Plan Review Details - Permit 18010561
Plan Review Stops For Permit 18010561
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-05-03 Cont ID  
Sent By jgomez Date 2018-05-02 Time 19:01 Rev Time 0.00
Received By jgomez Date 2018-05-02 Time 18:44 Sent To  
Notes
2018-05-02 18:46:12BUILDING DATA:
 BUILDING TYPE: III-B
 OCCUPANCY: A-2
 S. F. 2180
 OCC. LOAD: 84
 RESTROOMS: 2

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-04-10 Cont ID  
Sent By jgomez Date 2018-04-10 Time 08:59 Rev Time 0.00
Received By jgomez Date 2018-04-10 Time 08:08 Sent To  
Notes
2018-04-09 17:43:02ASSEMBLY (A2), BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- THE OCCUPANT LOAD CALCULATION ON SHEET 1.5A WAS
 REVISED. NEED TO COMPLY WITH THE MINIMUM 5% SEATING
 SPACES AS REQUIRED BY SEC. 226.1 OF FBC-ACCESSIBILITY
 CODE.
 (NOTE: THIS ISSUE WAS DISCUSSED AND CLARIFIED WITH PETE
 RUSSO ON 04/18/18).
  
 2- NUMBER OF PEOPLE SHOWN IN THE OCCUPANT LOAD
 CALCULATION ON SHEET 1.5A DOESN'T MATCH NUMBER OF
 PEOPLE SHOWN ON LIFE SAFETY NOTE #11 ON SAME SHEET.
 ALSO, IT DOESN'T MATCH NUMBER OF PEOPLE SHOWN ON SHEET
 C-1. REVISE ALL NUMBERS AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- NUMBER OF SEATS SHOWN IN THE OCCUPANT LOAD
 CALCULATION ON SHEET 1.5A DOESN'T MATCH NUMBER OF SEATS
 SHOWN ON SHEET C-1. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- FLOOR PLAN ON SHEET 1.0A IS INCOMPLETE. IT DOESN'T
 SHOW THE FRONT WALL AND REAR WALL. PROVIDE COMPLETE
 DRAWING. SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON' T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 BUILDING DATA:
 BUILDING TYPE: III-B
 OCCUPANCY: A-2
 S. F. 2180
 OCC. LOAD: ?????
 RESTROOMS: 2

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-08 Cont ID  
Sent By jwitmer Date 2018-03-08 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2018-03-08 Time 13:05 Sent To  
Notes
2018-03-08 13:27:01BUILDING DATA:
 BUILDING TYPE: III-B
 OCCUPANCY: A-2
 S. F. 2180
 OCC. LOAD: 59
 RESTROOMS: 2

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-23 Cont ID  
Sent By jwitmer Date 2018-01-23 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2018-01-23 Time 06:28 Sent To  
Notes
2018-01-23 07:34:002017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010561
 ADD: 6901 OKEECHOBEE BLVD. SUITE: B-B1
 CONT: A PLUS CONSTRUCTION
 TEL: 561-267-8255
 E-MAIL: APLUSCONSTRUCTIONLLC.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY JAN. 23/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET C-1 INDICATES THESE PLANS WERE
 CREATED UNDER THE 5TH EDITION OF THE FLORIDA BUILDING
 CODE. PLEASE NOTE THE 2017 EDITION (6 EDITION) OF THE
 FLORIDA BUILDING CODE WAS ADOPTED AND EFFECTIVE
 STATEWIDE ON DEC. 31/ 2017. PLEASE UPDATE THE PLANS AND
 ALL CODE REFERENCES.
  
 2) THE COVERSHEET HAS AN INDEX OF PLANS. WITHIN THE SET
 OF PLANS THERE ARE (2) SHEETS LISTED AS 1.1A OF 13 BUT
 THEY ARE 2 DIFFERENT SETS OF PLANS? DISCREPANCY IN
 PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET 1.0A SHOWS SECTIONS 3-6/ 1.2A WHEN YOU GO TO
 THAT SHEET THEY ARE MISSING. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET 1.5A THE LIFE SAFETY PLAN IS MISSING.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: BUILDING
 7) LIFE SAFETY PLAN
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 5) NONE OF THE SUBMITTED FLOOR PLANS SHOW COMPLIANCE
 WITH: COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE;
 5.1) ACCESS. CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 5.2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 5.3) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 5.3))(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5.3))(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) SHEET 4.1M SHOWS NEW ROOF TOP EQUIPMENT STAND BUT IN
 THIS PLAN REVIEW CYCLE NO PRODUCT APPROVALS WERE
 SUBMITTED. PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS
  
 7) SHEET 4.1M. FOR ROOF TOP A/C STANDS A PRODUCT
 APPROVAL WILL BE REQUIRED (2) , REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT.
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) SHEET 4.1M ALSO SHOWS NEW ROOFTOP CURB AND DOWN
 UNIT. THE DETAIL INDICATES 3X3 ANGLES TO BE WELDED TO
 THE BAR JOIST, NO INFORMATION AS TO THE TYPE OF WELD,
 NOR SIZE OF WELD, OR IF CONTINUOUS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-19 Cont ID  
Sent By jpearson Date 2018-03-19 Time 14:31 Rev Time 0.00
Received By jpearson Date 2018-03-19 Time 12:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-07 Cont ID  
Sent By jpearson Date 2018-02-07 Time 10:42 Rev Time 0.00
Received By jpearson Date 2018-02-07 Time 10:42 Sent To  
Notes
2018-02-07 10:42:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODE ABOVE)
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 5. RISER DIAGRAM SHOWS FOUR #3 AND ONE #8 WIRES IN A 1
 INCH CONDUIT FEEDING PANEL B. THIS NUMBER AND SIZE OF
 WIRES EXCEEDS THE CAPACITY OF A 1 INCH CONDUIT. PROVIDE
 CORRECTION. NEC CHAPTER 9, TABLES 4 AND 5.
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 7. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-05-01 Cont ID  
Sent By scaldero Date 2018-05-01 Time 11:40 Rev Time 0.00
Received By scaldero Date 2018-05-01 Time 11:34 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-04-06 Cont ID  
Sent By scaldero Date 2018-04-06 Time 12:39 Rev Time 0.00
Received By scaldero Date 2018-04-06 Time 12:26 Sent To  
Notes
2018-04-06 12:39:45PERMIT # 18010561
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 PER NFPA 101, CHAPTER 12 -
 12.2.5.9?APPROVAL OF LAYOUTS.
 12.2.5.9.1? WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION, PLANS DRAWN TO SCALE SHOWING THE
 ARRANGEMENT OF FURNISHINGS OR EQUIPMENT SHALL BE
 SUBMITTED TO THE AUTHORITY BY THE BUILDING OWNER,
 MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE
 CONFORMANCE WITH THE PROVISIONS OF 12.2.5.
 12.2.5.9.2? THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY
 ACCEPTABLE ARRANGEMENT, UNLESS ONE OF THE FOLLOWING
 CRITERIA IS MET:
 1. (1) THE PLANS ARE REVISED.
 2. (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED.
 3. (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF
 THE APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT
 LOAD IS NOT INCREASED AND THE INTENT OF 12.2.5.9 IS
 MAINTAINED.
  
 USING THE LAYOUT PROVIDED THE OCCUPANT LOAD IS AS
 FOLLOWS:
 KITCHEN - 8 PERSONS
 QUEING - 18 PERSONS
 TABLES/CHAIRS - 32 PERSONS
 BENCH - 19 PERSONS (KEEPING IN MIND THAT THE NUMBER OF
 TABLES PROVIDED IN THE LAYOUT, ALONG THE BENCH, DO NOT
 PROVIDE FOR 19 BENCH-SEATED PLACE SETTINGS)
 TOTAL OCCUPANT LOAD - 77 PERSONS
  
 IF YOU WOULD LIKE A HIGHER OCCUPANT LOAD, PLEASE SUBMIT
 FOR CONSIDERATION A LAYOUT THAT SHOWS THE ADDITIONAL
 SEATING, AS WOULD BE PERMITTED WHILE MAINTAINING
 COMPLIANCE WITH ALL EGRESS AND SEATING SPACE
 REQUIREMENTS UNDER THE FLORIDA FIRE CODE.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-03-09 Cont ID  
Sent By scaldero Date 2018-03-09 Time 11:14 Rev Time 0.00
Received By scaldero Date 2018-03-09 Time 10:53 Sent To  
Notes
2018-03-09 11:14:15PERMIT # 18010561
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW
 FAIL COMMENT:
  
 1) REPEAT COMMENT - - SHEET 1.5A - OCCUPANT LOAD
 CALCULATION: THERE ARE DISCREPANCIES REGARDING THE
 LISTED OCCUPANCY LOAD CALCULATIONS AND THE DETAILS
 PROVIDED IN THE DRAWING. BASED ON SQUARE FOOTAGE OF
 SEATING AREA (BENCH AND NON-FIXED) THE TOTAL SEATING
 COUNT SHOULD BE 33 PERSONS. PLEASE PROVIDE
 JUSTIFICATION REGARDING DISCREPANCY IN OCCUPANCY LOAD
 CALCULATION FOR NON-FIXED SEATING AND ACTUAL SEATING
 PROVIDED.
 TOTAL OCCUPANT LOAD FOR THIS LOCATION IS 59 PERSONS, AS
 LISTED ON SHEET C-1. HOWEVER, SEATING IS FOR 33
 PERSONS, NOT 40, AS INCORRECTLY LISTED ON SHEET C-1.
  
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By scaldero Date 2018-01-25 Time 11:31 Rev Time 0.00
Received By scaldero Date 2018-01-25 Time 11:14 Sent To  
Notes
2018-01-25 11:31:01PERMIT # 18010561
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) SHEET C-1 SHOWS COMPLIANCE WITH INCORRECT EDITION OF
 NFPA AND FLORIDA FIRE PREVENTION CODE. UPDATE THE CODE
 LIST TO REFERENCE THE 6TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2015 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. ALL WORK
 SHALL COMPLY WITH THE CURRENT EDITION.
  
 2) INDEX LISTS LIFE SAFETY PLAN UNDER SHEET 1.5. SHEET
 1.5A NOT INCLUDED, HOWEVER A SHEET 1.2A WAS LOCATED
 WITH A LIFE SAFETY PLAN DIAGRAM. UPDATE ALL SHEETS SO
 THAT THEY ARE REFLECTED PROPERLY IN THE INDEX AND THE
 ACTUAL DRAWINGS AND DRAWING NOTES.
  
 3) SHEET 1.2A - OCCUPANT LOAD CALCULATION: THERE ARE
 DISCREPANCIES REGARDING THE LISTED OCCUPANCY LOAD
 CALCULATIONS AND THE DETAILS PROVIDED IN THE DRAWING.
 EXAMPLE: DINING IS LISTED AS HAVING AN OCCUPANCY LOAD
 OF 14, HOWEVER SEATING FOR 24 IS SHOWN IN THE DRAWING.
 PLEASE REVIEW AND PROVIDE ACCURATE DETAILS AND
 EXPLANATIONS FOR DATA AND DETAILS PROVIDED.
  
 4) LOCATION OF EMERGENCY LIGHTING AND EXIT SIGNS ON
 SHEET 1.2A, DOES NOT MATCH WHAT IS PROVIDED ON SHEET
 2.1E (LIGHTING PLAN). PLEASE REVIEW AND CORRECT.
  
