Plan Review Details - Permit 18010557
Plan Review Stops For Permit 18010557
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-25 Cont ID  
Sent By lcrespo Date 2018-01-25 Time 12:49 Rev Time 0.00
Received By lcrespo Date 2018-01-24 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-17 Cont ID  
Sent By lcrespo Date 2018-01-17 Time 15:44 Rev Time 0.00
Received By lcrespo Date 2018-01-17 Time 15:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-01-25 Cont ID  
Sent By gjohnson Date 2018-01-25 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2018-01-25 Time 09:43 Sent To  
Notes
2018-01-25 09:46:52 
 PLUMBING COMMENTS:
  
 1. BACK FLOW SHALL BE LOCATED NEXT TO METER, PROVIDE
 DRAWING TO INDICATE. PER WPB UTILITIES CROSS CONNECTION
 CONTROL MANUAL
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-25 Cont ID  
Sent By lcrespo Date 2018-01-25 Time 12:49 Rev Time 0.00
Received By lcrespo Date 2018-01-24 Time 16:58 Sent To  
Notes
2018-01-25 13:53:461/25/18 APPROVED BY UTILITIES, PUT IN PROCESSING, LAC
2018-01-24 16:58:161/24/18 APPROVED BY PLUMBING AND SENT TO UTILITIES FOR
 REVIEW, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By lcrespo Date 2018-01-17 Time 15:44 Rev Time 0.00
Received By lcrespo Date 2018-01-24 Time 16:57 Sent To  
Notes
2018-01-25 13:51:04DENIED
  
 YOUR DEVICE DOES NOT MEET THE CROSS CONNECTION STANDS
 SET BY WPB.
  
 ALL BACKFLOW DEVICES MUST BE LEAD FREE. LEAD FREE (LF)
 SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED ON
 THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
  
 CERTIFICATION REQUIREMENTS: ALL INDIVIDUALS OR
 COMPANIES DESIRING TO: INSTALL, TEST, REPAIR, OVERHAUL,
 OR MAINTAIN BACKFLOW PREVENTION ASSEMBLIES WITHIN THE
 CITY OF WEST PALM BEACH UTILITIES SERVICE AREA, MUST
 SUBMIT THE FOLLOWING CURRENT DOCUMENTS TO THE
 DEPARTMENT OF PUBLIC UTILITIES IN ORDER TO BE A CITY
 CERTIFIED BACKFLOW PREVENTER TESTER/REPAIRER:
  
  
 PLEASE PROVIDE PLUMBING CONTRACTOR INFORMATION ON
 RE-SUBMITTAL
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW