Plan Review Details - Permit 18010592
Plan Review Stops For Permit 18010592
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-08-14 Cont ID  
Sent By pvalenti Date 2019-08-14 Time 10:25 Rev Time 0.00
Received By pvalenti Date 2019-08-14 Time 10:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-07-17 Cont ID  
Sent By pvalenti Date 2019-07-17 Time 17:47 Rev Time 0.00
Received By pvalenti Date 2019-07-17 Time 17:47 Sent To  
Notes
2019-07-17 17:57:39***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN (WINDOW RESUBMITTAL) REVIEW DENIED:
  
 FBC B 107.2.1 PLEASE PROVIDE LOCATIONS AND WINDOW TYPES
 THAT ARE TO BE ELIMINATED. THE WINDOW ELIMINATIONS NEED
 TO BE CLEARLY IDENTIFIED ON WINDOW SCHEDULE AND ON
 FLOOR PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By cthroop Date 2018-12-05 Time 09:46 Rev Time 0.00
Received By cthroop Date 2018-12-05 Time 07:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-21 Cont ID  
Sent By cthroop Date 2018-02-21 Time 10:10 Rev Time 0.00
Received By cthroop Date 2018-02-20 Time 12:24 Sent To  
Notes
2018-02-21 10:26:49BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017
 FLORIDA BUILDING CODE, 6TH EDITION.
  
 1. PROVIDE SOILS REPORT.
 2. THIS PROJECT IS NOT LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). FLOOD ZONE - X. PROPOSED FLOOD
 VENTS IN GARAGE ARE OPTIONAL.
 3. PROVIDE SITE DRAINAGE PLAN.
 4. PROVIDE SURVEY WITH FINISHED FLOOR ELEVATION.
 5. VALUE ADJUSTED FROM $610,000 STATED TO $697,232
 BASED ON ICC BUILDING EVALUATION DATA.
 6. OWNER/ AGENT TO SIGN ENERGY SUBMITTAL.
 7. PRODUCT APPROVALS WILL BE DEFERRED. INCLUDED ICYNENE
 INSULATION SUBMITTAL.
 8. STATED CONSTRUCTION TYPE ON PLAN PAGE A-0 IS TYPE IV
 (HEAVY TIMBER). THIS TYPE OF CONSTRUCTION SHOULD BE
 CLASSIFIED AS TYPE V UNPROTECTED. PLEASE CLARIFY.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 602.5 TYPE V.
 TYPE V CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN
 WHICH THE STRUCTURAL ELEMENTS, EXTERIOR WALLS AND
 INTERIOR WALLS ARE OF ANY MATERIALS PERMITTED BY THIS
 CODE
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-16 Cont ID  
Sent By jpearson Date 2019-07-16 Time 10:30 Rev Time 0.00
Received By jpearson Date 2019-07-16 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 13:22 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 13:49 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 13:02 Sent To  
Notes
2018-10-30 13:25:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 ALL PREVIOUS COMMENTS ADDRESSED EXCEPT THE FOLLOWING
 (SEE FURTHER COMMENTS IN PARENTHESES):
  
 1. 1ST AND 2ND FLOOR
  
 SMOKE ALARMS AND CO ALARM REQUIRED R314, R315
 (IT APPEARS THAT THE CORRECTIONS NOTED TO BE ON SHEET
 E4 WERE NOT SUBMITTED. THE E4 IN THE PACKAGE IS THE
 OLDER VERSION. PROVIDE CORRECTION.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By jleahy Date 2018-02-08 Time 16:38 Rev Time 0.00
Received By jleahy Date 2018-02-08 Time 12:08 Sent To  
Notes
2018-02-09 07:17:44FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 LAUNDRY AREA
  
 GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN
 THIS AREA.
  
 E3902.9 LAUNDRY AREAS.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(9)]
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
  
  
 KITCHEN
  
 GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN
 THIS AREA.
 COUNTER ON LEFT SIDE NEEDS OUTLETS PER CODE 210.52
 DISHWASHER NEEDS TO BE GFCI PROTECTED.
  
 E3902.6 KITCHEN RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT SERVE COUNTERTOP SURFACES SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(6)]
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
 E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
 E3901.4 COUNTERTOP RECEPTACLES.
 IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND
 SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR
 COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTIONS E3901.4.1 THROUGH E3901.4.5
  
  
 OUTDOOR PATIO (GRILL AREA)
  
 GFCI PROTECTION ON ALL 15 AND 20A OUTLETS INSTALLED
 OUTSIDE.
  