 5) PLEASE REVIEW AND COMPLY WITH COMMENT PROVIDED UNDER
 BUILDING PLAN REVIEW.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-04-16 Cont ID  
Sent By gjohnson Date 2018-04-16 Time 11:22 Rev Time 0.00
Received By gjohnson Date 2018-04-16 Time 11:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-19 Cont ID  
Sent By lcrespo Date 2018-03-19 Time 18:06 Rev Time 0.00
Received By lcrespo Date 2018-03-19 Time 18:05 Sent To  
Notes
2018-03-19 18:29:3203/19/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE TOTAL BTU IS 883 ON ISOMETRIC, IF YOU ADD UP GAS
 LOAD CALCULATION I COME UP WITH 848 BUT YOUR TOTAL SAYS
 818, WHICH ONE IS THE CORRECT LOAD. PLEASE ADDRESS THIS
 AS IT IS THE SECOND REQUEST FOR CLARIFICATION. PER WPB
 AMEND TO FBC 107.2.1
 2. THERE WAS A REQUEST FOR MANUFACTURES SPECIFICATION
 SHEET FOR ALL GAS EQUIPMENT AND ON YOUR REPLY LETTER,
 IT STATES IT HAS BEEN INCLUDED BUT CANNOT FIND IT AS
 THIS IS A SECOND REQUEST TO DO A REVIEW ON THIS GAS.
 NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 3. THERE ARE 2 NEW CONVENTIONAL OVENS AT 70 BTU ADDED
 TO THE NEW SUBMITTED PLAN WE WILL ALSO NEED
 SPECIFICATIONS FOR IT. PER WPB AMEND TO FBC 107.2.1
 4. 15. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. PROVIDE DOCUMENTATION FROM THE
 MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. 2017 FBC FUEL GAS SEC.410.1.
 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37).
 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS SEC. 402.2 AND 301.3
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-12 Cont ID  
Sent By gjohnson Date 2018-02-12 Time 14:08 Rev Time 0.00
Received By gjohnson Date 2018-02-12 Time 14:08 Sent To  
Notes
2018-02-12 14:08:581ST REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. THE BTU LOAD ON THE APPLIANCES DO NOT ADD UP OR
 MATCH THE TOTAL BTU LOADS ON THE RISER PIPING PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SOME OF THE LABELING ON THE RISER IS SHOWN AS
 EXISTING OTHER SECTIONS ARE NOT PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. ONE OF THE LABELS ON THE RISER NEXT TO THE EMERGENCY
 SHUT OFF LIST 21' @3/4(75K) BUT NO PIPING IS SHOWN
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. THE WATER HEATER IS SHOWN ON THE RISER WITH 180K BTU
 BUT ON THE GAS CALCULATIONS-IT IS SHOWN AS 75K PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. 2 STOCK POTS ARE SHOWN ON THE RISER BUT 3 ARE LISTED
 ON THE GAS CALC PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 6. THE TOTAL BTU LOAD ON THE GAS CALC IS 713 ON THE
 RISER IT ADDS UP TO 743 PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 7. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-03 Cont ID  
Sent By jgomez Date 2018-05-02 Time 19:01 Rev Time 0.00
Received By jgomez Date 2018-04-23 Time 13:23 Sent To I
Notes
2018-05-01 17:45:335/1 TO JG DESK
  
2018-04-24 13:23:40RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-16 Cont ID  
Sent By gjohnson Date 2018-04-16 Time 11:22 Rev Time 0.00
Received By gjohnson Date 2018-04-03 Time 12:57 Sent To  
Notes
2018-04-04 12:58:08B13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-19 Cont ID  
Sent By lcrespo Date 2018-03-19 Time 18:06 Rev Time 0.00
Received By lcrespo Date 2018-03-02 Time 10:17 Sent To  
Notes
2018-03-06 10:17:16B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-12 Cont ID  
Sent By gjohnson Date 2018-02-12 Time 14:38 Rev Time 0.00
Received By gjohnson Date 2018-01-17 Time 15:33 Sent To  
Notes
2018-01-18 15:34:07B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-01-23 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2018-01-23 Time 06:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-04-13 Cont ID  
Sent By ccole Date 2018-04-13 Time 15:38 Rev Time 0.00
Received By ccole Date 2018-04-13 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-13 Cont ID  
Sent By ccole Date 2018-03-13 Time 14:41 Rev Time 0.00
Received By ccole Date 2018-03-13 Time 14:40 Sent To  
Notes
2018-03-13 14:49:572ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18010561
 3/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.0M: THE REVISED PLAN IS INDICATING
 RECIRCULATION OF AIR FROM THE KITCHEN INTO THE DINING
 ROOM AND COUNTER AREA WHICH IS PROHIBITED PER FOOTNOTE
 B, TABLE 403.1.1.
  
 2) 4.0M: INDICATE HOW THE 246 CFMS OF COMBUSTION FOR
 THE APPLIANCES AIR WAS CALCULATED, AND HOW THE AIR IS
 BEING PROVIDED- SECTION 304 FBC-14 FBC-17 FUEL GAS.
  
 3) ADVISORY:CONCERNING THE FUTURE KITCHEN HOOD EXHAUST
 SYSTEM, PLEASE REVIEW SECTION C403.2.8 FBC-17 ENERGY
 CONSERVATION AS IT MAY IMPACT THE HVAC SYSTEMS.
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS.
  
