Plan Review Details - Permit 18010554
Plan Review Stops For Permit 18010554
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-06-01 Cont ID  
Sent By thunt Date 2018-06-01 Time 17:21 Rev Time 0.00
Received By thunt Date 2018-06-01 Time 17:21 Sent To  
Notes
2018-06-01 17:22:14SUB GAS PERMIT REQUIRED

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-05-22 Cont ID  
Sent By thunt Date 2018-05-22 Time 06:56 Rev Time 0.00
Received By thunt Date 2018-05-22 Time 06:56 Sent To  
Notes
2018-05-22 07:07:4805/22/2018 3RD GAS REVIEW**DENIED**
  
 CONTRACTOR IS TO COME IN FOR A 1 ON 1 REVIEW BEFORE ANY
 RESUMITTAL.
  
 COMMENTS FROM LAST REVIEW:
  
 1) ANSWERED
  
 2) ANSWERED
  
 3) ANSWERED
  
 4) YOU STILL HAVE NOT PROVIDE ANY INFORMATION OR BTU
 LOAD ON THE EXISTING GAS SYSTEM THAT MUST BE INCLUDED
 FOR THIS REVIEW. 2017 FBC-RES G2413.
  
 5) ANSWERED
  
 6) ANSWERED
  
 7) SIZING CHART PROVIDE ARE DATED FROM THE 2014 CODE.
 AS OF DEC, 31,2017 WE ARE USING THE 2017 6TH ED. FUEL
 AND GAS. ALSO YOUR INLET PRESSURE AND PRESSURE DROP
 STILL LEAVES YOU AT HIGH PRESSURE ( ABOVE 12" WC) AND
 WILL REQUIRED A GAS REGULATOR. PLEASE PROVIDE CORRECTED
 SIZING CHART AND LIST GAS OUTLET METER PRESSURE AND
 PRESSURE @ TANKLESS. REFER TO TABLES FBC-RES SEC
 G24512.4, G2412.8, G2413.1, G2413.2, G2413.3. PROVIDE
 GAS REGULATOR INFORMATION AS WHILE.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-02-21 Cont ID  
Sent By thunt Date 2018-02-21 Time 16:59 Rev Time 0.00
Received By thunt Date 2018-02-21 Time 16:59 Sent To  
Notes
2018-02-21 17:04:0302/21/2018 PLUMBING & GAS 2NG REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 ********************************PLAN CAN NOT BE DRAWN
 IN PENCIL FBC 107.3.1
  
 NONE OF MY COMMENTS FROM THE 1ST REVIEW HAVE BEEN
 ADDRESSED
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3) TYPE OF GAS (LP OR NATURAL).
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By thunt Date 2018-01-22 Time 05:54 Rev Time 0.00
Received By thunt Date 2018-01-22 Time 05:54 Sent To  
Notes
2018-01-22 05:54:3501/22/2018 PLUMBING & GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3) TYPE OF GAS (LP OR NATURAL).
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-01 Cont ID  
Sent By thunt Date 2018-06-01 Time 17:22 Rev Time 0.00
Received By thunt Date 2018-05-29 Time 15:34 Sent To I
Notes
2018-05-30 15:34:16RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-22 Cont ID  
Sent By thunt Date 2018-05-22 Time 07:08 Rev Time 0.00
Received By thunt Date 2018-05-17 Time 14:12 Sent To  
Notes
2018-05-18 14:12:27RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-21 Cont ID  
Sent By thunt Date 2018-02-21 Time 17:04 Rev Time 0.00
Received By thunt Date 2018-02-09 Time 14:00 Sent To  
Notes
2018-02-12 14:00:13RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By thunt Date 2018-01-22 Time 05:54 Rev Time 0.00
Received By thunt Date 2018-01-17 Time 08:24 Sent To I
Notes
2018-01-19 08:24:39PLUMB <5K

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-06-01 Cont ID  
Sent By thunt Date 2018-06-01 Time 17:22 Rev Time 0.00
Received By thunt Date 2018-06-01 Time 17:22 Sent To  
Notes
2018-06-01 17:22:50SUB GAS AND ELECTRICAL PERMITS REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-05-22 Cont ID  
Sent By thunt Date 2018-05-22 Time 07:08 Rev Time 0.00
Received By thunt Date 2018-05-22 Time 07:08 Sent To I
Notes
2018-05-22 07:08:2305/22/2018 3RD GAS REVIEW**DENIED**
  
 CONTRACTOR IS TO COME IN FOR A 1 ON 1 REVIEW BEFORE ANY
 RESUMITTAL.
  
 COMMENTS FROM LAST REVIEW:
  
 1) ANSWERED
  
 2) ANSWERED
  
 3) ANSWERED
  
 4) YOU STILL HAVE NOT PROVIDE ANY INFORMATION OR BTU
 LOAD ON THE EXISTING GAS SYSTEM THAT MUST BE INCLUDED
 FOR THIS REVIEW. 2017 FBC-RES G2413.
  
 5) ANSWERED
  
 6) ANSWERED
  
 7) SIZING CHART PROVIDE ARE DATED FROM THE 2014 CODE.
 AS OF DEC, 31,2017 WE ARE USING THE 2017 6TH ED. FUEL
 AND GAS. ALSO YOUR INLET PRESSURE AND PRESSURE DROP
 STILL LEAVES YOU AT HIGH PRESSURE ( ABOVE 12" WC) AND
 WILL REQUIRED A GAS REGULATOR. PLEASE PROVIDE CORRECTED
 SIZING CHART AND LIST GAS OUTLET METER PRESSURE AND
 PRESSURE @ TANKLESS. REFER TO TABLES FBC-RES SEC
 G24512.4, G2412.8, G2413.1, G2413.2, G2413.3. PROVIDE
 GAS REGULATOR INFORMATION AS WHILE.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-02-21 Cont ID  
Sent By thunt Date 2018-02-21 Time 17:04 Rev Time 0.00
Received By thunt Date 2018-02-21 Time 17:04 Sent To  
Notes
2018-02-21 17:04:2202/21/2018 PLUMBING & GAS 2NG REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 ********************************PLAN CAN NOT BE DRAWN
 IN PENCIL FBC 107.3.1
  
 NONE OF MY COMMENTS FROM THE 1ST REVIEW HAVE BEEN
 ADDRESSED
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3) TYPE OF GAS (LP OR NATURAL).
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By thunt Date 2018-01-22 Time 05:46 Rev Time 0.00
Received By thunt Date 2018-01-22 Time 05:46 Sent To  
Notes
2018-01-22 05:54:0001/22/2018 PLUMBING & GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3) TYPE OF GAS (LP OR NATURAL).
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  