 E3902.3 OUTDOOR RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(3)]
  
  
  
 MEDIA ROOM
  
 OUTLET SPACING DOES NOT APPEAR TO MEET CODE
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
  
  
 GARAGE
  
 DOOR OPENERS TO BE GFCI PROTECTED
  
 E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES
 INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF
 UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK
 AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(2)]
  
 BATH #2
  
 NO OUTLET INSTALLED
  
 E3901.6 BATHROOM.
 AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED
 IN BATHROOMS AND SUCH OUTLET SHALL BE LOCATED WITHIN 36
 INCHES (914 MM) OF THE OUTSIDE EDGE OF EACH LAVATORY
 BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL
 OR PARTITION THAT IS ADJACENT TO THE LAVATORY BASIN
 LOCATION, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. THE RECEPTACLE
 SHALL BE LOCATED NOT MORE THAN 12 INCHES (305 MM) BELOW
 THE TOP OF THE BASIN. RECEPTACLE OUTLETS SHALL NOT BE
 INSTALLED IN A FACE-UP POSITION IN THE WORK SURFACES OR
 COUNTERTOPS IN A BATHROOM BASIN LOCATION. RECEPTACLE
 OUTLET ASSEMBLIES INSTALLED IN COUNTERTOPS SHALL BE
 LISTED FOR THE APPLICATION. [210.52(
  
  
 1ST AND 2ND FLOOR
  
 SMOKE ALARMS AND CO ALARM REQUIRED R314, R315
  
 PAGE -E-2
  
 BATH #1
  
 NEEDS A LIGHT AND SWITCH AT EXTERIOR DOOR.
  
 E3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT
 LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL
 ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED
 GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A
 VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN
 OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS
 ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A
 WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT
 INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS
 WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE
 RISERS. [210.70(A)(2)]
  
  
  
  
 PAGE E-5
  
 RISER DIAGRAM SHOWS 1/0 ON 200A MAIN AS A FEED TO PANEL
 "B"
  
 E3603.1.2 UNGROUNDED FEEDER CONDUCTORS.
 FOR A FEEDER RATED AT 100 THROUGH 400 AMPERES, THE
 FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED
 WITH A ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS
 SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT IN A TWO-FAMILY DWELLING, SHALL HAVE AN
 AMPACITY OF NOT LESS THAN 83 PERCENT OF THE FEEDER
 RATING
  
 NEED INTER SYSTEM BONDING STRIP 250.94
  
 E3609.3 BONDING FOR OTHER SYSTEMS.
 AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER
 SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE
 SERVICE EQUIPMENT OR METERING EQUIPMENT ENCLOSURE AND
 AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS
 OR STRUCTURES.
  
  
 NOTES HAVE REFERENCES TO 2008 AND 2011 CODES WE ARE
 USING THE 2014 NEC.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-12-04 Cont ID  
Sent By jesmith Date 2018-12-04 Time 13:33 Rev Time 0.00
Received By jesmith Date 2018-12-04 Time 13:26 Sent To  
Notes
2018-12-04 13:33:20GAS COMMENTS: APPROVED
 PROVISO
 1. A REVISION IS REQUIRED AS FOLLOWS:
 A) RECONCILE RED LINED ITEMS ON P-1 TO MATCH P-3.
 REVISION IS REQUIRED TO BE IN PLACE PRIOR TO FINAL
 INSPECTION.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By gjohnson Date 2018-02-14 Time 07:21 Rev Time 0.00
Received By gjohnson Date 2018-02-14 Time 07:21 Sent To  
Notes
2018-02-14 08:23:191ST REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. THE DEVELOPED LENGTH TO TH FURTHEST APPLIANCE ON THE
 GAS RISER ADDS UP TO 165' UNDER THE GAS RISER NOTES IT
 IS LISTED AT 150 PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. THE SIZING TABLES ARE LISTED UNDER THE FBC 2014 THE
 CURRENT CODE IS THE FBC FG 2017 PLEASE CORRECT ON PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 6. THE FUTURE POOL HEATER IS MISSING FROM THE GAS LOAD
 CALCULATIONS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 7. THE BBQ GRILLE IS SHOWN AS 100,000 ON THE GAS RISER
 AND IS LISTED AS 75,000 ON THE GAS LOAD CALCULATION
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. THE FUTURE GENERATOR IS SHOWN AS 22,100 ON THE RISER
 AND 221,000 ON THE GAS LOAD CALCULATION PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 9. THE TANKLESS WATER HEATER IS SHOWN AS 199,000 ON THE
 RISER AND 130,000 ON THE GAS LOAD CALCULATION PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 10. THE TOTAL GAS LOAD CALCULATION I CAME UP WITH IS
 1,320,000 THE PLAN SHOWS 826,00 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 11. THE RISER IS SHOWING THE BRANCH TO THE WATER
 HEATER, DRYER AND FIRE PLACE AS UNDERGROUND PE WITCH IS
 NOT ALLOWED UNDER STRUCTURES THE FLOOR PLAN SHOWS ABOVE
 CLG SCH 40 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 12. SHOW THE TRANSITION FROM PE TO SCH 40 ABOVE THE
 GROUND AT THE FIRST BRANCH. PER WPB AMEND TO FBC
 107.2.1
  