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
  
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
  
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
  
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
  
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
  
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
  
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
  
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By ccole Date 2018-01-30 Time 08:56 Rev Time 0.00
Received By ccole Date 2018-01-30 Time 07:29 Sent To  
Notes
2018-01-30 09:34:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010561
 1/30/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 4.0M & 4.1M: PLEASE CORRECT THE NOTE ON SHEET
 4.1M THAT STATES " (2) EXISTING 10-TON PACKAGED UNITS
 SHALL BE REPLACED WITH NEW HIGH EFFICIENCY UNITS (1)
 5-TON & (1) 7.5-TON". THERE IS NO NEW 7.5 TON SYSTEM
 SHOWN ON THE PLAN OR IN THE SCHEDULE.
  
 2) 4.1M: VERIFY THE THE ROOF STAND INSTALLATION DESIGN
 WILL WITHSTAND 170 MPH WIND SPEED AND ASSOCIATED
 LATERAL AND UPLIFT PRESSURES. THE PLAN DESIGN IS
 INDICATING 140 MPH.
  
 3) THE MECHANICAL PLANS FOR THE RESTAURANT SHALL BE IN
 COMPLIANCE WITH SECTION 508.1.2 AIR BALANCE:
  
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION.
  
 4) SUBMIT TWO COPIES OF THE NOA FOR THE RMS AC ROOF
 STAND.
  
 5) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 HOODS, FIRE SUPRESSION SYSTEMS, AND WALK IN COOLERS AND
 FREEZERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-04-16 Cont ID  
Sent By gjohnson Date 2018-04-16 Time 11:22 Rev Time 0.00
Received By gjohnson Date 2018-04-16 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-03-19 Cont ID  
Sent By lcrespo Date 2018-03-19 Time 18:06 Rev Time 0.00
Received By lcrespo Date 2018-03-19 Time 18:05 Sent To  
Notes
2018-03-19 18:41:4503/19/2018 **2ND PLUMBING REVIEW DENIED **
  
 1. PLEASE SHOW INFORMATION TYPE OF TEMPERING DEVICE
 THAT CONFORMS TO ASSE 1070 ON DRAWING DETAILS ON PAGE
 3.0P FBC P 607.1.2 TEMPERED WATER TEMPERATURE CONTROL.
 2. THE THREE COMPARTMENT SINK IS SHOWN ON THE ISOMETRIC
 BUT THE SECOND-FLOOR SINK DOES NOT REFLECT THE FLAT
 DRAWING ON PAGE 3.0P WPB AMEND TO FBC 107.2.1
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-12 Cont ID  
Sent By gjohnson Date 2018-02-12 Time 11:49 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 16:14 Sent To  
Notes
2018-02-12 12:35:221ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE CALCULATIONS FOR THE EXISTING GREASE
 INTERCEPTOR WITH EXISTING LOAD AND THE NEW LOAD. PER
 WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE NOTE ON PLAN A SEPARATE PERMIT REQUIRED FOR
 BACKFLOW. PER WPB UTILITIES DEPT.
  
 3. THE NEW BACK FLOW SHALL BE INSTALLED NEXT TO METER.
 PER WPB CROSS CONNECTION MANUAL
  
 4. SHT. 3.0P PLUMBING NOTE #1 THE CURRENT CODE SHALL BE
 2017 6TH EDITION FBC
  
 5. BOTH OF THE PLUMBING SHEETS ARE LABELED 3.0P PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 6. THE SANITARY ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 IT SHOWS THE 2 AND 3 COMPARTMENT SINKS DRAINING
 TOGETHER INTO THE SAME FLOOR SINK THE FLOOR PLAN SHOW
 THEM ACROSS THE KITCHEN DRAINING INTO TWO SEPARATE
 FLOOR SINKS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 7. THE WATER ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 THE ISO SHOWS A 50 GAL WATER HEATER THE FLOOR PLAN
 SHOWS A TANKLESS AND THE 3 COMPARTMENT SINK IS MISSING
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. SHOW ON THE WATER ISOMETRIC, VALVES ON ALL THE DROPS
 AND AIR HAMMER ARRESTORS PER FBC PL 604.9 , 606.1 (5)
  
 9. SHOW TRAP PRIMER ON FLOOR DRAINS. PER FBC PL
 1002.4.1
  
 10. PLACE NOTE ON THE PLAN TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. PER FBC PL 416.5
  
 11. THE EXISTING GREASE INTERCEPTOR IS SHOWN AS 1000
 GAL ON FIRST PLUMB PAGE AND AS 1150 ON THE SANITARY
 ISOMETRIC DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  