPING, | | | DRIVEWAY, POOL ETC. INDICATE ON PLANS | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
|