 13. THE CONNECTION FOR THE GENERATOR SHALL BE A MIN. OF
 3/4 ON THE .05LB SIDE OF THE REGULATOR. PER FBC FG
 TABLE 402.4(2)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-17 Cont ID  
Sent By pvalenti Date 2019-07-17 Time 17:57 Rev Time 0.00
Received By pvalenti Date 2019-06-21 Time 14:55 Sent To  
Notes
2019-06-24 14:55:18R34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By cpuell Date 2018-12-20 Time 16:11 Rev Time 0.00
Received By cpuell Date 2018-10-17 Time 14:09 Sent To  
Notes
2018-12-08 10:33:4412/8 ROUTED TO ZONING BOX, SENT EMAIL
  
  
2018-10-19 14:10:06R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-21 Cont ID  
Sent By cthroop Date 2018-02-21 Time 10:26 Rev Time 0.00
Received By cthroop Date 2018-01-17 Time 15:40 Sent To I
Notes
2018-01-18 15:41:07R22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-02-21 Cont ID  
Sent By cthroop Date 2018-02-21 Time 10:08 Rev Time 0.00
Received By cthroop Date 2018-02-20 Time 12:24 Sent To  
Notes
2018-12-05 08:24:55MU 2018-1534 FEES PAID $21.91

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-05 Cont ID  
Sent By cmontell Date 2018-11-05 Time 13:21 Rev Time 0.00
Received By cmontell Date 2018-11-05 Time 12:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By cmontell Date 2018-02-15 Time 15:19 Rev Time 0.00
Received By cmontell Date 2018-02-15 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-04 Cont ID  
Sent By jesmith Date 2018-12-04 Time 13:26 Rev Time 0.00
Received By jesmith Date 2018-12-04 Time 13:25 Sent To  
Notes
2018-12-04 13:26:16PLUMBING COMMENTS: APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-14 Cont ID  
Sent By gjohnson Date 2018-02-14 Time 06:58 Rev Time 0.00
Received By gjohnson Date 2018-02-13 Time 16:03 Sent To  
Notes
2018-02-14 07:20:411ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINE BOX IS NOT VENTED. PER FBC RES
 P3101.2.1
  
 2. THE BAR SINK SHALL CONNECT TO THE BRANCH DRAIN OR
 BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP IT CAN
 NOT CONNECT TO THE HORIZONTAL WET DRAIN OF THE BATHROOM
 GROUP. P3108.1
  
 3. THE AAV ON THE BATHROOM #2 SHOWER SHALL BE
 ACCESSIBLE. FBC RES P3114.5 ACCESS AND VENTILATION.
 ACCESS SHALL BE PROVIDED TO AIR ADMITTANCE VALVES. SUCH
 VALVES SHALL BE INSTALLED IN A LOCATION THAT ALLOWS AIR
 TO ENTER THE VALVE.
  
 4. BATHROOM #2 IS LABELED AS LAUNDRY-ON THE ISOMETRIC
 DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. PROVIDE THE SQFT ON THE ROOF DRAINS. PER WPB AMEND
 TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By cthroop Date 2018-12-05 Time 09:46 Rev Time 0.00
Received By cthroop Date 2018-12-05 Time 07:49 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-02-21 Cont ID  
Sent By cthroop Date 2018-02-21 Time 10:08 Rev Time 0.00
Received By cthroop Date 2018-02-21 Time 08:39 Sent To  
Notes
2018-02-21 10:10:13BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017
 FLORIDA BUILDING CODE, 6TH EDITION.
  
 1. ROOFING PERMIT REQUIRED.
 2. ALL SUBMITTALS WILL BE DEFERRED.

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2019-07-10 Time   Rev Time 0.00
Received By pgreilic Date 2019-07-10 Time 12:54 Sent To  
Notes
2019-07-10 12:54:551.) PLEASE NOTE MAX DRIVEWAY WIDTH IS 20 FEET, SEPARATE
 PERMIT REQUIRED
  
 2.) LANDSCAPE PERMIT REQUIRED, PLEASE SUBMIT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-12-20 Time   Rev Time 0.00
Received By pgreilic Date 2018-12-20 Time 10:17 Sent To  
Notes
2018-12-20 10:18:421.) PLEASE NOTE MAX DRIVEWAY WIDTH IS 20 FEET, SEPARATE
 PERMIT REQUIRED
  
 2.) LANDSCAPE PERMIT REQUIRED, PLEASE SUBMIT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By PG Date 2018-02-02 Time 13:24 Rev Time 0.00
Received By pgreilic Date 2018-01-30 Time 16:53 Sent To  
Notes
2018-02-02 13:25:46FAILED
  
 1.) LABEL SETBACKS FOR ALL PROPOSED MECHANICAL
 EQUIPMENT
 2.) SEPARATE PERMITS REQUIRED FOR LANDSCAPING,
 DRIVEWAY, POOL ETC. INDICATE ON PLANS
  
 PAUL GREILICH, SENIOR PLANNER